Professional Documents
Culture Documents
Refrigeration PCM
Refrigeration PCM
Refrigeration PCM
Energy Reports
journal homepage: www.elsevier.com/locate/egyr
Research paper
article info a b s t r a c t
Article history: In this survey, the integration of a vapor compression cycle with a phase change material (PCM) storage
Received 9 February 2023 tank has been evaluated experimentally during the hottest days of five cities with different weather
Received in revised form 22 March 2023 conditions: Tehran, Ramsar Hamedan, Bushehr, and Ahvaz. The temperature conditions for outdoor
Accepted 16 July 2023
(condenser, compressor, etc.) and indoor (evaporator) air conditioning units are provided with the help
Available online xxxx
of two separated test chambers and a controller system. The desired system has been examined based
Keywords: on two scenarios. In each scenario, the system is assessed for the conventional air conditioning (AC)
PCM system (with no PCM involved) and the AC plus PCM unit. Based on scenario 1 operating strategy, the
Peak shaving results indicate that adding the PCM tank decreases the total daily COP compared to the conventional
Vapor compression cycle AC unit, which varies from 32.07% for Bushehr city to 17.23% for Tehran city. Whereas the AC plus PCM
system’s performance enhances during on-peak hours compared to the conventional AC system, which
varies from 65.99% for Hamedan city to 12.84% for Bushehr city. Based on scenario 2 operating strategy,
adding the PCM storage tank to the conventional AC unit increases total electric energy consumption
over 24 h, which varies from 29.35% for Bushehr city to 5.49% for Tehran city. While it leads to shaving
the electric peak load from 45.11% to 67.02% in which the highest peak load shaving belongs to Tehran
and the least is related to Bushehr city.
© 2023 The Author(s). Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND
license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
1. Introduction system stores cooling energy during off-peak hours and uses it
at on-peak hours (Wijesuriya and Tabares-Velasco, 2020). This
Nowadays, boosts in the world’s population and increasing benefits both consumers and the government. Consumers pay less
living standards have led to rising energy consumption (Mir- electricity price because the electricity tariff is higher at on-peak
javadi et al., 2022; Pourmoghadam et al., 2021). Based on the hours and lower at off-peak hours. Moreover, the government
IEA report, buildings, both commercial and residential, account no longer needs to construct a new power plant to supply elec-
for about 30% of energy use. They are also responsible for 55% of tricity demands at on-peak times and prevents blackout (Packer
the world’s electricity consumption, where 8.5% of which belong and Glicksman, 1979; Aponte and McConky, 2022). Owing to
to space cooling. There are currently 2 billion air conditioner this Chaichana et al. (2001) claimed that the electricity cost of a
units in operation worldwide, which is predicted to get to 3.3 building in Thailand, which used an ice storage tank, was reduced
billion by 2030 given to the rising average temperature of the up to 55% per month. Yau and Lee (2010) indicated that although
the use of an ice-slurry increased the total energy consumption
earth (IEA, 2021; Said and Hassan, 2021). The buildings are also
up to 20%, it diminishes the total cost by about 24%. Mazzoni
responsible for 40% of direct and indirect global CO2 emissions
et al. (2021) concluded that using latent thermal energy units
which a remarkable part of it is related to providing cooling
can significantly improve the efficiency of district cooling systems
energy (Zeinelabdein et al., 2020). Consequently, supplying this
and reduce their operating costs. However, the feasibility of such
amount of energy, especially on hot days of the year and during
systems depends on several factors such as the cost of energy,
on-peak hours, is one of the significant challenges ahead. One
the size of the system, and the availability of suitable storage
of the solutions to manage the proposed issue is to shave the
materials. It was found that the net present value of this system
peak during on-peak hours and shift it to off-peak hours (Erdemir was about 200,000 $ after 20 years.
et al., 2021; Imafidon and Ting, 2022). In this regard, the cooling Thermal energy storage (TES) systems are divided into three
categories in terms of their operation, which are sensible, latent,
∗ Corresponding author. and thermochemical (Afsharpanah et al., 2022). The sensible TES
E-mail address: behshad@sharif.edu (M.B. Shafii). units are uncomplicated and cheapest among the proposed TES
https://doi.org/10.1016/j.egyr.2023.07.031
2352-4847/© 2023 The Author(s). Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-
nc-nd/4.0/).
A. Riahi, H.J. Mosleh and M.B. Shafii Energy Reports 10 (2023) 850–863
Table 1
The summary of previous studies.
