Ref: PF/Offer/R/2024-10001123

Date- 13/05/2024
PROVITA GROUP
Provita Tower, House # 21 Rd 35, Dhaka 1212

WORK PROJECT: Provita Breeders Limited(Unit-02)

Sub:- Offer for Supply of 11/0.415 KV, 150 KVA Sub-Station Equipment.
Dear Sir,
We thank you a lot for your interest in Powerforce. The complete offer is enclosed along with price And
technical details as desired dry you. With reference to your request for supply of Sub-Station equipment,
we are hereby submitting our best offer for the mentioned equipment with the following terms &
conditions.

GENERAL TERMS & CONDITIONS


01) Price :- Quoted prices are in taka excluding VAT and AIT imposed by the govt. of
Bangladesh. If it is payable will be paid by the client.
02) Validity :- The offered price will remain valid up to 30 (Thirty) days from this date.
There after it will be subject to our further confirmation in writing.
03) Delivery :- Delivery within 4 to 6 weeks after receipt of technical and commercial
Clearance order. As well as advance payment.
04) Pre Delivery
Inspection :- Customers are requested to organize pre-delivery inspection if they think
This is required.
05) Payment :- A) 70% of the total order value will be paid along with the work order.
B) 20% of the total order value will be paid before delivery &
C) 10% will be paid along with Installation & Commissioning of Product.
06) Quality Control: - POWERFORCE ENGINEERING LTD. is one of the on going most
Professional Provita breeders limited Company in the country and
Growing rapidly Quality of our products is strictly controlled in accordance
to IEC 76, ANSI 57.12 and VDE- 0532.
07) Warranty :- 5 Year for Transformer replacement Guarantee & Equipment 1 Year
any Part or Parts replacement Guarantee.
08) Origin :- The Transformer Manufactured in our factory at Ramjan Market, Nishatnagar,
Turag, Uttara, Dhaka. The raw materials are imported from Japan & Belgium.
09) Excludes :- VAT & AIT Cables as per necessary.
10) Service :- Prompt service Within 5 hours by Call Basis for 24x7 Days in Dhaka.
We trust that we shall be able to strengthen our long-term relationship with
you and assuring you of our best services at all the time.

Thanking you

With Best Regards.

For POWERFORCE ENGINEERING LTD.

Thanking You

Md.Mijanur Rahman (Rony)


B,Sc Engineering (EEE)
Asst.Manager(Technical & Support)
Cell : 01723203403
E-mail :ronypowerforce@gmail.com
On Behalf of Powerforce Engineering Ltd.
TECHNICAL SPECIFICATION
11/0.415 KV, 150 KVA SUB STATION
S.N QTY DESCRIOTION
PART-A :- SUB-STATION EQUIPMENT
01 1 SET 11/0.415 KV, 150 KVA TRANSFORMER
3 Phase oil immersed, naturally air cooled Transformer acc. to VDE/IEC/ DIN standard with
3 HT Bushing and 4 LT Bushings arranged on tank top, conservator, oil level indicator, drain
and filling valves, lifting lugs, with first filling of oil in Transformer.
Technical Data :
Rated Capacity : 150 KVA
Rated Frequency : 50 Hz
Rated Voltage,
-Primary : 11000 V
-Secondary : 415 V
Rated Ampear
-Primary : 7.87A
-Secondary : 208.68A
Off-load tap changer : ±2.5%,-5%,-7.5%
Ambient Temperature : 40°C
Temperature rise,
- in Oil : 60°C (Max)
- in Coil : 65°C (Max)
Star point brought
out & loadable upto : 100%
Max. service altitude : 1000 Meters
Installation : Indoor/outdoor
No - load loss : 345 Watt
Load loss : 2412 Watt
Impedence : 4%
Tolerances, As per IEC 60076
Total losses : + 10% of the total losses
Component losses : + 15% of each component loss, provided
that the tolerance for total losses is not
exceeded.
Impedence voltage at rated : ± 10% of the declared
current (principal tapping) Impedance voltage for that tapping.
Accessories:
- Silicagel breather
- Thermometer
ORIGIN :
CORE : KAWASAKI, JAPAN.
COPPER STRIP : ORIENTAL COPPER CO. SINGAPORE.
INSULATION MATERIALS : WIEDMANN, SWITZERLAND.
TRANSFORMER OIL : SAVITA, INDIA.
SUPER ENAMELLED COPPER WIRE : RR/BRB/GAZI WIRES, BANGLADESH
MANUFACTURER BY : POWERFORCE ENGINEERING LTD
02 1 SET LT SWITCHGEAR - 250 A
Sheet steel clad powder coated (14 SWG), dust and vermin proof, free standing, floor
mounting, indoor type Low Tension Switchgear 415 V, 50 Hz, with hard drawn
copper busbars, TPN+ E equipped with:-
INCOMING :
1 No. T3N 250 FF R250A
250 A, 36 KA, TP MCCB with adjustable thermal overload and adjustable magnetic
short-circuit releases.
ORIGIN : ALL MCCB ABB, ITALY.

