O&M Manual - Air Curtain

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 70

O&M

MANUAL

AIR CURTAIN

Rapid Cool Trading Co. L.L.C.


P. O. Box: 2034, Dubai, UAE.
Tel: +971 4 425 6663
Fax: +971 4 276 5891
info@rapidcool.ae
www.rapidcool.ae
OPERATION AND MAINTENANCE MANUAL
AIR CURTAINS
PROJECT:
SKEIKH KHALIFA MEDICAL CITY
OUTPATIENT SPECIALITY CLINIC
PROJECT MAINTENANCE AND
REFURBISHMENT
LOCATION:
ABU DHABI, UAE
CLIENT:
M/s SEHA
CONSULTANT:
M/s MORGAN CONSULTING ENGINEERS
CONTRACTOR:
M/s AL REEM HOSPICO, LLC
SUPPLIER:

M/s RAPID COOL


TABLE OF CONTENTS
1. ABOUT THE PROJECT

2. EMERGENCY ESCALATION PROCEDURES

3. EMERGENCY INFORMATION

4. SYSTEM PURPOSE AND SCOPE

5. DESCRIPTION AND INTERFACE INFORMATION

6. EQUIPMENT SCHEDULE

7. OPERATING INSTRUCTIONS & PROCEDURES

8. MAINTENANCE PROCEDURES

9. SPARE PARTS

10. HSE & DISPOSAL INSTRUCTIONS

11. TESTING AND COMMISSIONING

12. DRAWINGS

13. MANUFACTURER AND SUPPLIERS LITRATURE

14. PRODUCT GUARANTEES AND WARRANTIES


1. ABOUT THE PROJECT
ABOUT THE PROJECT

The project is located in Sheikh Khalifa Medical City, Outpatient Speciality


Clinic. ARH scopes are consisting of the following;
1. Ground Floor (Clinics)

• Consists of Clinic’s 1, 2, 3, 4, VIP Clinic, Public Corridors, Radiology,


Laboratory and Pharmacy. Clinics are composed of Isolation Rooms (1
no.), Procedure Rooms (2 nos.), Treatment Rooms (3 nos.),
Examination Rooms, Patient Rooms, Laser Rooms, Phototherapy
Rooms, ECG Rooms, ENT Rooms, Ophthalmology, Audiology Room,
VNG Room.

• Equipment such as Air Curtains, VAV, CAV, CCU-DX / CHW, Fan Coil
Units, UPS, Transfer Pumps and Filtration System.
2. Roof / Top Roof Floor (Clinics)

• Consists of HVAC equipment such as FAHU, AHU, Bag-in Bag-out


HEPA filters, Inline HEPA filters, UV Lamps, Fans. For Water Supply;
Booster Pumps, Overhead Water Tanks, Copper Ionization, UV
Sterilization.
3. Roof Floor (Pharmacy, Radiology, Laboratory)

• Consists of HVAC equipment such as FAHU, AHU, Bag-in Bag-out


HEPA filters, Inline HEPA filters, UV Lamps, Fans, Chilled Water
Pumps, Dosing System, Chilled Water Pressurization System.

• Consists also of Chilled Water Pump Room, AGSS Room and MCC
Room.
2. EMERGENCY ESCALATION
PROCEDURES
TROUBLESHOOTING
(AIR CURTAIN)
S.
PROBLEM CAUSES SOLUTIONS
No.
Air curtain just  No power being supplied to the unit from  Confirm power source. Check
installed & power the electrical power source. if it is in ON position.
supplied to the unit  Circuit breaker is tripped.  Reset circuit breaker.
but unit not  Air curtain controller is disabled.  Connect the wired remote
working. controller supplied with air
curtain & press ON button on
or it.
 Door switch / sensor connected to air  Check if door sensor
Air curtain stopped curtain not responding. connected to air curtain & door
1 working. is opened. Replace limit switch
if faulty.
 Fuses on air curtain control board blown  Replace fuses.
off.
 Control board malfunctioning.  Repair or replace control board
as necessary.
 Motor capacitor malfunctioning.  Replace motor capacitor.
 Motor malfunctioning.  Repair or replace motor as
necessary.