Ref Type of cooling Type of storage system Experimental work Time of evaluation Effect of charging &
system discharging process
Chaichana et al. (2001) AC unit Ice storage No 1 Day No
Yau and Lee (2010) Chiller Ice storage No 1 Year No
separated test chambers designed to provide a realistic imitation to the lab, outdoor test chamber, and setpoint temperatures,
of weather conditions with high accuracy. The system evalua- the controller switches ON/OFF the electrical heaters and the
tion has been performed by simulating the weather conditions conventional 30 000 BTU AC unit to provide a realistic imitation of
of five different cities, which determines the effect of ambient the air temperature inside the outdoor test chamber (simulated
weather conditions on the performance of the condenser and, ambient temperature) according to the given temperature data
consequently, the performance of the vapor compression refrig- of the desired city. According to Fig. 2, the air is sucked into
eration system. In this work, a PCM TES, which uses water as the outdoor unit test chamber by an adjustable air fan, which its
its medium, integrated into the conventional vapor compression rotation speed is equal to the AC condenser’s speed fan. When
system (conventional AC) with minor changes in its pipelines. The the setpoint temperature of the outdoor test chamber, according
stored cooling energy in the PCM TES transfers to the indoor unit to the ambient temperature of the desired city understudy, has to
section with a circulating water pump. To the best of the authors’ be higher than the lab temperature, the sucked air will be heated
knowledge, no works have ever evaluated the performance of the up by the electrical heaters through a channel and then enters
compression cooling system combined with PCM TES like this. So, the outdoor test chamber. When the setpoint temperature of
this experimental work is novel and has been done for the first the outdoor test chamber, according to the ambient temperature
time. of the desired city understudy, has to be lower than the lab
temperature, the sucked air first will be cooled by the 30 000 BTU
2. Experimental setup AC unit and then is reached the desired temperature by the elec-
trical heaters. In fact, the PLC turns ON/OFF the electrical heaters
The whole setup consists of a conventional 12 000 BTU air and 30 000 BTU AC unit based on the received temperatures by
conditioning unit, electrical heaters, two air fans, a conventional the thermometers. The experimental setup of the outdoor test
30 000 BTU air conditioning unit (AC), a PCM thermal storage chamber with equipment used in it is indicated in Fig. 2. It
tank, a programmable logic controller (PLC), a circulating water should be noted that, since the only way for air stream to enter
pump, a water heat exchanger, and two test chambers, which the outdoor test chamber is through the adjustable air fan, the
its diagram is illustrated in Fig. 1. The aim of the test chambers amount of air stream is sucked by the adjustable air fan must
is to provide a realistic imitation of real indoor (building) and be the same as the amount of air sucked in by the condenser’s
outdoor (ambient) temperature conditions for the 12 000 BTU AC fan of the AC unit at normal operating condition. Otherwise, a
indoor and outdoor units, respectively. The electrical heaters and low or high amount of the adjustable fan load will affect the
a 30 000 BTU AC unit have been used to achieve the proposed performance of the AC unit condenser. So, an airflow meter has
purpose. Moreover, a control system is used to adjust the desired been used to adjust the outdoor test chamber fan speed. Also, the
temperature with high accuracy. amount of compressor and pump electric power consumptions of
the AC unit is measured through a wattmeter, which is located
2.1. Outdoor test chambers in the controller system. Then, these data are recorded by the
supervisory control and data acquisition (SCADA), which is an
Two separate test chambers have been constructed to simulate industrial software that connects the controller system to the
the ambient air (outdoor) and indoor (building) temperatures for computer.
the outdoor and indoor units of the AC system. The dimensions of
each of these test chambers are 4 m3 (2 × 2×1). The outdoor test 2.2. Indoor test chamber
chamber temperature is adjusted by the six electrical heaters, a
30 000 BTU AC unit, and an air fan. Its controller system, which is The indoor test chamber comprises two heat exchangers, elec-
equipped with four thermometers, adjusts the setpoint tempera- trical heaters, and an air fan. The aim of the indoor test chamber
ture of the outdoor test chamber. Three of the thermometers are is to simulate the temperature condition inside the building. The
implemented in the various spots inside the outdoor test cham- electrical heaters play the role of the heat gain of the building
ber, and one of them is located in the lab environment. According in the summer (required cooling load of the building). Two heat
852
A. Riahi, H.J. Mosleh and M.B. Shafii Energy Reports 10 (2023) 850–863
Fig. 2. The experimental setup of the outdoor test chamber with its equipment.
exchangers have been used to provide the building cooling loads removed from the indoor test chamber to maintain the tempera-
demand (the amount of heat energy that would need to be ture in an acceptable range, which is between 23–25 degrees).
