Professional Documents
Culture Documents
Protective Earth Cable Sizing - ELEK Software
Protective Earth Cable Sizing - ELEK Software
Home / Articles / Low Voltage Design
Correct sizing of protective earth (PE) cables is extremely important in order to safely clear
phase-to-earth faults. When a fault occurs there are high levels of thermal energy, referred
to as Joule Integral, generated during the clearing time of the protective device which
operates to disconnect the faulty equipment. This let-through energy should be compared
with the maximum permissible thermal energy that a protective earth (PE) cable can
withstand. This is the topic of this article.
Another important factor to consider when sizing PE cables is earth fault loop impedance,
which means the impedance should be sufficiently low to allow adequate fault current to
https://elek.com/articles/protective-earth-cable-sizing/ 1/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
pass for the protective device to operate within a sufficiently short time which is again, for
safety.
To avoid damage to a PE cable during a fault it must be capable of withstanding the let-
through energy of the protective device. The thermal withstand capability depends on
these factors:
Note that in some instances a PE cable may be a bare conductor without insulation.
It is also important to note not only the PE cable but that all components in the fault path
such as terminations, joints and bonds must also have adequate thermal withstand
capability.
Equations to use:
The fundamental equation 1 is given below where the left side is the let-through energy
developed during the fault and the right side represents the energy withstand of the cable.
https://elek.com/articles/protective-earth-cable-sizing/ 2/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
Where iG is the instantaneous earth fault current, tf is the fault clearing time, S is the cross-
sectional area of the conductor (mm2) and k2 is a factor that considers the resistivity,
temperature coefficient and heat capacity of the conductor material, the initial
temperature of the protective conductor at the inception of the fault and maximum
permissible short-time temperature of the cable.
\(k^2 = \frac{c}{\alpha_0\rho_0}\ln{\frac{1+\alpha_0\theta_M}{1+\theta_0\alpha_0}}\)
Equation 2
permissible short-time temperature. Typical values of constants for calculating k2 are given
in Table 1 and Table 2.
Note that smaller values for the k2 factor determine larger PE conductor sizes for the same
fault current and clearing time.
The analytical evaluation the left side of equation 1 is quite difficult because the fault
current iG is asymmetrical due to the transient DC component. Therefore, the IEC Standard
[1] has provided a simplified equation 3 below to determine the minimum cross-sectional
area of a PE conductor assuming adiabatic conditions and suitable only for fault clearing
times within 5 seconds.
The minimum conductor size given by equation 3 should be rounded up to the nearest
commercially available size. Of course, equation 3 can be used for different types of
protective conductors and not only for cables including armors, metallic sheaths, screens
etc.
Initial temperature
https://elek.com/articles/protective-earth-cable-sizing/ 3/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
This assumption is appropriate for PE cables integrated with the phase conductors (i.e.,
multicore cables) but too conservative for separate PE cables which will result in oversizing.
Non-adiabatic calculations
The adiabatic equation 3 assumes the let-through energy of the protective device is
entirely accumulated within the PE cable during the fault and that none of heat generated
is dissipated to the outside environment. According to the NFPA National Electrical Code
[3] the adiabatic assumption is reasonable and practical for most cases where they state
that the non-adiabatic condition is only useful in practice for very small conductors of 10
mm2 or less.
The IEC Standard [2] provides a non-adiabatic method and set of equations for
determining minimum conductor size. In practical terms the non-adiabatic equations are
useful for short-circuit ratings of power cable phase conductors and metallic components.
Reference data
Conductors
- Copper 1.7241 x 105 3.93 x 103 3.45 x 103
- Aluminium 2.8264 x 105 4.03 x 103 2.422 x 103
Sheaths and
armour
- Lead or lead 21.4 x 105 4 x 103 1.44 x 103
https://elek.com/articles/protective-earth-cable-sizing/ 4/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
Cross-linked elastomeric:
- R-EP-90, R-CPE-90, R-HF-90, R-CSP-90 90 250
- R-HF-110, R-E-110 110 250
Paper 85 250
Notes:
1. The Normal use temperature relates to the sustained current-carrying capacity.
2. The Short time maximum temperature is permitted under short-circuit conditions.
Size an underground protective earth cable which is separated away from the main power
cables and made up of copper conductors and will be PVC V-75 insulated. The maximum
earth fault current is 3.5 kA and associated fault clearing time is 0.3 seconds.