Air curtain not  Door limit switch / sensor not responding.  Check the door switch / sensor
switching on when with respect to door position.
door opens. Replace if necessary.
2
 Air curtain controller malfunctioning.  Repair or replace controller as
necessary.

Air curtain not  No integration with door.  Install a door switch / sensor
switching off when and connect to air curtain as
door closes. per manufacturer requirement.
 Door limit switch / sensor not responding.  Check the door switch / sensor
3 with respect to door position.
Replace if necessary.
 Air curtain controller malfunctioning.  Repair or replace controller as
necessary.

Air curtain found  Obstruction in air intake &/or discharge  Clear air intake &/or discharge
to blow less air. nozzle. from any obstruction.
 Dirty filter.  Clean or replace filter as
necessary.
 Blower rotating below normal speed.  Check motor. Repair or
replace as necessary. Check if
4 blower rubbing against
housing or any other
disturbance. Rectify
accordingly.
 Blower clogged with dust & debris.  Clean and remove dirt from
blower.
TROUBLESHOOTING
(AIR CURTAIN)
S.
PROBLEM CAUSES SOLUTIONS
No.
Air curtain not  Air barrier not adjusted properly.  Adjust the discharge nozzle as
able to blow air till per local conditions.
ground.  Obstruction in the direction of air flow.  Remove obstruction from air
path or relocate air curtain
such that there is no
obstruction in the direction of
air flow.
 Low air flow.  Follow the solutions provided
5
against s.no. 3 above.
 Negative building pressure.  Negative building pressure or
pressure imbalance across the
air curtain air barrier is highly
undesirable. Provide a make-
up air system to relieve
negative building pressure.

Air curtain is  Faulty installation.  Most of the complaints are


making excessive related to installation which
or abnormal noise are faulty & not as per
or vibration manufacturer requirements.
Check the installation
methods, frames, fixtures,
assemblies. Tighten or secure
any loose contact or part.
 Broken blower.  Replace blower.
 Blower become loose from motor  Relocate blower on motor
coupling. shaft & tighten the coupling
screw.
 Blower rubbing against air curtain housing.  Adjust blower location or part
6
of the housing which is in
contact with blower.
 Blower out of balance.  Replace blower.
 Blower clogged with dust & debris.  Clean and remove dirt from
blower.
 Obstruction in air intake &/or discharge  Clear air intake &/or discharge
nozzle. from any obstruction.
 Obstruction in the direction of air flow.  Remove obstruction from air
path or relocate air curtain
such that there is no
obstruction in the direction of
air flow.
3. EMERGENCY INFORMATION
SAFETY MEASURES
(AIR CURTAIN)

• Disconnect the air curtain from power supply before any operations with the unit.
• Make sure that the fan impeller is not running and the heating elements are cold. Follow all the
recommendations set forth in this manual while mounting and operating the air curtains as well as
all the applicable local and national building, electrical and fire safety norms and standards.
• Do not power up the electric heater without sufficient air supply to the tubular heating elements. In
case of thermal sensor switch actuation power the unit off, troubleshoot the malfunction which has
triggered the sensor and only after successful troubleshooting restart the unit.
• The device is not designed to be used by children, physically or mentally disabled persons, persons
with sensory disorder, persons with no appropriate life experience and/or expertise unless they are
properly instructed about the device use or supervised by the person in charge for their safety.
• All servicing operations shall be performed by duly qualified personnel only! Make sure of no foreign
objects in the air curtain duct before connecting the unit to power supply network.
• All servicing operations shall be performed by duly qualified personnel only! Make sure of no foreign
objects in the air curtain duct before connecting the unit to power supply network.
4. SYSTEM PURPOSE AND SCOPE
WHAT IS AN AIR CURTAIN
• Air Curtain is an electrical device producing a directional air flow. When mounted above the
entrance doorways it separates the indoor space from the outdoor ambience functioning as
if the door is closed. Meanwhile the door remains open and provides free entrance and
contact. By producing a homogeneous air flow the Air Curtain prevents the heat losses and
protects the indoor space from the adverse weather conditions outdoors. It also acts a barrier
to the dust, insects, flies, etc.

• This allows creating an agreeable microclimate indoors, thus reducing energy consumption
by heaters and/or air-conditioners.

• The air curtain barrier is highly effective at normal climatic conditions, provided the pressure
across the air barrier is balanced. The efficiency of the air barrier decreases with increase in
the outdoor air speed.