853
A. Riahi, H.J. Mosleh and M.B. Shafii Energy Reports 10 (2023) 850–863
Fig. 3. The experimental setup of the indoor test chamber with its equipment.
cools the water used as PCM. In the cold energy discharging mode
of the PCM, the circulating water enters the aluminum pipe and
is cooled by the PCM. Then it goes to the indoor water heat
exchanger by a circulating water pump.
cycle, and the other one uses circulating cold water, which is Table 2
integrated to the PCM TES by a circulating water pump. The The specifications of the main equipment used in this study.
schematic of the cold energy discharging process is depicted in Equipment Description
Fig. 6c. The cooling load demand of the indoor test chamber AC cooling unit 12 000 BTU rated cooling capacity
(building) during this time is provided from the conventional AC Maximum input power = 1700 W
Refrigerant type = R410A
unit and PCM TES by the heat exchanger 2 and heat exchanger
Manufacture = General Max
1, respectively. In other words, during cold energy discharging Electrical heater 5 electrical heaters with 2 kW power each one
mode, all of the cooling load production by the vapor compression Expansion valve MOP = 15 ◦ C
system is transferred to the indoor test chamber (building) by Design type = Thermostatic
the heat exchanger 2 to provide part of the building cooling load Manufacture = Honeywell
Temperature range = −50 to 15 ◦ C
demand. The rest is supplied by the PCM TES with the circulating Air fan Voltage = 380 V
water pump simultaneously. It should be noted that the cold Power = 750 W
energy discharge time depends on the type of scenarios, which 2800 RPM (Max)
will be discussed later. Manufacture = Moto Gen
In the conventional mode with no PCM involvement, the water Inverter Power = 1.5 kW
Model = LS iG5 A
pump is switched off the whole time, and the vapor compression Temperature sensors Model = PT 100
system alone (conventional AC) provides all the cooling load Error = ±0.2 ◦ C
demand by the refrigerant evaporator (heat exchanger 2). In this Range = −200 to 850 ◦ C
mode, the refrigerant exits from the expansion valve and enters Pressure gauges Error = 2.5%
the solenoid valve 1 (point 3). Then it goes to heat exchanger 2 Range = 0 to 40 bar
Type = Analog
to absorb the heat load produced by the electrical heaters inside Wattmeter Type = Digital
the indoor test chamber (building). After that, it enters the com- Error = 0.5%
pressor to complete the normal process of the conventional vapor
compression cycle. The schematic of the conventional mode pro-
cess is illustrated in Fig. 6d. The conventional mode times also
vary depending on the types of scenarios. Moreover, the power Fig. 7. It is notable that the changes in the outdoor test chamber
consumption of the electrical heaters inside the indoor test cham- (ambient) during the day directly affect the performance of the
ber, which is measured by the wattmeter, plays the role of the vapor compression cycle condenser. Consequently, changes in
cooling load demand of the building. In other words, the amount condenser conditions lead to changing the whole system’s perfor-
of the power consumption of the electrical heaters inside the mance. Also, the temperature variations in the indoor test cham-
indoor test chamber is equal to cooling load production, named ber (building) and outdoor test chamber (ambient) are measured
as the building accessible cooling load by the proposed system in by the thermometers and are recorded by the SCADA software in
each mode. a computer.
The specifications of the main equipment which are used in
the desired experimental evaluation are listed in Table 2. 2.6. Performance evaluation
2.5. Outdoor test chamber (ambient) temperature condition To evaluate the performance of the proposed system, the
following formulas have been used.
To simulate the realistic imitation of ambient temperature QHeaters
COP = (1)
in the outdoor test chamber, the weather data of five different Wcomp + WPump
cities on their hottest days of the year have been given to the
QHeaters = QBuilding = QHex,1 + QHex,2 (2)
controller. The weather data information has been extracted from
Meteonorm software and then has been read by the TRNSYS Peak load = Max pow er consumption
software. The only parameter, which has been controlled in the − AVG pow er consumption of conv entional cooling system (3)
outdoor test chamber is temperature, and the other climatic
Peak load shav ing
conditions such as humidity are constant during the test and are
Peak load of conv entional system − Peak load of PCM integrated system
( )
not controlled. =
Peak load of conv entional system
The cities are Tehran, Ahvaz, Hamedan, Ramsar, and Bushehr,
which their temperature changes over the 24 h are indicated in × 100 (4)
855
A. Riahi, H.J. Mosleh and M.B. Shafii Energy Reports 10 (2023) 850–863
Fig. 6. (continued).
