ELECTRICAL
ELECTRICAL
NOTES
1. CONTRACTOR SHOULD BE SURVEYING & LEVELING AS PER SITE CONDITION IF ANY
CHANGE FOR LEVEL SHOULD BE APPLY TO DM BEFORE THE COMPLETION CERTIFICATE.
2. THE COLUMN INSIDE THE BUILDING WILL COVERED BY CONCRETE / CEMENT BOARD
AS PER ENGINEER APPROVAL.
PLOT LIMIT NEIGHBOUR PLOT NEIGHBOUR PLOT PLOT LIMIT 3. THE AREA CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY APPROVAL
4. THE NO. OF CAR PARKING CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY
APPROVAL
B2/DB-EXT
ISO FOR CHILLER UNIT 1 ISO FOR CHILLER UNIT 2 PROPOSED
S
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20
HOLDING TANK
SECURITY ROOM
W
N
ONE WAY
40
INTERLOCK
ON
AY
39
EW
EW
ON
AY
38
37
36
35
ONE WAY
RYB7/DB-L
34
ONE WAY
CAR CHARGIING
NEIGHBOUR PLOT
RYB6/DB-L
33
CAR CHARGIING
NEIGHBOUR PLOT
32
RYB5/DB-L
CAR CHARGIING
31
30
PROPOSED WORKSHOP
29
+0.20m
Y4/DB-EXT
25
24
23
ONE WAY
Y2/DB-EXT
22
ONE WAY
21
SMDB-
AHU CB-1
SERVICE BLOCK
INTERLOCK
PROPOSED
INTERLOCK
LV ROOM DETAILS
GROUND FLOOR
(SCALE:- 1:50)
P O Box :377041
ENGINEERING CONSULTANCIES Dubai, UAE
CONTRACTOR
PROJECT NO. PROJECT PLOT NO. LOCATION DRAWING TITLE SCALE DRAWING NO.
OWNER LESSEE GATE LEVEL
PROPOSED WAREHOUSE SETTING LAYOUT SHAIKH MOHAMMED BIN BUTTI BIN HAMED ALHAMED
1099 AL QOUZ IND. THIRD 1:150 E-100 GOVERNMENT OF DUBAI - DUBAI REAL ESTATE CORPORATION
& WORKSHOP 3680446 ELECTRICAL LAYOUT
B+G+M UNITED ALSAQER HEAVY EQUIPMENT SERVICE CENTER (WORKSHOP)
SIGN & STAMP BY DM MUNICIPALITY
NOTES
1. CONTRACTOR SHOULD BE SURVEYING & LEVELING AS PER SITE CONDITION IF ANY
CHANGE FOR LEVEL SHOULD BE APPLY TO DM BEFORE THE COMPLETION CERTIFICATE.
2. THE COLUMN INSIDE THE BUILDING WILL COVERED BY CONCRETE / CEMENT BOARD
OVER GROUND
WORKSHOP AREA
S
DOMESTIC / FIRE
FIGHTING TANKS ( 2 nos )
Air Compressor Open Height area for Vehicles weight lifts
OFFICES AREA 588.60 SQ.M / 6335.70 SQ.FT
W
N
B1/DB-GF1
ST
ST
MANUAL WASH
BAY area
Y1/DB-GF1
R1/DB-GF1
PUMP ROOM
( 2 nos ) R1/DB-GF2
Auto Car Lift M.TOI
Y1/DB-GF2 F. TOILET
SP
FT
LI
ST
ST
+0.30m
F.F.L
ST
F.F.L
ST
ST
ST
Y5/DB-SH
H.TOI
R1/DB-SH
+0.30m
+0.30m F.F.L
F.F.L W/P F. TOILET
Y1/DB-SH
W/P
M. TOILET
B1/DB-SH
H.TOI
SP
R2/DB-SH R5/DB-SH
B2/DB-SH
MAIN CONSULTANT
Lead Consultants:
+0.30m © Drawing & Design Copyright of:
F.F.L Options Engineering Consultancies
00
P O Box :377041
F.F.L
ENGINEERING CONSULTANCIES Dubai, UAE
T:+971 (4) 2854383
F:+971 (4) 2855251
CONTRACTOR
NOTES
1. CONTRACTOR SHOULD BE SURVEYING & LEVELING AS PER SITE CONDITION IF ANY
CHANGE FOR LEVEL SHOULD BE APPLY TO DM BEFORE THE COMPLETION CERTIFICATE.