Solution
https://elek.com/articles/protective-earth-cable-sizing/ 5/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
Final temperature θM = 140 ˚C taken from Table 2 for conductor sizes ≤ 300 mm2.
Therefore, using equation 3 the minimum size of the conductor should be > 14.47 mm2.
The nearest available trade size is 16 mm2.
Note if initial temperature is assumed to be 75 ˚C then the minimum size is 20.02 mm2
which leads to a larger earth cable size than necessary.
Determine the minimum protective earth cable with a copper conductor which is
integrated inside a low-voltage XLPE (X-90) insulated multicore power cable. The maximum
earth fault current is 5 kA and associated fault clearing time is 0.4 seconds.
Solution
Final temperature θM = 250 ˚C taken from Table 2 for XLPE insulated cables.
Therefore, using equation 3 the minimum size of the conductor should be > 22.69 mm2.
The nearest available trade size is 25 mm2.
References:
https://elek.com/articles/protective-earth-cable-sizing/ 6/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
IEC Standard 60364-5-54 Electrical Installations of Buildings – Part 5-54: Selection And
Erection Of Electrical Equipment – Earthing Arrangements, Protective Conductors And
Protective Bonding Conductors.
IEC Standard 949 Calculation of thermal permissible short-circuit currents, taking into
account non-adiabatic heating effects.
National Electrical Code, NFPA 70, 2011.
Related Articles:
The purpose of this document is to provide a better understanding of Fault Loop Impedance, also
referred to as Earth Fault Loop Impedance so that the requirements of AS/NZS 3000 Wiring Rules for
safety, design, installation and testing of electrical installation may be met.
https://elek.com/articles/protective-earth-cable-sizing/ 7/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
Voltage Drop Limits per the Wiring Rules AS/NZS 3000 as well as rules of thumb to assist with electrical
design. Includes AC and DC voltage drop or rise limits.
Derating factors are applied to the cable current rating ensuring that cable operating temperature limits
are not exceeded. Derating factors are derived to match the specific cable installation conditions.
Reference tables for diversity factors and energy demand from Wiring Rules AS/NZ 3000 for domestic and
non-domestic installations.
https://elek.com/articles/protective-earth-cable-sizing/ 8/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
The neutral conductor is required for each primary circuit, and there are rules in the Standards for its
sizing.
This article explains how to perform cable pulling tension and sidewall pressure calculations and also
includes an example.
Voltage rise can occur in solar PV systems on the AC side between the power inverters and network
connection point. Voltage rise calculations are no different to those for voltage drop.
https://elek.com/articles/protective-earth-cable-sizing/ 9/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
The new maximum demand module provides fast and accurate calculations for loads in accordance with
rules from the Standards and for custom loads. An ingenious automatic phase balancing algorithm
ensures maximum demand and phase imbalance are both minimised.
Accurately calculating voltage drop results in lower voltage drops which leads to smaller cable sizes and
saves money.
GET IN TOUCH
FOLLOW US
https://elek.com/articles/protective-earth-cable-sizing/ 10/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
SOFTWARE
SafeGrid Earthing
Cable Pulling
Line Rate
Power Bundle
FREE CALCULATORS
Voltage Drop
Arc Flash
Technical Articles
Software Tutorials
Publications
CONTACT US
Email:
enquiry@elek.com
Need Help?
Lodge a Support Ticket
https://elek.com/articles/protective-earth-cable-sizing/ 11/12
10/10/23, 6:55 PM Protective Earth Cable Sizing - ELEK Software
Phone:
1300 093 795
International:
+61 (0)2 8231 6673
© 2023 All Rights Reserved Privacy Policy Quality Policy Security Policy Terms of Use
https://elek.com/articles/protective-earth-cable-sizing/ 12/12