SCHEMATIC DIAGRAM OF 220/132 KV RECEIVING SUBSTATION CUM 132/55 KV TRACTION SUBSTATION AT JAGADHARI

6
6
(under construction)to Meerut

(under construction)to Meerut


6

132 kV IR Transmission line

132 kV IR Transmission line


132 kV IR Transmission line

1
1
132 kV IR Transmission line

(Future) to Sahnewal(IR)
(Future) to Sahnewal(IR)

25
25

FUTURE FEEDER
25

25

FUTURE MAIN
MAIN LINE
4
4

FEEDER
4

5
5
5

5
100kVA, 25kV/ 240V

3
3
AUX. TRANSFORMER

3
12
13
LV POWER SUPPLY
132/55 kV SCOTT-CONNECTED 55kV DP
TRACTION TRANSFORMER 55kV ISOLATOR
CURRENT TRANSFORMER
FUTURE PROVISION
7 9 11 AUTO
3 132kV CT 5 TRANSFORMER
25 6 8
F 55kV/ 2X25kV

T 15
T
8
F 8
M 14 18 14
T
132kV 11 9 10 11 26 8
132 kV ,TP 4 LA
TP ISOLATOR 2
CIRCUIT BREAKER LA
LV BUSHING CT'S 55kV DP
WITH ISOLATOR CIRCUIT BREAKER
14 15 26 8
HV BUSHING CT'S 14
3 5 3 14
14

CT
26 8 8
27 16 17 18
14 9 Power Factor
Correction Unit
18 14
11 9 10 11 26 26 8
3

3
14 14 22 24

TO BURIED
8 CUT-IN 24

RAIL
14 INSULATOR
5

5
CT
26 27 16 17 PTFE
26 14 9 Power Factor NEUTRAL
Correction Unit 15 SECTION
4

4
23
18 8 55kV DP
8 INTERRUPTER
14 18 14 24 24
25

25
26
11 9 10 11 8
26
23
6

6
STANDBY
AUTO TRANSFORMER
14 8
14 14
14 14
POWER TRANSFORMER

POWER TRANSFORMER
150 MVA, 220/132 kV

150 MVA, 220/132 kV

CT
26 27 16 17
14 9 Power Factor
7A

7A

Correction Unit 26
14 15
26 9 27 16 8 8 18
132/55 kV SCOTT-CONNECTED
TRACTION TRANSFORMER 18 14
17 26 8
14 26
132kV TP
6

CIRCUIT BREAKER 7 9 2
3 25 11
6 8
F 11 9 10 11 8
T
4A

4A

14 14
T
55kV/110V
F POTENTIAL TRANSFORMER 55kV/110V
(Protection Type) LINE POTENTIAL TRANSFORMER
M
5A

5A

T
4 25kVA, 25kV/240V
5 AUX. TRANSFORMER
LA LA 13
3A

3A

LV POWER SUPPLY
12
220 kV ,TP ISOLATOR
F T F T
T-BUS M-BUS

MAIN LINE

FUTURE MAIN
FEEDER

FUTURE FEEDER
3A
1A

1A

LEGENDS
6

6
25

25

REF. SYMBOL
NO. DESCRIPTION 10 55 kV DOUBLE POLE CIRCUIT BREAKER

CIRCUIT 2
1 132 kV TRIPLE POLE ISOLATOR WITH EARTH BLADE
11 55 kV DOUBLE POLE ISOLATOR
CIRCUIT 1

1A 220 kV TRIPLE POLE ISOLATOR WITH EARTH BLADE


12 AUXILIARY TRANSFORMER
220 kV INCOMING FROM PGCIL
2 55 kV DOUBLE POLE CIRCUIT BREAKER(Transformer Bay) 13 DROP OUT FUSE SWITCH

3 132 kV TRIPLE POLE ISOLATOR


14 55 kV/110V POTENTIAL TRANSFORMER GENERAL CONSULTANT
3A 220 kV TRIPLE POLE ISOLATOR
15 AUTO TRANSFORMER (55kV / 2 X 25 kV)

4 132 kV CURRENT TRANSFORMER


16 55 kV Power Factor Correction Unit-I

NOTES:- 4A 220 kV CURRENT TRANSFORMER


1. The drawing is indicative and shall be read in conjunction with the
17 55 kV Power Factor Correction Unit-II EASTERN CORRIDOR
5 132 kV TRIPLE POLE CIRCUIT BREAKER
specifications & relevant standards if any. PROJECT SAHNEWAL TO PILKHANI
18 55 kV DOUBLE POLE INTERRUPTER (VACUUM / SF6)
2. All ratings/dimensions are indicative.The contractor shall provide 5A FROM CH: 116440 TO CH: 170600
220 kV TRIPLE POLE CIRCUIT BREAKER
the design as approved by the Engineer. 23 PTFE NEUTRAL SECTION STRUCTURE
3. The Equipment and the other structure shown by dotted line is
6 LIGHTNING ARRESTER CONTRACT PACKAGE - 304
132/55kV, 60/84/100 MVA SCOTT-CONNECTED 24 CUT-IN INSULATOR TITLE
indicated only for space requirement of future extension during 7
T

TRACTION TRANSFORMER WITH BUSHING CTs. M

doubling the section. 7A 220/132kV, 150 MVA POWER TRANSFORMER


25 132kV/110 V POTENTIAL TRANSFORMER

4. However, the Provision of Gantry for termination of 132kV outgoing SCALE DATE DRAWN BY CHECKED BY APPROVED BY DRG. NO. REV.
8 26 55 kV DOUBLE POLE ISOLATOR(Line Feeder)
transmission line will have to be constructed by the contractor LIGHTNING ARRESTER

under this contract (CP-304). 9 55 kV, CURRENT TRANSFORMER 27 55 kV DOUBLE POLE CIRCUIT BREAKER( for capacitor bank) NTS 12-05-2017 K.R. A.K.D. A.K.D GC/DFCC/PS/TSS/SCH/TYP/101