2. THE COLUMN INSIDE THE BUILDING WILL COVERED BY CONCRETE / CEMENT BOARD
ST ST ST ST
ST ST ST ST
WORKSHOP AREA
SPARE PART
Chiller Area +4.50m HB HB
Open Height area for Vehicles weight lifts
HB HB HB HB HB HB
S
F.F.L STORE
ST ST ST ST Y2/DB-GF1
B2/DB-MEZZ1
W
N
ST ST ST ST HB HB HB HB HB HB HB
DN
B2/DB-GF1
R4/DB-MEZZ1
ST ST ST ST
Y1/DB-MEZZ1
+4.80m
F.F.L
B1/DB-MEZZ1 R2/DB-MEZZ1
LI DN
FT
R3/DB-SH
HB HB HB HB HB HB HB HB HB HB HB HB
Y3/DB-SH
HB HB HB HB HB HB HB HB HB HB HB HB
B3/DB-SH
HB HB HB HB HB HB HB HB HB HB HB HB
CAR LIFT
DN
DN
R1/DB-MEZZ2 +4.50m
F.F.L
Y1/DB-MEZZ2
B1/DB-MEZZ2 R2/DB-MEZZ2
B2/DB-MEZZ2
REV. DESCRIPTION DATE
+4.50m
F.F.L
R3/DB-MEZZ2 Y3/DB-MEZZ2
MAIN CONSULTANT
Lead Consultants:
© Drawing & Design Copyright of:
Options Engineering Consultancies
P O Box :377041
ENGINEERING CONSULTANCIES Dubai, UAE
T:+971 (4) 2854383
F:+971 (4) 2855251
CONTRACTOR
NOTES
1. CONTRACTOR SHOULD BE SURVEYING & LEVELING AS PER SITE CONDITION IF ANY
CHANGE FOR LEVEL SHOULD BE APPLY TO DM BEFORE THE COMPLETION CERTIFICATE.
2. THE COLUMN INSIDE THE BUILDING WILL COVERED BY CONCRETE / CEMENT BOARD
AS PER ENGINEER APPROVAL.
3. THE AREA CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY APPROVAL
4. THE NO. OF CAR PARKING CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY
APPROVAL
WS
N
REV. DESCRIPTION DATE
MAIN CONSULTANT
Lead Consultants:
© Drawing & Design Copyright of:
Options Engineering Consultancies
P O Box :377041
ENGINEERING CONSULTANCIES Dubai, UAE
T:+971 (4) 2854383
F:+971 (4) 2855251
CONTRACTOR
ROOF PLAN
PROJECT NO. PROJECT PLOT NO. LOCATION DRAWING TITLE SCALE DRAWING NO.
