Professional Documents
Culture Documents
AC I DC Power System Fault Simulation Based On
AC I DC Power System Fault Simulation Based On
AC I DC Power System Fault Simulation Based On
ADPSS
Changhui Ma Qun Xu
Shandong Electric Research Institute Shandong Qingdao Power Supply Company
Jinan, China Qingdao, China
e-mail: machanghui@163.com e-mail: xuqunxuqun@sina.com
Abstract—Both the security of the whole network and the they are often related to the structure of AC/DC system and
operating characteristics of a DC system need to be simulated in specific operating condition. Usually, the electromechanical or
detail for a large-scale AC/DC power system. Through transient electromagnetic transient simulation method is applied in the
hybrid simulation, virtues of electromechanical-electromagnetic simulation of DC power transmission system separately. The
can be achieved simultaneously. Based on mechanism analysis of advantage of the electromechanical transient simulation is that
electromechanical-electromagnetic transient hybrid simulation, it is able to simulate large-scale systems, but the disadvantage
three operation modes of Shandong Power Grid in 2010 are is that many phenomena such as the influence of unbalanced
analyzed. Various HVDC faults and the AC faults near the point faults on the operating condition of converter valves, the inner
of fall for HVDC are simulated by the electromechanical
faults of converter valves, the commutation failure of inverters,
transient simulation and the electromechanical-electromagnetic
the effect of control system on the process of commutation,
transient hybrid simulation based on ADPSS. Simulation results
from two different simulation methods are compared. The cannot be modeled exactly because all DC power transmission
superiority of hybrid simulation is demonstrated convincingly systems adopt quasi-steady-state model. However, the
through the simulation of commutation failure. electromagnetic transient simulation has shortcomings also,
such as small-scale stimulation and slow calculation speed. For
Keywords—advanced digital power system simulator(ADPSS); simulating a system, equivalent simplification has to be
AC/DC power system; hybrid simulation;HVDC finished, which reduces the calculation accuracy. And if the
operation mode changes, the equivalent simplification needs to
be done again. This will cause huge work burden[2].
I. INTRODUCTION
China Electric Power Research Institute took 8 years to
At present, the two main subjects in the development of
research and develop the ADPSS, which achieved both
China power grid are the "West-East Electricity Transmission"
theoretical innovation and technical breakthrough on key
and the "National United Power Grid" project. The project of
technologies such as the real-time simulation of large-scale
DC power transmission from the east of Yinchuan to Jiaodong,
power system and the electromechanical-electromagnetic
which connects the Northwest Power Grid and the Shandong
transient hybrid simulation. ADPSS overcomes the deficiencies
Power Grid, has been brought into service in the latter half of
of other similar simulation devices inland and abroad, which
2010. The designed capacity of this DC project is 4000MW for
can only simulate small-scale systems and are hard to be
two poles. Only monopolar operation mode has been brought
updated and expanded[2-4].
into service in 2010 and the whole project will be put into
operation completely in 2011. Along with the project being put ADPSS achieves the electromechanical-electromagnetic
into operation, the power sources of Shandong Power Grid are transient hybrid simulation mode, which combines both of their
becoming more and more complicated, which means growing virtues. While the AC/DC power system is being stimulated
instabilities. and analyzed, the electromagnetic transient simulation is used
in parts of a DC system which need to be researched in detail
For a large-scale AC/DC power system, it is very
and the electromechanical transient simulation is adopted in the
significant to study the interaction between AC and DC
other parts of the network. In this case, the interior rapid
system[1] such as what kind of faults in AC systems may lead to
transient change process of DC devices can be simulated. And
commutation failure and what measures should be taken to
meanwhile, the network calculation scale can be huge and the
keep the system stable to the greatest extent. Those problems
power grid doesn't need to be equivalently simplified, which
can be solved only through simulation and calculation based on
greatly improves the accuracy of simulation and analysis[5-7].
the software for large-scale AC/DC power system, because
515
concentrated in the western region, while the capacity is "West to East electricity transmission" lines, which weakens
relatively small in central and eastern region; from the aspect the characteristics of "West to East electricity transmission" in
of the load of each region, the load of the central and eastern Shandong Power Grid. Instead, the features of "South to North
region (mainly Jinan, Zibo, Qingdao, Weifang, Yantai) is more electricity transmission" become more distinctive in central and
concentrated, while the quantity is relatively small in western western regions. And the influence of DC fault is just the
region. So integrating the generation with the load condition, opposite.
Liaocheng and Jining are the main power generation areas;
while Zibo, Weifang, Yantai and Qingdao are the major power IV. SIMULATION RESULTS
consumption areas.
Figure 2 is the sketch map of 500kV main grid of Shandong A. System Analysis
Power Grid in 2010, which shows the feature of "West to East The simulation analysis process focuses on studying a kind
electricity transmission". of control method that combines constant DC current control at
the rectification side of DC control system with low-voltage
current-limiting control, and integrates constant turn-off angle
control at the inversion side with low-voltage current-limiting
control. This approach is often used in DC power transmission
project and obtains a good operating performance . But the
control model does not consider the frequency modulation and
power modulation.