Fig. 6. The schematic of the (a) conventional AC plus PCM TES (b) cold energy
charging process (c) cold energy discharging process (d) conventional AC unit.
also denote the cooling load provided by the heat exchanger 1
and heat exchanger 2, respectively. It should be noted the values
where QHeaters , Wcomp , and WPump are the electric heaters’ power of electrical heaters inside the test chamber, vapor compressor,
consumption inside the indoor test chamber (counterbalancing and circulating water pump power consumptions have been mea-
cooling load production), vapor compressor power consumption, sured by the wattmeters and are recorded by the SCADA software
and circulating water pump power, respectively. QHex,1 and QHex,2 in a computer.
856
A. Riahi, H.J. Mosleh and M.B. Shafii Energy Reports 10 (2023) 850–863
Table 3
The brief description of scenario 1 operating conditions.
Type of system Off-Peak hours (00:00–08:00) On-Peak hours (12:00–19:00) Conventional mode
(08:00–12:00 & 19:00–24:00)
AC plus PCM Providing 0.5 kW cooling load from PCM TES Providing cooling energy from PCM Working at maximum capacity
by the circulating water pump & charging PCM TES & AC unit simultaneously with no PCM involved
TES simultaneously
Conventional AC unit Working at maximum capacity Working at maximum capacity Working at maximum capacity
Table 4
The brief description of scenario 2 operating conditions.
Type of system Off-Peak hours (00:00–08:00) On-Peak hours (Based on Desired Conventional mode (Based on Desired
Building Cooling Load Demand) Building Cooling Load Demand)
AC plus PCM Providing desired building cooling load from Providing cooling energy from PCM Working based on desired building
PCM TES by the circulating water Pump & TES & AC unit simultaneously cooling load demand with no PCM
charging PCM TES simultaneously involved
Conventional AC unit Working based on desired Building cooling Working based on desired building Working based on desired building
load demand cooling load demand cooling load demand
Fig. 9. The T-S diagrams of the charging process in PCM and conventional modes
for (a) storage tank temperature about 0 ◦ C (b) storage tank temperature about
21 ◦ C.
859
A. Riahi, H.J. Mosleh and M.B. Shafii Energy Reports 10 (2023) 850–863
Table 5
The daily results of the conventional AC system (with no PCM TES involved) and AC plus PCM unit based on scenario 1 operating conditions.
Cities Tehran Hamedan Ramsar Bushehr Ahvaz
Modes Conventional AC plus Conventional AC plus Conventional AC plus Conventional AC plus Conventional AC plus
AC PCM AC PCM AC PCM AC PCM AC PCM
Daily total accessible cooling energy (kWh) 31.83 28.50 37.50 32.97 38.25 33.02 31.53 23.10 23.79 18.02
Daily total compressor energy consumption (kWh) 25.09 25.55 24.83 25.34 24.33 24.81 25.58 26.02 28.09 28.50
Daily total pump energy consumption (kWh) 0 1.59 0 1.79 0 1.89 0 1.57 0 1.49
Daily total electric energy consumption (kWh) 25.09 27.15 24.83 27.14 24.33 26.70 25.58 27.58 28.09 30.00
Daily average COP 1.27 1.05 1.51 1.21 1.57 1.24 1.23 0.84 0.85 0.60
COP at on-peak hours (12–19) 0.91 1.52 1.05 1.74 1.32 1.82 0.81 0.92 0.51 0.66
Accessible cooling energy at on-peak hours (12–19) (kWh) 7.53 13.79 8.55 15.94 9.91 15.62 6.61 8.17 4.63 6.36
among all cities. In contrast, Ahvaz, which has the highest am- daily total accessible cooling energy belongs to Bushehr city with
bient temperature, achieves the lowest accessible cooling load −26.73% shown in red in Table 6. In contrast, the lowest re-
power of 574 W at its maximum ambient temperature among all duction is related to Tehran city with −10.44% shown in red in
cities. It can be seen that ambient temperature plays a significant Table 6.