OWNER LESSEE GATE LEVEL
PROPOSED WAREHOUSE ROOF PLAN SHAIKH MOHAMMED BIN BUTTI BIN HAMED ALHAMED
1099 AL QOUZ IND. THIRD 1:150 EL-103 GOVERNMENT OF DUBAI - DUBAI REAL ESTATE CORPORATION
& WORKSHOP 3680446 LIGHTING LAYOUT
B+G+M UNITED ALSAQER HEAVY EQUIPMENT SERVICE CENTER (WORKSHOP)
SIGN & STAMP BY DM MUNICIPALITY
OVER GROUND
DOMESTIC / FIRE WORKSHOP AREA
FIGHTING TANKS ( 2 nos )
Open Height area for Vehicles weight lifts
S
Air Compressor
Y4/DB-GF2 R3/DB-GF1
OFFICES AREA 588.60 SQ.M / 6335.70 SQ.FT
R3/DB-L
W
N
ISO FOR JOCKEY PUMP
ISO FOR FIRE PUMP
ISO FOR DIESEL PUMP
MANUAL WASH
BAY area
B4/DB-GF2
R4/DB-L B3/DB-GF2
PUMP ROOM FACP R4/DB-GF1
B3/DB-GF1
RYB5/DB-GF2
( 2 nos )
RYB13/DB-GF2 ISO FOR G-01
Auto Car Lift M.TOI
ISO FOR G-01 RYB7/DB-GF2 RYB8/DB-GF2 RYB9/DB-GF2 RYB10/DB-GF2 RYB11/DB-GF2 F. TOILET
+0.30m R3/DB-GF2
GARBAGE ROOM
RYB6/DB-GF2 F.F.L
RYB14/DB-GF2 G-01
H.TOI H.TOI
G-01
DB-L
SMDB-L
FT
LI
R7/DB-SH R6/DB-SH
DB-SHOWROOM
+0.30m
F.F.L
F.F.L
B7/DB-SH
H.TOI
+0.30m
+0.30m F.F.L
F.F.L F. TOILET
B6/DB-SH
M. TOILET
H.TOI
Y7/DB-SH
R6/DB-SH Y6/DB-SH
MAIN CONSULTANT
ISO FOR SIGNAGE +0.30m
F.F.L Lead Consultants:
00
© Drawing & Design Copyright of:
Options Engineering Consultancies
F.F.L
P O Box :377041
ENGINEERING CONSULTANCIES Dubai, UAE
T:+971 (4) 2854383
F:+971 (4) 2855251
CONTRACTOR
NOTES
1. CONTRACTOR SHOULD BE SURVEYING & LEVELING AS PER SITE CONDITION IF ANY
CHANGE FOR LEVEL SHOULD BE APPLY TO DM BEFORE THE COMPLETION CERTIFICATE.
2. THE COLUMN INSIDE THE BUILDING WILL COVERED BY CONCRETE / CEMENT BOARD
AS PER ENGINEER APPROVAL.
3. THE AREA CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY APPROVAL
4. THE NO. OF CAR PARKING CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY
APPROVAL
WORKSHOP AREA
SPARE PART
Chiller Area +4.50m
F.F.L STORE
Open Height area for Vehicles weight lifts
ISO FOR F-01
S
Y5/DB-MEZZ1
F-01
W
N
DN
B6/DB-MEZZ1 Y6/DB-MEZZ1
F-01 CHILLER PUMP R5/DB-MEZZ1 ( MEZZANINE FLOOR AREA )
R7/DB-MEZZ1
FOR WORKSHOP OFFICES
ISO FOR F-01 OFFICES AREA 180.00 SQ.M / 1937.50 SQ.FT
SMDB-MEZZ
DB-MEZZ 1
+4.80m
F.F.L
R6/DB-MEZZ1 B5/DB-MEZZ1
LI DN
FT
DN
DB-SM DB-MEZZ 2
Y5/DB-MEZZ2
MAIN CONSULTANT
R7/DB-MEZZ2
Lead Consultants:
© Drawing & Design Copyright of:
Options Engineering Consultancies
P O Box :377041
ENGINEERING CONSULTANCIES Dubai, UAE
T:+971 (4) 2854383
F:+971 (4) 2855251
CONTRACTOR
PROJECT NO. PROJECT PLOT NO. LOCATION DRAWING TITLE SCALE DRAWING NO.
