ABSTRACT OF COST
NAME OF WORK:- Aug. of LWSS Sanjwan Malal Rajgir in Tehsil Indora Distt.Kangra HP.
SUB HEAD:- S/E of Centrifugal pumping machinery with allied accessories for stage 2nd.
DESCRIPTION
Supply of horizontal spindle,horizontal/radial split casing and suction (backpull out arrangement) single/
double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/
Jyoti /Kirloskar /BE /Maxflow /Beaconweir make conforming to BIS: 1520-1980 (latestwith upto date
ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned
charactristics with impellers of bronze/suitable alloy, priming funnels,casing ring & shaft sleeves of bron
suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling
on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping set
to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar / NGEF /
Crompton / Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read read with BIS: 900-1968
(latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. and
shall be suitable for operation as per data given below.
Location of site The Site is located at a distance of __.01__ KMs from
_____ Railway station by road and _18__ KM by head load
The altitude of place in which Altitude of place is 450__ m above MSL
pumping set is intended to work
Type of current AC three phase with frequency of 50cycles/second
Rated Voltage 415V ± 10%
Type of water (Raw/Treated) Clear cold and freash water_______
Charactrstics of water a) Temperature _20 °C e) Total solids __ mg/litre
b) Turbidity _50_ NTU f) Others ____
c) pH _7.5___
d) Hardness __ Mg/Litre(as CaCO3)
Depth of Tank/ T.well 3.00 mts.
L.W.L in Tank/sump well 320.15 M.
Centre line Level of Pump 320.10 M.
Suction head Positive
Discharge Level of highest point 353.20 M.
Nos of pumps reqd. 2 Nos. pumps (One to act as standbye)
Capacity 6.42 lps for each pump
Static Head in meters 33.10 mts.
Total head in Mts. 78.32 mts
Length of R/Main 900 mts
Dia of R/Main 80 mm
Pumping hours per day 8 hours
Limits of pump operation (-) 25% to (+) 10% of Total head at duty point
HP of motor /Drive unit Required BHP of pump at (+) 10% & (-) 25% of total head or BHP
with following margins/multiplying factor at duty point, whichever is highe
a) Upto 2 HP = 1.5 d) 10 to 20 HP = 1.2
b) 2 to 5 HP = 1.4 e) 20 to100 HP = 1.15
c) 5 to 10 HP = 1.3 f) Above 100 HP=1.10
R.P.M.of Pump (2900/1450rpm) _2900___r.p.m.
Test Run 16 hours continueously for 7 days
NPSH available positive
Supply of suitable oil immersed star delta starter of standard make such as MEI/
Kilburn/Jyoti/L&T/S&S conforming to BIS:8544-1979 latest with up to date ammendments for squirrel cage
motor (make to be specified by the tenderers) mounted on panel board with magnetic type over load
release & dashpot,time lag,under voltage release with initial oil filling .
Note:- Star delta starter upto 37.5 KW, Auto Transformer Stareter between 37.5 KW to 75 KW and Stator Rotor Starter with slippering motor.
Providing M S sheet 16 SWG steel fabricated floor mounted closed almirah type switch board
including angale iron post of suitable height and size ISA 65x65x6mm duly painted comprising and
capable of mounting the following accessaries with all internal electric connections.
Note:- The drawing of panel board shall be subject to approval of Engineer in charge.
Ammeter AC supply,100 mm circular/square dial Auto electric/AE/IMP/Havells make of suitable range for
above motor with selector switches conforming to BIS: 1248-1983 latest with up to date ammendments.
Voltmeter AC supply,100 mm circular/square dial Auto electric/AE/IMP/Havells make of suitable range for
above motor with selector switches conforming to BIS: 8044-1978 with up to date ammendments.
ICTP switches with HRC fuses Kilburn/L&T/Standard/Siemen's/Havell's make and having capacity 30%
extra of the operational rating of motor as per BIS: 4064-1978 with upto date ammendments immediatly
after the power meter of HPSEB.
Busbar chamber having 3 copper bars of suitable rating for full length of 3 live phases and one copper bar
of half rating of full length for neutral conforming to BIS: 8084-1976 and BIS;11353-1985 read with
BIS;5578-1985 all latest with upto date ammendments.
MCB/OCB of suitable capacity of Kilburn/L&T/MEI/Standard/GEC make on in comming
feeder for motors offered by the tenderer conforming to BIS: 2516-1985 latest with upto date
ammendments with neutral linked under voltage release.
Three phase indicating lamps complete with toggle switches for individual motors conforming to BIS: 3452
( part I & II) latest with up to date ammendments.
Earth leakage circuit breaker (ELCB) of Standard/ Havell's make as per BIS: 2516-1977 with upto date
ammendments and of suitaible range with which should have control box, operating handel and trip/reset
bush button, on/ off indicators, re-indicating off spring condition of the circuit breaker for over current
protection. The circuit should be equipped with magnetic thermal release with metallic tape CTs.It should
also be fitted with earth fault for tripping of breaker on occurance of earth fault on/off breaker load side.