OUTGOING :
1 No. T1C 160 FF R125A ( FOR PFI )
125 A, 25 KA, TP MCCB with adjustable thermal overload and adjustable magnetic
short-circuit releases.
1 No. T3N 250 FF R200A ( FOR METERING PANEL With ATS )
200 A, 36 KA, TP MCCB with adjustable thermal overload and adjustable magnetic
short-circuit releases.
1 No. S203 –C 63A ( FOR SOLAR PANEL )
63 A, 6 KA, TP MCB
ORIGIN : ALL MCCB ABB, ITALY.

METERING SYSTEM :
DIGITAL MULTI METER : SECURE, INDIA.
HEAT REDUCED FAN SYSTEM.
TEMPARATURE METER SYSTEM.
DOUBLE DOOR LAMP SYSTEM.
ASSEMBLED BY POWERFORCE ENGINEERING LTD. BANGLADESH.
03 1 SET 90 KVAR AUTOMATIC PFI PLANT :
Sheet steel clad powder coated (14 SWG), dust and vermin proof, free standing, floor
mounting, 415V, 50 Hz, 90 KVAR Indoor type Automatic Power Factor Improvement
Plant, with hard drawn copper busbars, TP+E comprising :-

2 Nos. 20 KVAR Bank of TP dry type Power Capacitors with built-in discharge
resister.
3 Nos. 15 KVAR Bank of TP dry type Power Capacitors with built-in discharge
resister.
1 No. 5 KVAR Bank of TP dry type Power Capacitors with built-in discharge resister
(Direct).
ORIGIN : ANER, SPAIN.

1 No. Automatic Power Factor Correction Relay


ORIGIN : MIKRO, MALAYSIA.

5 Nos. SH203 –C 40A


40 A, 6 KA, TP MCB with adjustable magnetic short-circuit releases.
4 Nos. SH203 –C 20A
20 A, 6 KA, TP MCB with adjustable magnetic short-circuit releases.
3 Nos. SH203 –C 10A
10 A, 6 KA, TP MCB with adjustable magnetic short-circuit releases.
ORIGIN : ALL MCB ABB, GERMANY.

5 Nos. DMC-32b, AC3/440, AC1 TP Air Contactors of adequate rating.


3 Nos. DMC-18b, AC3/440, AC1 TP Air Contactors of adequate rating.
3 Nos. DMC-12b, AC3/440, AC1 TP Air Contactors of adequate rating.
ORIGIN : DONGA OR HYUNDAI, KOREA.