OWNER LESSEE GATE LEVEL
PROPOSED WAREHOUSE MEZZANINE FLOOR SHAIKH MOHAMMED BIN BUTTI BIN HAMED ALHAMED
1099 AL QOUZ IND. THIRD 1:150 EP-102 GOVERNMENT OF DUBAI - DUBAI REAL ESTATE CORPORATION
& WORKSHOP 3680446 POWER LAYOUT
B+G+M UNITED ALSAQER HEAVY EQUIPMENT SERVICE CENTER (WORKSHOP)
SIGN & STAMP BY DM MUNICIPALITY
NOTES
1. CONTRACTOR SHOULD BE SURVEYING & LEVELING AS PER SITE CONDITION IF ANY
CHANGE FOR LEVEL SHOULD BE APPLY TO DM BEFORE THE COMPLETION CERTIFICATE.
2. THE COLUMN INSIDE THE BUILDING WILL COVERED BY CONCRETE / CEMENT BOARD
AS PER ENGINEER APPROVAL.
3. THE AREA CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY APPROVAL
4. THE NO. OF CAR PARKING CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY
APPROVAL
WS
N
REV. DESCRIPTION DATE
MAIN CONSULTANT
Lead Consultants:
© Drawing & Design Copyright of:
Options Engineering Consultancies
P O Box :377041
ENGINEERING CONSULTANCIES Dubai, UAE
T:+971 (4) 2854383
F:+971 (4) 2855251
CONTRACTOR
ROOF PLAN
PROJECT NO. PROJECT PLOT NO. LOCATION DRAWING TITLE SCALE DRAWING NO.
OWNER LESSEE GATE LEVEL
PROPOSED WAREHOUSE ROOF PLAN SHAIKH MOHAMMED BIN BUTTI BIN HAMED ALHAMED
1099 AL QOUZ IND. THIRD 1:150 EP-103 GOVERNMENT OF DUBAI - DUBAI REAL ESTATE CORPORATION
& WORKSHOP 3680446 POWER LAYOUT
B+G+M UNITED ALSAQER HEAVY EQUIPMENT SERVICE CENTER (WORKSHOP)
SIGN & STAMP BY DM MUNICIPALITY
NOTES
1. CONTRACTOR SHOULD BE SURVEYING & LEVELING AS PER SITE CONDITION IF ANY
CHANGE FOR LEVEL SHOULD BE APPLY TO DM BEFORE THE COMPLETION CERTIFICATE.
2. THE COLUMN INSIDE THE BUILDING WILL COVERED BY CONCRETE / CEMENT BOARD
AS PER ENGINEER APPROVAL.
3. THE AREA CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY APPROVAL
4. THE NO. OF CAR PARKING CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY
APPROVAL
WS
N
SL
O
ELECTRICAL NON COMBUSTIBLE ELECTRICAL
PE
NON LOUVERED DOOR
ROOM R4/DB-EXT ROOM
1:1
00
R1/DB-EXT
R3/DB-SS R1/DB-SS
SUBSTATION ROOM LAYOUT
SHALL BE AS PER DEWA
REQUIREMENTS.
SUBSTATION SUBSTATION
00
SL
1:1
OP
E
E
R3/DB-SS
OP
1:1
SL
00
PLOT LIMIT PLOT LIMIT PLOT LIMIT
SERVICE BLOCK SERVICE BLOCK SERVICE BLOCK
1 GROUND FLOOR PLAN 1 GROUND FLOOR PLAN 1 ROOF PLAN
SCALE 1:100 SCALE 1:100 SCALE 1:100 REV. DESCRIPTION DATE
MAIN CONSULTANT
Lead Consultants:
© Drawing & Design Copyright of:
Options Engineering Consultancies
P O Box :377041
ENGINEERING CONSULTANCIES Dubai, UAE
T:+971 (4) 2854383
F:+971 (4) 2855251
CONTRACTOR
PROJECT NO. PROJECT PLOT NO. LOCATION DRAWING TITLE SCALE DRAWING NO.