role in the amount of conventional AC unit accessible cooling Furthermore, adding the PCM TES to the conventional AC
load. So, adding the PCM TES to the conventional AC unit and system increases daily total electric energy consumption (time-
using its stored cold energy during on-peak hours, which also integral of electric power) for all cities. Since the AC plus PCM
coincides with high ambient temperature, can enhance the acces- unit uses a circulating water pump in addition to the conventional
sible cooling load during the proposed time. As a result, there is AC unit, its daily total electric energy consumption is higher than
no need to use a larger conventional AC system to provide cooling the conventional AC one. As mentioned, the AC plus PCM unit’s
load demand during on-peak hours. evaporator temperature (PCM TES temperature) is less than the
The ambient temperature also affects the compressor power conventional AC unit’s evaporator temperature (heat exchanger
consumption, as shown in Fig. 10. It can be seen that the con- 2) during the cold energy charging process. So, it reduces the AC
ventional AC unit’s compressor power consumption reaches its plus PCM unit’s evaporator pressure. Consequently, the pressure
minimum from 00:00–8:00 for all cities due to their lower ambi- difference between the condenser and evaporator of the AC plus
ent temperature compared to other times of the day. In contrast, PCM is more than the conventional AC during this time. Hence,
it reaches its maximum during on-peak hours from 12:00–19:00 the compressor consumes more electric energy to provide the
for all cities due to their higher ambient temperature compared desired pressure difference. The highest increase in daily total
to other times of the day. For instance, Tehran city’s compres- electric energy consumption belongs to Ramsar city with 9.74%.
sor power reaches 865 W from 00:00–8:00. In comparison, it In contrast, the lowest rise is related to Ahvaz city with 6.77%
increases up to 1210 W during on-peak hours from 12:00–19:00. shown in red in Table 6.
Moreover, Hamedan, which has the lowest ambient tempera- Obviously, as a result of higher daily total electric energy
ture, achieves the lowest compressor power consumption with consumption and lower daily total accessible cooling energy of
825 W at its minimum ambient temperature. In contrast, Ahvaz, the AC plus PCM unit compared to the conventional AC unit,
which has the highest ambient temperature, achieves the highest adding the PCM TES to the conventional AC unit lowers the daily
compressor power consumption with 1335 W at its maximum averaged COP based on Eq. (1). Shown in red in Table 6, the
ambient temperature. highest and lowest decline in COP is related to Bushehr and
In fact, the changes in ambient temperature affect the AC Tehran cities with −32.07% and −17.23%, respectively. It is noted
system’s condenser pressure and temperature. In this regard, that since the cooling energy stored in the PCM comes to the
condenser temperature and pressure increase as the ambient aid of the AC cooling unit, adding PCM TES to the conventional
temperature increases. Hence, the AC unit’s compressor must AC system boosts the accessible cooling energy and COP during
consume more power to boost the refrigerant pressure from on-peak hours only from 12:00–19:00 for all cities. For example,
evaporator pressure to the condenser pressure. Also, the amount the average COP of AC plus PCM and accessible cooling energy
of cooling load production is affected according to the proposed for Hamedan city rise 65.99% and 86.34%, respectively, during
changes. cold energy discharging hours (on-peak hours) from 12:00-19:00,
The results of the daily performance of the conventional AC compared to the conventional AC unit.
system with no PCM TES involvement and the AC plus PCM based
on scenario 1 operating conditions are summarized in Table 5. 3.2. Scenario 2 results
Also, the changes in the performance of the AC plus PCM com-
pared to the conventional AC one are stated in Table 6. It should The changes in fulfillable building cooling load demand and
be noted that the negative sign in Table 6 indicates a decrease power consumptions of the AC unit plus PCM and the con-
in the desired parameters after adding the PCM TES to the con- ventional AC system with no PCM TES involvement based on
ventional AC unit. The positive sign indicates an increase in the scenario 2 operating conditions are shown in Fig. 11 over 24 h
desired parameters after adding the PCM TES to the conventional for Ramsar and Ahvaz cities. As it is mentioned before, each city
AC unit. has a specific fulfillable building cooling load demand profile. The
It can be seen that adding PCM TES to the conventional AC unit cities with the lower daily average ambient temperature can have
leads to a reduction in daily total accessible cooling energy for all a higher daily total fulfillable building cooling energy demand.
cities, which was obtained by integrating accessible cooling load According to Table 7, Ahvaz with the daily average ambient
over time. It happens due to the heat transfer loss during the cold temperature of 42.07 ◦ C, has the lowest daily total fulfillable
energy charging and discharging processes. Moreover, the AC plus building cooling energy demand of 14.95 kWh, shown in red. In
PCM unit’s evaporator temperature (PCM TES temperature) is less contrast, Hamedan with 29.91 kWh achieves the highest daily
than the conventional AC unit’s evaporator temperature (heat ex- total fulfillable building cooling energy demand (shown in red).
