Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software


Home / Articles / Low Voltage Design

Protective Earth Cable Sizing


How to properly size earth cables - includes the Method, Equations, Constants
and Example Calculations

Avoiding damage to earth cables during faults

Correct sizing of protective earth (PE) cables is extremely important in order to safely clear
phase-to-earth faults. When a fault occurs there are high levels of thermal energy, referred
to as Joule Integral, generated during the clearing time of the protective device which
operates to disconnect the faulty equipment. This let-through energy should be compared
with the maximum permissible thermal energy that a protective earth (PE) cable can
withstand. This is the topic of this article.

Another important factor to consider when sizing PE cables is earth fault loop impedance,
which means the impedance should be sufficiently low to allow adequate fault current to

https://elek.com/articles/protective-earth-cable-sizing/ 1/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

pass for the protective device to operate within a sufficiently short time which is again, for
safety.

To avoid damage to a PE cable during a fault it must be capable of withstanding the let-
through energy of the protective device. The thermal withstand capability depends on
these factors:

Conductor cross-sectional area


Conductor material (e.g. copper)
Insulation type (e.g. PVC)
Initial temperature at the inception of the fault
Maximum temperature it can withstand without damage

Note that in some instances a PE cable may be a bare conductor without insulation.

It is also important to note not only the PE cable but that all components in the fault path
such as terminations, joints and bonds must also have adequate thermal withstand
capability.

How to calculate minimum earth conductor size


1. Obtain the material constants for the conductor type from Table 1.
2. Obtain the temperature limits for the cable type from Table 2.
3. Determine initial temperature, θ0:
a. Use Normal use temperature of the loaded phase cable – if the PE cable is
combined inside a multicore cable or bunched with a phase conductor;
otherwise
b. Use ambient environment temperature (i.e., 25 ˚C for buried or 40 ˚C in air –
check your local standards).
4. Determine maximum short-circuit temperature, θM:

5. Calculate k2 using equation 2.


6. Calculate minimum conductor size S using equation 3.

There are example calculations at the end of this report.

Equations to use:

The fundamental equation 1 is given below where the left side is the let-through energy
developed during the fault and the right side represents the energy withstand of the cable.

\(\int_{0}^{t_f} {i^2}_G \,dt \leq k^2S^2\) Equation 1

https://elek.com/articles/protective-earth-cable-sizing/ 2/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

Where iG is the instantaneous earth fault current, tf is the fault clearing time, S is the cross-

sectional area of the conductor (mm2) and k2 is a factor that considers the resistivity,
temperature coefficient and heat capacity of the conductor material, the initial

temperature of the protective conductor at the inception of the fault and maximum
permissible short-time temperature of the cable.

The equation for the factor k2 is given as follows.

\(k^2 = \frac{c}{\alpha_0\rho_0}\ln{\frac{1+\alpha_0\theta_M}{1+\theta_0\alpha_0}}\)
Equation 2

Where α0 is the temperature coefficient of resistivity of the conductor material, c is the


volumetric heat capacity, ρ0 resistivity, θ0 is initial temperature and θM is maximum

permissible short-time temperature. Typical values of constants for calculating k2 are given
in Table 1 and Table 2.

Note that smaller values for the k2 factor determine larger PE conductor sizes for the same
fault current and clearing time.

The analytical evaluation the left side of equation 1 is quite difficult because the fault
current iG is asymmetrical due to the transient DC component. Therefore, the IEC Standard
[1] has provided a simplified equation 3 below to determine the minimum cross-sectional
area of a PE conductor assuming adiabatic conditions and suitable only for fault clearing
times within 5 seconds.

\(S \geq \frac{I_G}{k}\sqrt{t_f}\) Equation 3

The minimum conductor size given by equation 3 should be rounded up to the nearest
commercially available size. Of course, equation 3 can be used for different types of
protective conductors and not only for cables including armors, metallic sheaths, screens
etc.

Initial temperature

The initial temperature of the PE cable may be taken as either:

1. Same as the operating temperature of the phase cables.

https://elek.com/articles/protective-earth-cable-sizing/ 3/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

This assumption is appropriate for PE cables integrated with the phase conductors (i.e.,
multicore cables) but too conservative for separate PE cables which will result in oversizing.