OWNER LESSEE GATE LEVEL
PROPOSED WAREHOUSE SUBSTATION & ELEC ROOM SHAIKH MOHAMMED BIN BUTTI BIN HAMED ALHAMED
1099 AL QOUZ IND. THIRD 1:150 EP-104 GOVERNMENT OF DUBAI - DUBAI REAL ESTATE CORPORATION
& WORKSHOP 3680446 POWER LAYOUT
B+G+M UNITED ALSAQER HEAVY EQUIPMENT SERVICE CENTER (WORKSHOP)
SIGN & STAMP BY DM MUNICIPALITY
NOTES
1. CONTRACTOR SHOULD BE SURVEYING & LEVELING AS PER SITE CONDITION IF ANY
CHANGE FOR LEVEL SHOULD BE APPLY TO DM BEFORE THE COMPLETION CERTIFICATE.
2. THE COLUMN INSIDE THE BUILDING WILL COVERED BY CONCRETE / CEMENT BOARD
AS PER ENGINEER APPROVAL.
3. THE AREA CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY APPROVAL
4. THE NO. OF CAR PARKING CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY
APPROVAL
WS
N
SMDB-
AHU CB-1
LV ROOM DETAILS
GROUND FLOOR
(SCALE:- 1:50)
CB-1 LV-PANEL
CB-1
LV-PANEL
SMDB-AHU
MAIN CONSULTANT
Lead Consultants:
© Drawing & Design Copyright of:
Options Engineering Consultancies
P O Box :377041
ENGINEERING CONSULTANCIES Dubai, UAE
T:+971 (4) 2854383
F:+971 (4) 2855251
CONTRACTOR
PROJECT NO. PROJECT PLOT NO. LOCATION DRAWING TITLE SCALE DRAWING NO.
OWNER LESSEE GATE LEVEL
PROPOSED WAREHOUSE LV ROOM DETAILS SHAIKH MOHAMMED BIN BUTTI BIN HAMED ALHAMED
1099 AL QOUZ IND. THIRD 1:150 EP-105 GOVERNMENT OF DUBAI - DUBAI REAL ESTATE CORPORATION
& WORKSHOP 3680446
B+G+M UNITED ALSAQER HEAVY EQUIPMENT SERVICE CENTER (WORKSHOP)
SIGN & STAMP BY DM MUNICIPALITY
ELECTRIC FIRE PUMP JOCKEY PUMP
TCL = 60.00 kw TCL = 6.00 kw
PUMP MOTOR PUMP MOTOR DIESEL FIRE PUMP
CONTROL PANEL CONTROL PANEL BATTERY CHARGER DB-B
TCL = 4.00 kw TCL = 16.00 kw
TPN TPN TPN
4C,70mm² XLPE/SWA/PVC/CU+
4C,16mm² XLPE/SWA/PVC/CU+
4C,16mm² XLPE/SWA/PVC/CU+
4C,16mm² XLPE/SWA/PVC/CU+
1C,35mm² Y/G CU. AS ECC
RYB1
RYB2
RYB3
RYB4
AS PER ENGINEER APPROVAL.