• Functionally air curtains represent the energy saving class of equipment and are used
together with other types of climate control equipment like air-conditioners, space heaters,
etc.

• Apart from acting as invisible door barrier, Air curtains can also act as space heater or air-
conditioner by providing heating or cooling batteries in it.
5. DESCRIPTION AND INTERFACE
INFORMATION
WHAT IS AN AIR CURTAIN
• Air Curtain is an electrical device producing a directional air flow. When mounted above the
entrance doorways it separates the indoor space from the outdoor ambience functioning as
if the door is closed. Meanwhile the door remains open and provides free entrance and
contact. By producing a homogeneous air flow the Air Curtain prevents the heat losses and
protects the indoor space from the adverse weather conditions outdoors. It also acts a barrier
to the dust, insects, flies, etc.

• This allows creating an agreeable microclimate indoors, thus reducing energy consumption
by heaters and/or air-conditioners.

• The air curtain barrier is highly effective at normal climatic conditions, provided the pressure
across the air barrier is balanced. The efficiency of the air barrier decreases with increase in
the outdoor air speed.

• Functionally air curtains represent the energy saving class of equipment and are used
together with other types of climate control equipment like air-conditioners, space heaters,
etc.

• Apart from acting as invisible door barrier, Air curtains can also act as space heater or air-
conditioner by providing heating or cooling batteries in it.
6. EQUIPMENT SCHEDULE
Project : SHEIKH KHALIFA MEDICAL CITY, ABU DHABI ISLAND
OLEFINI (GREECE) Air Curtain
Selection Schedule Date:02/01/2024
SPECIFIED PROPOSED
Motor
Door Door No. of Length of Air Total Door Maximum Air Curtain Air Curtain Power
S. Reference Models Type / Type of No. of Total Rated
Location Width Height Qty units req. Curtain Coverage Inst. Height Air Volume Outlet Velocity Supply
No. Number Selected Series Mounting Doors Qty. Power
per Door
(m) (m) mm mm mm (m3/h) (m/s) (kW) (V / Hz / N)

1 ACR 4 Pharmacy 1.8 2.9 1 RS-37 Recessed Concealed 1 1 1 1855 1975 3500 - 4000 4130 11 0.66 230 / 50 / 1

2 ACR 4 Pharmacy 1.8 2.9 1 RS-37 Recessed Concealed 1 1 1 1855 1975 3500 - 4000 4130 11 0.66 230 / 50 / 1

Pharmacy
3 ACR 4 2.5 2.9 1 RS-34 Recessed Concealed 2 1 2 1375 2750 3500 - 4000 2600 11 0.35 230 / 50 / 1
(Sliding Door)

4 ACR 1 & 2 Public Corridor 1 2.5 3.4 1 RS-34 Recessed Concealed 2 1 2 1375 2750 3500 - 4000 2600 11 0.35 230 / 50 / 1

5 ACR 1 & 2 Public Corridor 1 2.5 3.4 1 RS-34 Recessed Concealed 2 1 2 1375 2750 3500 - 4000 2600 11 0.35 230 / 50 / 1

6 ACR 2 Public Corridor 2 2.5 3.4 1 RS-34 Recessed Concealed 2 1 2 1375 2750 3500 - 4000 2600 11 0.35 230 / 50 / 1

7 ACR 2 Public Corridor 2 2.5 3.4 1 RS-34 Recessed Concealed 2 1 2 1375 2750 3500 - 4000 2600 11 0.35 230 / 50 / 1

8 ACR 3 Clinic 1, Airlock 1.8 2.7 1 RS-37 Recessed Concealed 1 1 1 1855 1975 3500 - 4000 4130 11 0.66 230 / 50 / 1

8 13

Note(s):
Proposed units are elegant in design and supplied in heavyduty GI.
All the air curtains above shall be provided with Infra‐red Remote controller for the ease of operation of air curtain manually.
All the air curtains shall be provided with a volt‐free contact for the ease of interlocking the unit with door operation with help of door sensor.
Door sensor to be selected as per the type & operation of door.
All the units above can be integrated with BMS system, if required, via a RS‐485 Modbus serial communication card (optional).
7. OPERATING INSTRUCTIONS AND
PROCEDURES
SEQUENCE OF OPERATION
OLEFINI AIR CURTAIN
(ECO controller)

1.0 INTRODUCTION

This sequence of operation is applicable for Olefini air curtains provided with ECO controller.

