Over Current and Earth Fault Setting 11kV
Over Current and Earth Fault Setting 11kV
Over Current and Earth Fault Setting 11kV
Stage-2: DMT/INSTANTANEOUS
Time=0 sec
Stage-1 : IDMT
Stage-2: DMT/INSTANTANEOUS
Time=0
11kV Incoming
Setting= 525*1.2 A
Stage-3: DMT/INSTANTANEOUS
Current= Maximum Fault Current*70% [at 11 kV (3Phase Fault MVA=10MVA/%Z= 10/0.08= 125 MVA, If=
125/(1.732* 11= 6.5kA)]= 4.5kA
Time=0 sec