System analysis results are shown in Table 2, where
monopolar faults include short circuit and open circuit; bipolar
faults include grounding short circuit, shot circuit and bipolar
open circuit; and AC faults include single-phase as well as
three-phase short, break and other kinds of faults. Both static
security analysis and safety checking programs apply the
failure modes described in 1.2 (1). And after DC faults exit
from operation, the system is analyzed.
Figure 2. Sketch map of Shandong 500kV power grid in 2010
516
Figure 4. Simulation results of short-circuit fault of ac line near the HVDC
in bipolar operation mode
C. AC Faults
Under DC bipolar operation mode, the fault is set to be a
three-phase permanent grounding at the head of "Jiaodong-
Daze 500kV line" from Jiaodong converter station. In addition,
it happens at 3.0s and after 0.1s, the protection of the lineis
triggered . The observed simulation results are identical to the
above, as shown in Figure 4.
Figure 5. Influence of monopolar block on system frequency under
monopolar operation mode
E. Result Analysis
The results of transient stability (including
electromechanical transient analysis and electromechanical-
electromagnetic hybrid analysis) show a good transient
stability under both monopolar and bipolar operation modes of
Yinchuan-Jiaodong DC power transmission system, and the
system is able to maintain stability when DC lines have faults
and AC systems near DC lines have faults. Additionally, when
faults happen in DC lines, after checking the security and
stability of the system, it is found that the system still could
keep transient stability.
Although most of the analysis results (except the
commutation failure simulation) of the hybrid simulation are
not inconsistent with that of the electromechanical transient
simulation, it is apparent that the hybrid simulation is able to
517
depict the post-fault dynamic process more detailed, especially of commutation failure of electromechanical transient
the recovery process. simulation is [0,27] (ohm), and that of hybrid simulation is
[0,118] (ohms). Therefore, in the grounding resistance range
V. SIMULATION OF COMMUTATION FAILURE [28,118], the results of electromechanical transient simulation
and hybrid simulation are inconsistent.
To simulate the phenomenon of DC commutation failure, in
monopolar operation mode, "Jiaodong Convertor Station 500"
bus of Inverter station bus on the AC side is set a three-phase VI. CONCLUSION
grounding short circuit with grounding resistance of 100 ohms. Because of the limitation of calculation data, in the
The start time of grounding is 3.0s, and the end time is 3.1s. examples above, detail data of Northwest China Power Grid
The simulation results are shown in Fig.6. It is obvious that the and Shandong Power Grid can not be acquired. And then
results of electromechanical and electromagnetic transient Northwest China Power Grid is substituted by equivalent
simulation are completely different, and there are no generator, which may influences the results of simulation to
commutation failure phenomena in the electromechanical some degree.
transient simulation. However, from the valve current
waveform of the hybrid simulation, it can be clearly seen that China has become the country with the most DC projects
the relative physical process of commutation failure, so the that are being built and have been built. Therefore, the study on
criterion of the electromechanical transient simulation is too AC/DC power systems is of great significance. The hybrid
"optimistic" in this example. simulation function of ADPSS is a powerful tool for studying
practical interacted system on a large scale. It also provides a
kind of resolution for the conflict between the scales, the
rapidity and accuracy of power system simulation.
REFERENCES
[1] Xu Zheng, Cai Ye, Liu Guoping. Some problems in the simulation of
large-scale AC/DC power systems[J]. Automation of Electric Power
Systems. 2002,26(15): 4-8.
[2] Tian Fang, Li Yalou Zhou Xiaoxin, and et al. Advanced Digital power
system simulator[J]. Power System Technology, 2008, 32(22): 17-22.
[3] User manual for Advanced Digital Power System Simulator. China
Electric Power Research Institute, 2007
[4] Tian Fang, Li Yalou Zhou Xiaoxin, and et al. Research, development
and application of advanced digital power system simulator(ADPSS)[C].
The International Conference on Electrical Engineering 2008, Okmawa,
Japan, 2008.
[5] Yue Chengyan, Tian Fang, Zhou Xiaoxin, et al. Principle of interfaces
for hybrid simulation of power system electromagnetic-
electromechanical transient process[J]. Power system Technology, 2006,
30(1): 23-27, 87.
[6] Yue Chengyan, Tian Fang, Zhou Xiaoxin, et al. Implementation of
interfaces for hybrid simulation of power system Technology
electromagnetic-electromechanical transient process[J]. Power System
Technology, 2006,30(4):7-10.
[7] Yue Chengyan, Tian Fang, Zhou Xiaoxin, et al. Application of hybrid
simulation of power system electromagnetic electromechanical transient
process[J]. Power system Technology, 2006,30(11):1-5.
[8] Guide on Security and Stability for Power System. State Economic and
Trade Commission, DL755-2001
[9] Zhang Shuqing, Liang Xu, Tong Luyuan, et al. Key Technologies of the
power system electromagnetic/ electromechanical real-time hybrid
simulation, Implementation of interfaces for hybrid simulation of power
system Technology[J]. Automation of Electric Power Systems, 2008,
32(15): 89-96.
518