2. The ambient temperature of the environment. 


This assumption is appropriate when the PE cable is separate and not bunched with the
load-carrying phase cables.

Non-adiabatic calculations

The adiabatic equation 3 assumes the let-through energy of the protective device is
entirely accumulated within the PE cable during the fault and that none of heat generated
is dissipated to the outside environment. According to the NFPA National Electrical Code
[3] the adiabatic assumption is reasonable and practical for most cases where they state
that the non-adiabatic condition is only useful in practice for very small conductors of 10
mm2 or less.

The IEC Standard [2] provides a non-adiabatic method and set of equations for
determining minimum conductor size. In practical terms the non-adiabatic equations are
useful for short-circuit ratings of power cable phase conductors and metallic components.

Reference data

Table 1. Material constants for calculation of k2

Resistivity, ρ0 Temperature coefficient of Volumetric heat capacity,


Material
(Ω.mm) resistivity, α0 (per K at 20 ˚C) c (J.mm-3.K-1)

Conductors
- Copper 1.7241 x 105 3.93 x 103 3.45 x 103
- Aluminium 2.8264 x 105 4.03 x 103 2.422 x 103

Sheaths and
armour
- Lead or lead 21.4 x 105 4 x 103 1.44 x 103

alloy 13.8 x 105 4.5 x 103 3.756 x 103


- Steel 70 x 105 Negligible 3.756 x 103
- Stainless steel 4.03 x 103
2.84 x 105 2.422 x 103
- Aluminium

Table 2. Temperature limits for insulating materials in contact with conductors

Insulation type Operating temperatures of conductors

https://elek.com/articles/protective-earth-cable-sizing/ 4/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

Normal use (˚C) – Short time maximum, θM (˚C)


Note 1 – Note 2

Thermoplastic: V-75, HFI-75-TP, TPE-75, V-90, HFI-
90-TP, TP-90, V-90HT
75 140
- Up to and including 300 mm2
75 160
- Greater than 300 mm2

Polyethylene: PE, LLDPE


- Up to and including 300 mm2 70 140
- Greater than 300 mm2 70 160

Cross-linked elastomeric:
- R-EP-90, R-CPE-90, R-HF-90, R-CSP-90 90 250
- R-HF-110, R-E-110 110 250

Cross-linked polyolefin (XLPE):


- X-90, X-90UV, X-HF-90 90 250
- X-HF-110 110 250

Mineral-insulated metal-sheathed (MIMS) 100 250 (conservative)

High temperature: R-S-150 and Type 150 fibrous 150 350

Paper 85 250

Notes:
1. The Normal use temperature relates to the sustained current-carrying capacity.
2. The Short time maximum temperature is permitted under short-circuit conditions.

Worked examples - calculating minimum earth size


Example 1 – separate earth cable

Size an underground protective earth cable which is separated away from the main power
cables and made up of copper conductors and will be PVC V-75 insulated. The maximum
earth fault current is 3.5 kA and associated fault clearing time is 0.3 seconds.

Solution

The material constants from Table 1 are:

Temperature coefficient α0 = 3.93 x 10-3 per K at ˚C

https://elek.com/articles/protective-earth-cable-sizing/ 5/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

Volumetric heat capacity c = 3.45 x 10-3 J.mm-3.K-1

Resistivity ρ0 = 1.7241 x 10-5 Ω.mm



The initial and maximum temperatures are:

Initial temperature θ0 = 25 ˚C which is assumed to be the temperature of the soil


(environment).

Final temperature θM = 140 ˚C taken from Table 2 for conductor sizes ≤ 300 mm2.

The k2 factor is calculated using equation 2 to be 17549.

Therefore, using equation 3 the minimum size of the conductor should be > 14.47 mm2.
The nearest available trade size is 16 mm2.

Note if initial temperature is assumed to be 75 ˚C then the minimum size is 20.02 mm2
which leads to a larger earth cable size than necessary.

Example 2 – integrated earth cable

Determine the minimum protective earth cable with a copper conductor which is
integrated inside a low-voltage XLPE (X-90) insulated multicore power cable. The maximum
earth fault current is 5 kA and associated fault clearing time is 0.4 seconds.

Solution

The material constants are same as for Example 1.