200A. TPN + E TINNED CU BUS BARES. SMDB-B 3. THE AREA CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY APPROVAL
4. THE NO. OF CAR PARKING CAN BE ADJUSTED DURING FINAL DESIGN AND AUTHORITY
TCL : 86.00 Kw APPROVAL
DIVERSITY : 1.00
200A TP
V + A
ACH + HST MD : 86.00 Kw
MCCB N/A
50KA V + A
R Y B
E- BAR R Y B ACH + HST
N- BAR
S
LOCATION OF SMDB-B : BASEMENT FLOOR
W
N
AHU-GF 1 AHU-GF 2 AHU-GF 3 AHU-GF 4 AHU-MF 1 AHU-MF 2 AHU-MF 3 AHU-MF 4 AHU-SPARE
SPARE TCL = 11.20 kw TCL = 11.20 kw TCL = 11.20 kw TCL = 11.20 kw TCL = 11.20 kw TCL = 11.20 kw TCL = 11.20 kw TCL = 11.20 kw TCL = 5.60 kw
DB-SHOWROOM DB-GF1 DB-GF2 DB-TEL DB-EXT DB-SM TCL= 10.60 kw ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR
TPN TPN TPN TPN TPN TPN TPN TPN TPN
TCL = 25.30 kw TCL = 20.80 kw TCL = 39.80 kw TCL = 8.00 kw TCL = 13.50 kw TCL = 30.00 kw
4C,10mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
1C,10mm² Y/G CU. AS ECC
4C,16mm² XLPE/SWA/PVC/CU+
4C,35mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,25mm² XLPE/SWA/PVC/CU+
1C,16mm² Y/G CU. AS ECC
RYB1
RYB2
RYB3
RYB4
RYB4
RYB4
RYB4
RYB4
RYB4
25KA 25KA 25KA 25KA 25KA 25KA 25KA
RYB1
RYB2
RYB3
RYB4
RYB5
RYB5
RYB6
200A. TPN + E TINNED CU BUS BARES.
SMDB-AHU
300A. TPN + E TINNED CU BUS BARES.
SMDB-GF TCL : 95.20 Kw
200A TP DIVERSITY : 1.0
TCL : 148.00 Kw V + A
V + A
300A TP MCCB N/A ACH + HST
DIVERSITY : 1.0 MD : 95.20 Kw
MCCB N/A V + A R Y B ACH + HST 35KA
V + A MD : 148.00 Kw R Y B
35KA E- BAR
R Y B ACH + HST N- BAR
R Y B ACH + HST
E- BAR N- BAR
FAHU
TCL = 10.00 kw
CHILLER PUMP-1 CHILLER PUMP-2 CHILLER PUMP-3 CHILLER PUMP-1 CHILLER PUMP-2 CHILLER PUMP-3
DB-MEZZ 1 DB-MEZZ 2 CONTROL PANEL FUTURE LIFT SPARE SPARE
TCL = 21.00 kw TCL = 21.00 kw TCL = 21.00 kw TCL = 21.00 kw TCL = 21.00 kw TCL = 21.00 kw
TCL = 18.20 kw TCL = 22.60 kw ISOLATOR TCL = 6.00 kw TCL = 10.00 kw TCL = 10.00 kw
ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR
TPN TPN TPN TPN TPN TPN TPN
4C,16mm² XLPE/SWA/PVC/CU+
4C,10mm² XLPE/SWA/PVC/CU+
4C,16mm² XLPE/SWA/PVC/CU+
4C,16mm² XLPE/SWA/PVC/CU+
4C,16mm² XLPE/SWA/PVC/CU+
4C,16mm² XLPE/SWA/PVC/CU+
4C,16mm² XLPE/SWA/PVC/CU+
4C,16mm² XLPE/SWA/PVC/CU+
4C,4mm² XLPE/SWA/PVC/CU+
1C,16mm² Y/G CU. AS ECC
40A TP 60A TP 32A TP 32A TP 63A TP 63A TP 63A TP 32A TP 63A TP 63A TP 63A TP 32A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA
RYB1
RYB2
RYB3
RYB4
RYB1
RYB2
RYB3
RYB4
RYB1
RYB2
RYB3
RYB4
125A. TPN + E TINNED CU BUS BARES. 160A. TPN + E TINNED CU BUS BARES. 160A. TPN + E TINNED CU BUS BARES.