Please contact Rapid Cool Trading Co. LLC, P.O. Box 2034, Dubai, UAE, Tel: 04-4256663, Fax:
04-2765891, info@rapidcool.ae, to know the controller details provided in the air curtain.

It is assumed that air curtain has been installed and wired as per site requirements & manufacturer’s
recommendation, maintaining necessary operational & maintenance clearances, and connected to
a suitable power source (230V / 1~ / 50Hz) as per the local requirements & standard codes of
practice.

2.0 PRE-COMMISSIONING CHECK

Prior to starting up the unit, ensure that air curtain is free from any foreign object, blower is free to
rotate & firmly fixed to the shaft of motor, in order to avoid any accidental damage to blowers during
startup & operation.

Provide power supply (230V, 1~, 50Hz) to the air curtain.

Read the display on the control panel (shown on page 2) provided on the air curtain. A small red
“dot” will appear on the display if the unit is in off condition, otherwise the speed is displayed at which
the air curtain is running as illustrated below:
 F3 – High speed
 F2 – Medium speed
 F1 – Low speed
 F0 – Stop, unit ON
 “dot” – Unit OFF (Disabled)

In case the display is blank, check power supply to the unit. If


required, open the front motor cover and check the red LED
light on the control board. If the light is off, please contact the
supplier at the contact details provided above.

Page 1 of 4
3.0 OPERATIONAL PROCEDURE

3.1 Control Panel

OLEFINI air curtain is supplied with an HMI device for ease of user interactions with the air curtain.
Below picture explains the various functionality of the control panel.

SPEED UP / DOWN
(adjustment) BUTTONS
LED INDICATORS

MODE BUTTON
DISPLAY PANEL (for service technician)

INFRARED ON/OFF BUTTON


SENSOR (to Enable / Disable controller)

3.2 DEFAULT operation

This section explains the operational details of the default operation which is continuous operation
wherein a door sensor or door-status is not connected to air curtain’s controller. Hence, air curtain
will remain in same state of operation as set by user, until operated again by the user to change to
a new state of operation.

DEFAULT operational mode is available only where door


sensor is not connected or disconnected from the air
curtain. In this mode, user has to operate the air curtain
manually to switch on & off.

If air curtain is off, press “ON/OFF” button on the control panel to switch air curtain on. Air curtain
shall start running at high speed with “F3” on the display panel.

Now, user can adjust the operational speed of the air curtain to any desired speed through the speed
adjustment buttons. Use up or down speed buttons to select desired speed (F3 / F2 / F1 / F0).

Above procedure can also be executed from wireless remote


provided with the unit. However, the wireless remote must be
facing the infra-red sensor on the control panel.

In order to switch off the unit completely, press “ON/OFF” button again. A red dot will appear on the
display indicating the controller is disabled.

Page 2 of 4
3.3 AUTOMATIC operation

This section explains the operational details of the AUTOMATIC operation wherein a door sensor
or door-status is connected to air curtain’s controller. The air curtain will then start-stop or change
speed automatically depending upon door status, without any user interaction.

ECO controller is provided with a contact for ease of connecting to a volt-free door contact or door
sensor in order to set the air curtain in automatic mode of operation.

When volt-free contact is opened (NO), air curtain will run; and
when the contact is closed (NC), air curtain will stop after few
seconds.

Door status to air curtain can be provided with help of suitable


door sensor depending upon type & operation of door.
Please contact supplier for more details.

If air curtain is off, press “ON/OFF” button on speed regulator to “ENABLE” the controller. The air
curtain may or may not run depending upon door is open or closed. When door is opened, air curtain
will start running at high speed with “F3” on the display panel (factory-set speed for door open
condition). When door is closed, air curtain will stop after some delay pre-set in the controller with
“F0” on the display panel.

Do not switch on & off air curtain frequently. It is HIGHLY


RECOMMENDED to reduce the frequency of on / off cycle
by increasing off-delay where door is used very frequently.

Above factory default settings of AUTOMATIC mode can be changed by using speed adjustable
buttons as explained below.