Hour run meter of approved make of four digit capacity conforming to BIS: 722 (latest edition)
Change over Switch of reputed make & suitable capacity conforming to relevant BIS code
Single phase preventor of reputed make & suitable capacity conforming to relevant BIS code
Providing C.I. double flanged sluice valve of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/
Leader make of size___mm & class_PN-1_ having one size higher to delivery size of pump and capable of
with standing nominal seat pressure of __10_ kg/cm^2 ( Valve size to be specified by the tenderer)
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader make C.I.double flanged
swing check type reflux valve having bye pass arrangement and one size higher to delivery size of pump
( size___mm & class _PN-1_ ) and shall be suitable for withstanding nominal seat pressure of __10__ kg/cm^2
( Valve size to be specified by the tenderer)
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader make Cast Iron double flanged
swing check type reflux valve having bye pass arrangement and of size equal to dia of Rising main
i.e 80 mm & of class PN 1.0 and shall be suitable for withstanding nominal seat pressure of 10 kg/cm^2
NOTE:- The C.I. reflux valve shall conform to BIS: 5312-1984- Part-I ( latest edition). However if the seat pressure exceeds the
limits prescribed in BIS 5312 then it shall be of cast steel conforming to class ASA-150 for seat pressure upto 21 Kg/cm² or
class ASA-300 for seat pressure 52 Kg/cm² as per BS 1868 (API 600) .
Supply of Kirloskar/Jyoti/Standard/KilburnKartar make cast iron double flanged sluice valve or foot valve on
suction side of pump having size one step higher than the suction size of pump (Valve size to be specified by the ten
NOTE:-TheC.I. sluice valve shall conform to BIS: 780-1984 & the foot valve shall conform to BIS 4838-1986 (latest edition) .
Providing & laying PVC insulated armoured power copper cable of Siemens/Finolex/Grandlay/
Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable
size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment
/accessories such as thimbles,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or
trenches under floor .The type,size & make will be subject to approval of HPSEB authorities.In case
of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
a) On supply side of 3½ core( From HPSEB Meter to Switch &Starter) = 10mts of Size _____ mm².
b) On motor side 3 core ( From Switch & Starter to Motor) = 20 mts. of Size _____ mm².
Providing & laying double loop earthing with copper plate 600x600x3mm thick electrode complete with material
such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & copper strips of suitable
size conforming to BIS:3043-1978 (latest edition) for above motors & other electrical equipments.
NOTE:-The strip size shall be 20x3 upto 18.5 KW, 25x3 for 18.5 to 37 KW, 25x5 for 37 to 55 KW & 32x5 beyond 55 KW.
Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986
latest with upto date ammendments of BHEL/GEC/Machneil/ Mager/Bajaj make to raise the prevailing
power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR
according to HP of motor offered including cable of Siemens/Gloster/ICC make from busbar chamber
chamber to capacitor & also including ICTP switches Kilburn/L&T/Standard/Siemen's/Havell's of conforming to
4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.)
Supply of 100mm dia circular/square dial pressure gaugeof suitable rangeof Fiebeg/Bourden/ Precision/PREGA
make with all accessories such as stop cock,copper tubing etc. conforming to BIS:3624-1987 latest
with up to date ammendments.
Supply of 100mm dia circular/square dial vacuum gauge of suitable range of Fiebeg//Bourden/ Precision/PREGA
make with all accessories such as stop cock,copper tubing etc. conforming to BIS: 3624-1987 latest
with up to date ammendments.
Prov. & laying MSERW/GI pipes conforming to BIS; 1978-82/ BIS;1239-1990 of suitable size for suction,delivery a
header considering site requirements & NPSH required / available.The pipe sizes for suction & delivery shall as
per the requirement of offered pump and common header shall be equal to dia of R/main including cost of tapers,
flanges (conforming to relevant table of BIS:6392-1971), bends, rubber gaskets,3mm thick nuts & bolts and
specials up to 5 mtrs.away from the outer wall of pump house as per layout drawing approved by Engineer-in-
Charg. Pipe & material shall be capable of withstanding field test pressure equal to 1.5 times the operating pressure
The complete arrangement shall comprise of ; a) Suction pipe _____mm dia __ mm thick ( to be mentioned by tenedere
b) Delivery pipe _____mm dia __mm thick ( -----do--- )
c) Common header 80_mm dia 4.80mm thick
Errection of all equipments from S.No. 1 to 4, & 6 i/c cost of tees,bends tapers & any other fittings
required as per site conditions & as per directions of Engineer-in-Charge
TOTAL AMOUNT
b) Motor
ble coupling
c) Coupling
d) Base plate
ng etc. and
s __ mg/litre
otal head or BHP
nt, whichever is higher
2 Nos Each
or squirrel cage
2 Nos. Each
2 No. Each
1 No. Each
Ts.It should
2 Nos. Each
1 No. Each
1 No. Each
2 Nos. Each
and capable of
2 Nos. Each
__10__ kg/cm^2
1 Nos. Each
equipment
beyond 55 KW.
2 Nos. Each
s of conforming to
135000.00
the make as