15 Nos. Indicating Lamps


1 Set of 32A TP MCB
HEAT REDUCED FAN SYSTEM.
ASSEMBLED BY POWERFORCE ENGINEERING LTD. BANGLADESH.
04 1 SET DROPOUT FUSE :
Technical Specification :
Rated maximum Voltage :15 KV
Rated Frequency : 50 Hz
BIL : 75 KV
Rated current RMS : 100 A
Interrupting Current RMS : 10 KA
Withstand Test Voltage
Dry, 1 Min. : 35 KV
Wet, 10 Sec. : 30 KV
ORIGIN : BRAZIL.
05 1 SET LIGHTNING ARRESTOR :
Technical Specification :
Rated Voltage (RMS : 9 KV
Rated System Voltage : 12 KV
Frecuency : 50 Hz
Minimum Spark Over (RMS) : 14 KV
Maximum Spark Over (RMS) : 40 KV
Maximum Impulse Spark (Crest) : 45KV
Withstand Voltage
Dry, 1 Min. : 28 KV
Wet, 10 Sec. : 24 KV
Discharge 33 kV (Crest) : 5 KA
Impulse Current Withstand : 55 KA
ORIGIN : BRAZIL.
06 1 SET METERING BOX With ATS PANEL- 200 A:-
Sheet steel clad powder coated (14 SWG), dust and vermin proof, free standing, floor
mounting, indoor type Metering Box With ATS PANEL 415 V, 50 Hz, with hard
drawn copper busbars, TPN+ E equipped with:-
INCOMING :
1 No. T3N 250 FF R200A (DPDC)
200 A, 36 KA, TP MCCB with adjustable thermal overload and adjustable magnetic
short-circuit releases.
1 No. T1C 160 FF R100A ( GEN.)
100 A, 25KA, TP MCCB with adjustable thermal overload and adjustable magnetic
short-circuit releases.
ORIGIN : ALL MCCB ABB, TALY.

14 Nos. DMC-22b. Magnetic Contactor AC Coil 20A (AC3), 3P, ITH 40A , (AC1)
(Floor)
2 Nos. DMC-40b. Magnetic Contactor AC Coil 32A (AC3), 3P, ITH 60A , (AC1)
(Motor)
2 Nos. DMC-85b. Magnetic Contactor AC Coil 78A (AC3), 3P, ITH 135A , (AC1)
(Lift)
ORIGEN : DONGA OR HYUNDAI, KOREA.

OUTGOING :
1 No. T1C 160 FF R100A ( LIFT.)
100 A, 25KA, TP MCCB with adjustable thermal overload and adjustable magnetic
short-circuit releases.
20 Nos. SH203-C32 A (UNIT FLOOR)
32 A, 6 KA, DP MCB with adjustable magnetic short-circuit releases.
1 No. SH203-C40 A (MOTOR-1)
40 A, 6 KA, TP MCB with adjustable magnetic short-circuit releases.
1 No. SH203-C40 A (MOTOR-2)
40 A, 6 KA, DP MCB with adjustable magnetic short-circuit releases.
20 Nos. SH201-C16 A (UNIT FLOOR / COMM.)
16 A, 6 KA, SP MCB with adjustable magnetic short-circuit releases.
ORIGIN : ALL MCB ABB, GERMANY.

