PIPING SUPPORT LOAD CALCULATION SHEET

Operating Wt Operating
Max No. of Total Empty Total Test. Total Operating Load
Pipe Pipe Empty Pipe Wt + Insulation Wind Insul./ Pipe Wt + (Kg/m) = Wind Load load + Wind
Pipe Support Pipe Support tag Support Pipe Support Height Water Wt Pipe Load Load KN
Line Designation Phase Size length Pipe Wt Water Wt thickness Pressure Lining Wt. Ins. Wt Empty (Lateral) Load REMARKS
Node Number number Type Sch. for Limit (m) (Kg/m) (Vertical). (Vertical)
mm M (Kg/m) (Kg/m) mm in Kpa (Kg/m) (Kg/m) Pipe+Insulati KN (Lateral)
stop KN KN
on+Water KN
AXIAL VERTCIAL LATERAL

PIPE LOAD CALCULATION AT TIER GL 15600 ~ GL +18200 MM


0.36 1.80
L6-1 82-5058 14"-95-BDU8302-LM1 LIQUID 356 R 10 2.5 55 147 18.2 1.35 0 55 92 147 1.35 3.61 1.08 3.61 1.44
PIPE LOAD CALCULATION AT TIER GL 18200 ~ GL +21500 MM
L7-1 82-5513 6"-95-MHU8202-MB1-H7 LIQUID 150 R 40 2.6 30 47 22.0 1.38 0 30 17 47 0.77 1.20 0.36 1.20 0.12 0.00 0.00
PIPE LOAD CALCULATION AT TIER GL 21500 ~ GL +25000 MM
2.13 7.62 Added valve weight
L8-1 82-6008 18"-95-MHU8202-LB1-P6 LIQUID 457 R 10 6 71 226 40 25.5 1.42 8 79 155 234 4.18 13.30 6.40 21.32 5.49
L8-2 82-6011 18"-95-MHU8202-LB1-P6 LIQUID 457 R 10 1.05 71 226 40 25.5 1.42 8 79 155 234 0.73 2.33 0.72 2.41 0.24 0.96 1.20
L8-3 82-6501 18"-95-MHU8202-LB1-P6 LIQUID 457 R 10 2 71 226 40 25.5 1.42 8 79 155 234 1.39 4.43 1.38 4.59 0.46 1.83 2.29
L8-4 82-XXXX 18"-95-MHU8202-LB1-P6 LIQUID 457 R+G 10 2.1 71 226 40 25.5 1.42 8 79 155 234 1.46 4.66 6.11 20.37 6.11 1.92 8.03 Added valve weight
L8-5 82-6502 18"-95-MHU8202-LB1-P6 LIQUID 457 R+G 10 1.8 71 226 40 25.5 1.42 8 79 155 234 1.25 3.99 5.91 19.68 5.91 1.65 7.55

NOTES :
1) Insulation density = 130kg/m3.

2) Operating Weight for Vapour service is 1/3 rd of water actual value.

3) Total test weight has been taken as the summation of total empty pipe weight & the water weight of the pipe in the section

4) Guide load are calculated based on 0.3xVertical load.

5) Axial load are calculated based on sum of number of supports vertical load on longest section of upstream or downstream section from axial stop, multiplied with friction co-efficient 0.3

6) Wind loads are calculated for 10" & above piping based on BS 6399-2 considering wind drag/force co-efficient = 1.2, Wind Pressure is taken from Project Design Basis para 7.2.3-e

7) For rest support lateral load shall be 0.1 of vertical load

8) For rest support Axial load shall be 0.3 of vertical load

9) SUPPORT LEGEND; R- Rest, G-Guide, L-Axial Stop