changer 2) due to the PCM melting temperature (0 ◦ C) during the As shown in Fig. 11, the total electric energy consumption
cold energy charging process from 00:00–8:00. So, it decreases of the AC plus PCM during cold energy charging hours (00:00–
the AC plus PCM unit’s evaporator pressure, which reduces the 8:00) is higher than the conventional AC one for all cases. Dur-
daily total accessible cooling energy. The highest reduction in ing the proposed time, the conventional AC unit only needs to
860
A. Riahi, H.J. Mosleh and M.B. Shafii Energy Reports 10 (2023) 850–863
Table 6
The reduction and increase of the AC plus PCM unit parameters compared to the conventional AC system.
Table 7
The performance of the AC plus PCM based on scenario 2 operating condition for various cities.
4. Conclusion
for Tehran, Hamedan, Ramsar, Bushehr, and Ahvaz cities. More- Chaichana, C., Charters, W.W.S., Aye, L., 2001. An ice thermal storage computer
over, the precise realistic imitation of temperature conditions model. Appl. Therm. Eng. 21 (17), 1769–1778. http://dx.doi.org/10.1016/
S1359-4311(01)00046-1, 2001/12/01/.
for outdoor (condenser, compressor...) and indoor (evaporator)
units of the vapor compression system is provided by the two Erdemir, D., Altuntop, N., 2018. Effect of encapsulated ice thermal storage system
on cooling cost for a hypermarket. Int. J. Energy Res. 42, http://dx.doi.org/
separated test chambers with the help of the controller. Some 10.1002/er.3971, 01/12.
of the main results of the proposed analysis are summarized as Erdemir, D., Altuntop, N., Çengel, Y.A., 2021. Experimental investigation on
follows. the effect of ice storage system on electricity consumption cost for a
hypermarket. Energy Build. 251, 111368. http://dx.doi.org/10.1016/j.enbuild.
• According to scenario 1 operating strategy, the conventional 2021.111368, 2021/11/15/.
AC system (with no PCM involved) based on Ramsar temper- Gholamibozanjani, G., Farid, M., 2020a. Application of an active PCM storage
ature conditions, which has the minimum average ambient system into a building for heating/cooling load reduction. Energy 210,
temperature over 24 h, has the best performance compared 118572. http://dx.doi.org/10.1016/j.energy.2020.118572, 2020/11/01/.
to proposed cities. Gholamibozanjani, G., Farid, M., 2020b. A comparison between passive and
active PCM systems applied to buildings. Renew. Energy 162, 112–123.
• Based on scenario 1 operating strategy, adding the PCM TES
http://dx.doi.org/10.1016/j.renene.2020.08.007, 2020/12/01/.
to the conventional AC system leads to decreasing daily total
Habibi, R., Mehrpooya, M., Pourmoghadam, P., 2021. Integrated Mg-Cl hy-
COP and daily total accessible cooling energy for all cases. drogen production process and CaO/CaCO3-CaCl2 thermochemical energy
• Based on scenario 1 operating strategy, adding the PCM storage phase change system using solar tower system. Energy Convers.
TES to the conventional AC system boost COP and acces- Manage. 245, 114555. http://dx.doi.org/10.1016/j.enconman.2021.114555,
sible cooling energy during on-peak hours (12:00–19:00). 2021/10/01/.
The AC plus PCM maximum accessible cooling load power Hoseini Rahdar, M., Emamzadeh, A., Ataei, A., 2016. A comparative study on
PCM and ice thermal energy storage tank for air-conditioning systems in
during the cold energy discharging time (12:00–19:00) for
office buildings. Appl. Therm. Eng. 96, 391–399. http://dx.doi.org/10.1016/j.
Hamedan city (3112 W) boosts about 113% compared to the applthermaleng.2015.11.107, 2016/03/05/.
conventional AC unit. IEA, 2021. Global Energy Review 2021. IEA, Paris, https://www.iea.org/reports/
• Based on scenario 2 operating strategy, adding the PCM global-energy-review-2021 (accessed).