The initial and maximum temperatures are:

Initial temperature θ0 = 90 ˚C which is same as the normal operating temperature of the


cable.

Final temperature θM = 250 ˚C taken from Table 2 for XLPE insulated cables.

The k2 factor is calculated using equation 2 to be 19426.

Therefore, using equation 3 the minimum size of the conductor should be > 22.69 mm2.
The nearest available trade size is 25 mm2.

Try the free Earth Cable Size Calculator.

References:
https://elek.com/articles/protective-earth-cable-sizing/ 6/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

IEC Standard 60364-5-54 Electrical Installations of Buildings – Part 5-54: Selection And
Erection Of Electrical Equipment – Earthing Arrangements, Protective Conductors  And
Protective Bonding Conductors.
IEC Standard 949 Calculation of thermal permissible short-circuit currents, taking into
account non-adiabatic heating effects.
National Electrical Code, NFPA 70, 2011.

Cable Pro Web


Cable sizing and maximum demand software in the cloud. No installation, use on any device.

Try For Free

Related Articles:

Understanding Earth Fault Loop Impedance

The purpose of this document is to provide a better understanding of Fault Loop Impedance, also
referred to as Earth Fault Loop Impedance so that the requirements of AS/NZS 3000 Wiring Rules for
safety, design, installation and testing of electrical installation may be met.

Voltage drop limits for Low Voltage installations

https://elek.com/articles/protective-earth-cable-sizing/ 7/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

Voltage Drop Limits per the Wiring Rules AS/NZS 3000 as well as rules of thumb to assist with electrical
design. Includes AC and DC voltage drop or rise limits.

Cable Current Rating Derating Factors Explained

Derating factors are applied to the cable current rating ensuring that cable operating temperature limits
are not exceeded. Derating factors are derived to match the specific cable installation conditions.

Maximum Demand Tables

Reference tables for diversity factors and energy demand from Wiring Rules AS/NZ 3000 for domestic and
non-domestic installations.

https://elek.com/articles/protective-earth-cable-sizing/ 8/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

Neutral Conductor Sizing

The neutral conductor is required for each primary circuit, and there are rules in the Standards for its 
sizing.

Cable Pulling Tension Calculations

This article explains how to perform cable pulling tension and sidewall pressure calculations and also
includes an example.

Voltage Rise Calculations

Voltage rise can occur in solar PV systems on the AC side between the power inverters and network
connection point. Voltage rise calculations are no different to those for voltage drop.

https://elek.com/articles/protective-earth-cable-sizing/ 9/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

Automatic Maximum Demand Calculations

The new maximum demand module provides fast and accurate calculations for loads in accordance with 
rules from the Standards and for custom loads. An ingenious automatic phase balancing algorithm
ensures maximum demand and phase imbalance are both minimised.

Accurate voltage drop calculations

Accurately calculating voltage drop results in lower voltage drops which leads to smaller cable sizes and
saves money.

FOR INFORMATION OR TO SPEAK WITH OUR HELPFUL ADVISORS

GET IN TOUCH

Electrical Power Systems Design & Analysis Software

FOLLOW US

https://elek.com/articles/protective-earth-cable-sizing/ 10/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

SOFTWARE

Cable Pro Web 


Protection Coordination

SafeGrid Earthing

Cable High Voltage

Cable Pulling

Line Rate

Power Bundle

FREE CALCULATORS

Cable Sizing AS3008

Cable Sizing BS7671

Voltage Drop

Arc Flash

Earth Cable Sizing

Fault Loop Impedance

Earth Grid Resistance

Earth Grid Conductor Sizing

Earthing Rods Resistance

Lightning Protection Design

Relay Tripping Time

Equivalent Thermal Resistance

RESOURCES & SUPPORT

Technical Articles

Software Tutorials

Publications

Training and Certification

Customer Licence Portal

CONTACT US

Email:
enquiry@elek.com

Need Help?
Lodge a Support Ticket

https://elek.com/articles/protective-earth-cable-sizing/ 11/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software

Phone:
1300 093 795

International:
+61 (0)2 8231 6673 

© 2023 All Rights Reserved Privacy Policy Quality Policy Security Policy Terms of Use

https://elek.com/articles/protective-earth-cable-sizing/ 12/12

You might also like