 Open the door and set desired speed for air curtain (F3 / F2 / F1) using speed selection
buttons and wait for few seconds till the speed is registered in the controller.

Do not select fan speed F0 when door is opened.


This will make air curtain blower to stop running while door
remains opened.
 Close the door and wait for the time more than the pre-set off-delay time. Subsequently,
set desired speed (F3 / F2 / F1 / F0) using speed selection buttons and wait for few
seconds till the speed is registered in the controller.

Page 3 of 4
It is advisable to select fan speed F0 in order to stop air curtain
blower when door is closed, for energy savings.

 Check the operation of air curtain by opening and closing the door. The air curtain should
run at the user-defined speeds automatically.

 If the operation of the air curtain is not as per the requirement, repeat above procedure
again.

Above procedure can also be executed from wireless remote


provided with the unit. However, the wireless remote must be
facing the infra-red sensor on the control panel.

Air curtain is now commissioned to work successfully.

Page 4 of 4
8. MAINTENANCE PROCEDURES
PERIODIC MAINTENANCE
(AIR CURTAIN)
Periodic maintenance is essential for efficient operation and extended service life of air curtains.
Failure to provide regular and correct servicing may result in malfunctioning or break-down of the
equipment, lower service life and nullify warranty.

Maintenance & service of air curtains should be carried out by qualified personnel.

All maintenance & service works are allowed only after disconnecting air curtain from main power
supply. In case, units are supplied with electrical heaters, it is recommended to switch off the unit from
control panel and wait for few minutes to allow the heaters cool down prior to disconnecting main
power supply.

WEEKLY
Inspect air curtain visually for desirable operation.
If unit operation is not satisfactory or not as per requirement, follow
troubleshooting procedure as attached.
Inspect air curtain for any abnormal sound.
In case of abnormal sound, follow the troubleshooting procedure.
Inspect inlet (suction) & outlet (discharge) and ensure they are free from
dust & foreign bodies.
MONTHLY
Perform weekly maintenance schedule.
Inspect filters, if supplied. Clean or replace if necessary.
Open the intake grilles and inspect the blower-motor assembly for any dust
or debris. Clean the blowers, if necessary, by blowing compressed air.
Remove any foreign object from the cabinet.
Clean all the interior surfaces of the cabinet, if necessary.
Clean all the exterior surfaces.
QUATERLY
Complete the weekly & monthly maintenance schedule.
Check motor blower coupling. Tighten the screws if necessary.
Check blower bearing support. Clean or replace if necessary.
Check all electrical components, wiring, connections & terminals. Tighten
the connections where necessary.
Clean all the interior & exterior surfaces of the cabinet.

Above schedule is for guidance purpose only. However, the performance and efficiency of air curtains
are dependent on cleanliness of blower wheels, motor(s), intake & discharge grilles. Building up of
dust on blowers can cause unit to vibrate, noisy and excessive wear of bearings. Hence, frequency of
periodic maintenance & cleaning is mainly dependent on the environment where unit is operating.
Dirty, dusty or humid environments could require a frequent maintenance schedule than above
depending upon the environmental condition and amount of dust or debris being accumulated in air
curtain.
9. SPARE PARTS
SPARE PART LIST

Item : AIR CURTAIN


Make : OLEFINI
Origin : GREECE

S. No. Model Spare Part Part No. Self-Life

Rubber Bush Set OL-BB-120W 2 Years

1 RS-34
ECO Electronic Board OL-ECO 5 Years

Rubber Bush Set OL-BB-120W 2 Years

2 RS-37
ECO Electronic Board OL-ECO 5 Years
10. HSE AND DISPOSAL
INSTRUCTIONS
11. TESTING AND COMMISSIONING
TESTING & COMMISSIONING CHECK LIST-AIR CURTAIN
Description Check That Remarks

MECHANICAL CHECK

1 Check Air curtains for any damages

Check the installation of Air curtains as per manufacturer’s


2
instruction and approved drawings.

3 Check that there are no foreign bodies in the unit.

Check and ensure the availability of Mounting brackets


with air curtains.
4

Check and ensure the availability of wall mounted speed


5
regulator with air curtains.

6 Check the fan rotates freely by hand.


ELECTRICAL CHECK

Ensure that wall mounted speed regulator is connected to


7
the unit.