TES to the conventional AC unit increases total electric con- Imafidon, O.J., Ting, D.S.K., 2022. Energy consumption of a building with phase
sumption over 24 h. The highest increase in total electric change material walls – The effect of phase change material properties. J.
energy consumption belongs to Ramsar city with 9.74%. In Energy Storage 52, 105080. http://dx.doi.org/10.1016/j.est.2022.105080.
contrast, the lowest rise is related to Ahvaz city with 6.77%. Korth, T., Loistl, F., Storch, A., Schex, R., Krönauer, A., Schweigler, C., 2020.
• Based on scenario 2 operating strategy, adding the PCM Capacity enhancement of air conditioning systems by direct integration of
a latent heat storage unit. Appl. Therm. Eng. 167, 114727. http://dx.doi.org/
TES to the conventional AC unit leads to electric peak load 10.1016/j.applthermaleng.2019.114727, 2020/02/25/.
shaving amount ranging from 45.11% to 67.02%, in which the
Lin, W., Ma, Z., McDowell, C., Baghi, Y., Banfield, B., 2020. Optimal design
highest peak load shaving belongs to Tehran, and the least of a thermal energy storage system using phase change materials for a
is related to the Bushehr city. net-zero energy Solar Decathlon house. Energy Build. 208, 109626. http:
//dx.doi.org/10.1016/j.enbuild.2019.109626, 2020/02/01/.
CRediT authorship contribution statement Mazzoni, S., Sze, J.Y., Nastasi, B., Ooi, S., Desideri, U., Romagnoli, A., 2021.
A techno-economic assessment on the adoption of latent heat thermal
Alireza Riahi: Writing – original draft, Conceptualization, Ex- energy storage systems for district cooling optimal dispatch & operations.
Appl. Energy 289, 116646. http://dx.doi.org/10.1016/j.apenergy.2021.116646,
perimental tests, Investigation, Result evaluation. Hosein Jafari
2021/05/01/.
Mosleh: Writing – original draft, Conceptualization, Experimen-
Mirjavadi, K., Pourfayaz, F., Pourmoghadam, P., Kasaeian, A., 2022. A comparison
tal tests, Investigation, Result evaluation. Mohammad Behshad of using organic Rankine and Kalina cycles as bottom cycles in a solar-
Shafii: Conceptualization, Investigation, Writing – review & edit- powered steam Rankine cycle. Energy Sci. Eng. http://dx.doi.org/10.1002/
ing. ese3.1161, n/a, (n/a).
Mosaffa, A.H., Garousi Farshi, L., Infante Ferreira, C.A., Rosen, M.A., 2014. Ad-
Declaration of competing interest vanced exergy analysis of an air conditioning system incorporating thermal
energy storage. Energy 77, 945–952. http://dx.doi.org/10.1016/j.energy.2014.
10.006, 2014/12/01/.
The authors declare that they have no known competing finan-
cial interests or personal relationships that could have appeared Packer, M.B., Glicksman, L.R., 1979. An assessment of thermal energy storage in
conjunction with heat pumps for residential heating and cooling. Energy 4
to influence the work reported in this paper. (3), 393–399.
Pourmoghadam, P., Farighi, M., Pourfayaz, F., Kasaeian, A., 2021. Annual transient
Data availability analysis of energetic, exergetic, and economic performances of solar cascade
organic Rankine cycles integrated with PCM-based thermal energy storage
No data was used for the research described in the article. systems. Case Stud. Therm. Eng. 28, 101388. http://dx.doi.org/10.1016/j.csite.
2021.101388, 2021/12/01/.
References Pourmoghadam, P., Jafari Mosleh, H., Karami, M., 2022. Dynamic simulation of
a solar ejector-based trigeneration system using TRNSYS-EES co-simulator.
Afsharpanah, F., Pakzad, K., Mousavi Ajarostaghi, S.S., Arıcı, M., 2022. Assessment Energy Sci. Eng. 10 (3), 707–725. http://dx.doi.org/10.1002/ese3.1055.
of the charging performance in a cold thermal energy storage container with Pourmoghadam, P., Mehrpooya, M., 2021. Dynamic modeling and analysis
two rows of serpentine tubes and extended surfaces. J. Energy Storage 51, of transient behavior of an integrated parabolic solar dish collector and
104464. http://dx.doi.org/10.1016/j.est.2022.104464. thermochemical energy storage power plant. J. Energy Storage 42, 103121.
Aponte, O., McConky, K.T., 2022. Forecasting an electricity demand threshold to http://dx.doi.org/10.1016/j.est.2021.103121, 2021/10/01/.
proactively trigger cost saving demand response actions. Energy Build. 268,
Riahi, A., Kavian, S., jafari mosleh, H., Shafii, M., 2021a. Evaluation of a cooling
112221. http://dx.doi.org/10.1016/j.enbuild.2022.112221, 2022/08/01/.