METERING SYSTEM :
HEAT REDUCED FAN SYSTEM.
DOUBLE DOOR LAMP SYSTEM.
ASSEMBLED BY POWERFORCE ENGINEERING LTD. BANGLADESH.
07 EARTHING FOR SUBSTATION:-
6 SET EARTH ELECTRODE
Installation of 1x20', 1½" dia GI Pipe having ¼" hole at required' interval l buried upto
the depth of 100'- 0"(with connecting copper link) in the damp soil including 2 SWG
copper wire from bottom of GI Pipe upto connecting link.
2 SET EARTHING BLOCK
Installation, testing and commissioning of copper earthing block with required Nos. of
¼" hole one for ECC connection Size - 254mm x 30mm x 10mm and another for
transformer neutral earthing.
120 rft EARTHING LEAD
Installation of earthing lead, 2 SWG copper wire through 1" dia GI pipe (if required
than supplied by customer) from earthing block to earth electrode including inter-
connection between two electrodes.
100 rft EARTH CONTINUITY CONDUCTOR
Installation of 2 SWG copper earth continuity conductor running from the bodies of
substation equipment to the earthing block.
08 1M HT CABLE
Supply, laying and terminating of 11KV HT cable type NYSEYFGbY 3cx70mm² of
M/s. BRB/RR/BBS Cables Ltd.
- PIB tape
- Carbon Tetrachloride (CTC)
- Cable lugs
- Nut, Bolt, Brick, Sand, etc.
1M LT CABLE
Supply, laying and terminating of LT cable type NYY 1cx 120 mm² from transformer
LT bushing to LT panel as double cable per phase including supply of
M/s. BRB/RR/BBS Cables Ltd.
- PIB tape
- Cable lugs
- Nut, Bolt, etc.
09 2 SET Supply & installation of Heat Shrinkable cable end kit for HT cable terminal
protection.
SN QTY. PRICE PROPOSAL UNIT TOTAL
PRICE PRICE
150 KVA SUB-STATION EQUIPMENT
PART –A
01 1 SET 150 KVA 11/0.415 KV TRANSFORMER 390000 390000
02 1 SET LT SWITCHGEAR PANEL 250 A 140000 140000
03 1 SET 90 KVAR PFI PLANT WITH CIRCUIT BREAKER 110000 110000
04 1 SET DROPOUT FUSE 10000 10000
05 1 SET LIGHTNING ARRESTOR 10000 10000
06 1 JOB ELECTRICAL LICENSING BOARD PURPOSE 60000 60000
07 6 SET EARTHING FOR SUB-STATION EQUIPMENT 25000 150000
08 1 JOB TRANSPORTATION & LOADING AND 45000 45000
UNLOADING WITH INSTALLATION
09 2 SET HEAT SHRINK KIT 3500 7000
10 1 JOB INSTALLATION ACCESSORIES 15000 15000
SUB - TOTAL TAKA 937000
PART- B (DESCO METERING)
01 1 SET 11KV INDOOR LT-CT METERING 90000 90000
02 1 JOB DEMAND LOAD PERMISSION COST 80000 80000
03 1 JOB DEMAND LOAD COST(120 KW) 120000 120000
04 1 JOB MATERALS COST 45000 45000
05 18 Set SINGLE PHASE METER COST 6500 117000
06 18 Set SINGLE PHASE METER CONNECTION COST 15000 15000
07 1 JOB APPLICATION FREE MATHER METER 7000 7000
SUB - TOTAL TAKA 474000
PART- C (METERING PANEL WITH ATS)
01 1 SET METERING BOX WITH ATS PANEL-200A 290000 290000
SUB - TOTAL TAKA 290000
PART- D (SOLAR SYSTEM)
01 1 KW SOLAR SYSTEM (ON GRID) 70000
SUB - TOTAL TAKA
PART- F (CABLE)
01 1M 3C x 70 mm² (NYSEYFGbY) BRB/RR/BBS 8313
02 1M 1C x 120 mm² (NYY) BRB/RR/BBS(FOR Tr. to LT) 2426
03 1M 1Cx96 mm² (NYY) BRB/RR/BBS (FOR LT to 1942
METERING BOX)
04 1M 1Cx70 mm² (NYY) BRB/RR/BBS (FOR LT to PFI) 1453
05 1M 1Cx16 mm² (BYA) BRB/RR/BBS (FOR EARTHING) 324
06 1M 1Cx10 mm² (BYA) BRB/RR/BBS (FOR HT CABLE
EARTHING) 205
SUB - TOTAL TAKA
TOTAL (PART-A+B+C+D) TAKA 1701000

Note:- LIST OF INCLUSIONS


1. Supply Installation & Testing of 150 KVA Substation Equipment.
2. All formalities for getting license from Chief Electrical Inspector.
LIST OF EXCLUSIONS
1. Any Civil work like base foundation and Cable Trench cutting and making is beyond our scope
of offer.
2. Any kind of fencing.

Thanking you

With Best Regards.

For POWERFORCE ENGINEERING LTD.

Thanking You

Md.Mijanur Rahman (Rony)


B,Sc Engineering (EEE)
CEO
Cell : 01723203403
E-mail :ronypowerforce@gmail.com