SMDB-MEZZANINE SMDB-CHILLER SMDB-CHILLER
TCL : 56.80 Kw TCL : 73.00 Kw TCL : 73.00 Kw
125A TP DIVERSITY : 1.0 V + A 160A TP DIVERSITY : 1.0 V + A 160A TP DIVERSITY : 1.0
MCCB N/A MD : 53.00 Kw MCCB N/A V + A MCCB N/A V + A
V + A V + A ACH + HST MD : 73.00 Kw ACH + HST MD : 73.00 Kw
35KA R Y B ACH + HST 35KA R Y B ACH + HST 35KA
R Y B R Y B
R Y B ACH + HST R Y B ACH + HST
E- BAR N- BAR E- BAR N- BAR E- BAR N- BAR
LOCATION OF SMDB-MEZZANINE : MEZZANINE FLOOR LOCATION OF SMDB-CHILLER : CHILLER. ROOM LOCATION OF SMDB-CHILLER : CHILLER. ROOM
CHILLER-1 CHILLER-2
TCL = 143.70 kw TCL = 143.70 kw SPARE SPARE SPARE
CONTROL PANEL CONTROL PANEL
DB-SS
TCL = 42.00 kw TCL = 80.00 kw TCL = 80.00 kw TCL = 2.00 kw
ISOLATOR ISOLATOR
TPN TPN
3x4C,240mm² XLPE/SWA/PVC/CU+
1x4C,185mm² XLPE/SWA/PVC/CU+
1x4C,185mm² XLPE/SWA/PVC/CU+
1x4C,185mm² XLPE/SWA/PVC/CU+
1x4C,95mm² XLPE/SWA/PVC/CU+
1x4C,50mm² XLPE/SWA/PVC/CU+
1x4C,70mm² XLPE/SWA/PVC/CU+
1x4C,95mm² XLPE/SWA/PVC/CU+
1x2C,16mm² XLPE/SWA/PVC/CU+
RYB11
RYB1
RYB2
RYB3
RYB4
RYB5
RYB6
RYB7
RYB8
RYB9
RYB9
B10
P O Box :377041
2500A. TPN + E TINNED CU BUS BARES.
VOLT METER +
POWERFACTOR
METER PF
ENGINEERING CONSULTANCIES Dubai, UAE
AMMETER +
FORM-4 , TYPE-6
T:+971 (4) 2854383
PF
SELECTOR SWITCH SELECTOR SWITCH 1000A TP
3NoS PHASE ACH LV PANEL
ACB
35KA
F:+971 (4) 2855251
INDICATOR LAMP PMU
OS SC EF
AUTO TRANSFER 2500A.4P TCL : 950.00 Kw
V + A + PF SWITCH
SEGREGATED WITH SEPARATE M
K.W.H-CT METER D.O TYPE A.C.B DIVERSITY : 1.0
2500A.4P 2500/5A
COMPARTMENT FOR PAD LOCKING 65KA
EARTH BAR HA R Y B ACH + HST D.O TYPE A.C.B (CHECK METER 0.9S) ELECTRO MECHANICAL MD : 950.00 Kw
SEALING PROVISION BY DEWA 65KA
OC/SC
CASTLE KEY INTER LOCK N- BAR
SET TO 0.9 SET TO 0.9
CONTRACTOR
2x1C,150mm² Y/G PVC/SC
LOCATION OF LV PANEL : LV ROOM
SUBSTATION
EP-1 EP-2 BY DEWA
TRANSFORMER
1500KVA
PROVISION FOR
BY DEWA MOBILE GENERATOR
PROJECT NO. PROJECT PLOT NO. LOCATION DRAWING TITLE SCALE DRAWING NO.
OWNER LESSEE GATE LEVEL
PROPOSED WAREHOUSE SINGLE LINE DIAGRAM SHAIKH MOHAMMED BIN BUTTI BIN HAMED ALHAMED
1099 AL QOUZ IND. THIRD 1:150 EP-106 GOVERNMENT OF DUBAI - DUBAI REAL ESTATE CORPORATION
& WORKSHOP 3680446
B+G+M UNITED ALSAQER HEAVY EQUIPMENT SERVICE CENTER (WORKSHOP)