Azzouz, K., Leducq, D., Gobin, D., 2009. Enhancing the performance of household system integrated with different phase change materials and its effect on
refrigerators with latent heat storage: An experimental investigation. Int. peak load shaving. Int. J. Energy Res. http://dx.doi.org/10.1002/er.6530, 02/19
J. Refrig. 32 (7), 1634–1644. http://dx.doi.org/10.1016/j.ijrefrig.2009.03.012, 2021.
2009/11/01/. Riahi, A., Mosleh, H.J., Kavian, S., Shafii, M.B., 2021b. Performance analysis and
Bista, S., Hosseini, S.E., Owens, E., Phillips, G., 2018. Performance improvement transient simulation of a vapor compression cooling system integrated with
and energy consumption reduction in refrigeration systems using phase phase change material as thermal energy storage for electric peak load
change material (PCM). Appl. Therm. Eng. 142, 723–735. http://dx.doi.org/ shaving. J. Energy Storage 35, 102316. http://dx.doi.org/10.1016/j.est.2021.
10.1016/j.applthermaleng.2018.07.068, 2018/09/01/. 102316, 2021/03/01/.
862
A. Riahi, H.J. Mosleh and M.B. Shafii Energy Reports 10 (2023) 850–863
Said, M.A., Hassan, H., 2021. Impact of energy storage of new hybrid system Wang, F., Maidment, G., Missenden, J., Tozer, R., 2007c. The novel use of phase
of phase change materials combined with air-conditioner on its heating and change materials in refrigeration plant. Part 3: PCM for control and energy
cooling performance. J. Energy Storage 36, 102400. http://dx.doi.org/10.1016/ savings. Appl. Therm. Eng. 27 (17), 2911–2918. http://dx.doi.org/10.1016/j.
j.est.2021.102400, 2021/04/01/. applthermaleng.2005.06.010, 2007/12/01/.
Selvnes, H., Allouche, Y., Hafner, A., 2021. Experimental characterisation of a Wijesuriya, S., Tabares-Velasco, P.C., 2020. Experimental apparatus and method-
cold thermal energy storage unit with a pillow-plate heat exchanger design. ology to test and quantify thermal performance of micro and macro-
Appl. Therm. Eng. 199, 117507. http://dx.doi.org/10.1016/j.applthermaleng. encapsulated phase change materials in building envelope applications.
2021.117507, 2021/11/25/. J. Energy Storage 32, 101770. http://dx.doi.org/10.1016/j.est.2020.101770,
Torregrosa-Jaime, B., López-Navarro, A., Corberan, J., Esteban-Matias, J., 2020/12/01/.
Klinkner, L., Payá, J., 2013. Experimental analysis of a paraffin-based cold Yang, T., Wang, C., Sun, Q., Wennersten, R., 2017. Study on the application of
storage tank. Int. J. Refrig. 36, 1632–1640. http://dx.doi.org/10.1016/j.ijrefrig. latent heat cold storage in a refrigerated warehouse. Energy Procedia 142,
2013.05.001, 09/01. 3546–3552. http://dx.doi.org/10.1016/j.egypro.2017.12.243, 2017/12/01/.
Wang, F., Maidment, G., Missenden, J., Tozer, R., 2007a. The novel use of Yau, Y.H., Lee, S.K., 2010. Feasibility study of an ice slurry-cooling coil for
phase change materials in refrigeration plant. Part 1: Experimental inves- HVAC and r systems in a tropical building. Appl. Energy 87 (8), 2699–2711.
tigation. Appl. Therm. Eng. 27 (17), 2893–2901. http://dx.doi.org/10.1016/j. http://dx.doi.org/10.1016/j.apenergy.2010.02.025, 2010/08/01/.
applthermaleng.2005.06.011, 2007/12/01/. Zeinelabdein, R., Omer, S., Mohamed, E., 2020. Parametric study of a sustain-
Wang, F., Maidment, G., Missenden, J.F., Tozer, R., 2007b. The novel use of phase able cooling system integrating phase change material energy storage for
change materials in refrigeration plant. Part 2: Dynamic simulation model buildings. J. Energy Storage 32, 101972. http://dx.doi.org/10.1016/j.est.2020.
for the combined system. Appl. Therm. Eng. 27, 2902–2910. 101972, 2020/12/01/.
863