8 Check the direction of rotation of fans on initial start up

Check that there is no unusual noise or vibration developed


9
during the initial start up

Check the electrical isolators are located close to the unit


10
to access emergency stop for emergency and maintenance.

Check all cables have been terminated properly and


11
tightened.
START-UP

12 Start the unit by switching ON/OFF.

13 Check Door interlocks Start/Stop the unit.


12. DRAWINGS
13. MANUFACTURERS AND
SUPPLIERS’ LITERATURE
2023

PRODUCT
CATALOG
INDEX

COMPANY PROFILE______________________________________________________ 4 - 9
OPERATION WAYS_________________________________________________ 10 - 15
ECO SYSTEM___________________________________________________________ 12-13
UD SYSTEM________________________________________________________________14
ΑIR CURTAIN CONTROLS___________________________________________________15

COMMERCIAL______________________________________________________ 16 - 27
for maximum door height from 2,5m up to 4,0m

• “w” SERIES__________________________________________________________ 18 - 21
SIMPLE
ELECTRICALLY HEATED
HOT WATER HEATED

• “AP” SERIES _________________________________________________________ 22 - 23


SIMPLE

• “X” SERIES__________________________________________________________ 24 - 25
SIMPLE

• “PLASTIC” SERIES____________________________________________________ 26 - 27
SIMPLE or ELECTRICALLY HEATED

1
GENERAL___________________________________________________________ 28 - 43 SPECIAL TYPE_______________________________________________________ 50 - 53
for maximum door height from3,5m up to 4,0m
• “w” SERIES__________________________________________________________ 30 - 35 • “TRUCK” SERIES__________________________________________________________ 51
SIMPLE 12V or 24V
SIMPLE for maximum door height 2,5m
ELECTRICALLY HEATED
HOT WATER HEATED • “RV” horizontal SERIES____________________________________________________ 52
HOT-COLD WATER HEATED SIMPLE & ELECTRICALLY HEATED
for maximum height of revolving door 4,0m

• CASSETTE TYPE______________________________________________________ 36 - 39 • “RV” vertical SERIES______________________________________________________ 53


SIMPLE SIMPLE & ELECTRICALLY HEATED
for maximum height of revolving door 2,8 m
ELECTRICALLY HEATED
HOT WATER HEATED
IP 24 GENERAL & INDUSTRIAL
• “C” SERIES__________________________________________________________ 40 - 41 • “CLASSIC” SERIES___________________________________________________ 54 - 57
SIMPLE & ELECTRICALLY HEATED for maximum height 3,5m - 6,0m

• “ANEMOESSA” SERIES________________________________________________ 42 - 43
SIMPLE & ELECTRICALLY HEATED

INDUSTRIAL________________________________________________________ 44 - 49
for maximum door height 6,0m
• “CLASSIC” SERIES____________________________________________________ 46 - 47
SIMPLE

• “CLASSIC” SERIES____________________________________________________ 48 - 49
ELECTRICALLY HEATED
HOT WATER HEATED

2 3
COMPANY PROFILE

Injection Moulding Machines Department

Established in 1977 OLEFINI S.A.


started as an injection molding
designer and manufacturer of
thermoplastic technical products
having a long course in engineering CNC Automated Injection machines pro-
plastics and relative constructions. duction line for plastic parts, capable of
producing parts weighting from 10 gr up
After 34 years company has managed to 6.5 kgr.
today to be the ONLY manufacturer
of Air Curtains in Greece and one
of the Global Leading firms in this Ultrasonic Department
product field.
As a reward to management’s commitment in High quality and efficient products company Exports it’s units in more than 30 countries
all over the world.
Following ISO 9001:2015 guiding rules, with advanced R&D Mould making and also Electronics department, in it’s private owned
premises since 2005, OLEFINI S.A. produces CE complied units that can serve all various customer demands.
In this 12.000 m2 space Olefini produces it’s Air Curtains and today has reached a 400 models Variation of: Simple, Electrically Heated,
Hot Water Heated & Hot-Cold Water Heated types.
Among others OLEFINI products include:
f ECO Technology air curtains, equipped with sophisticated electronics in order to transform unit in an Energy Saving product.
f Recessed air curtains Ultrasonic welding machines for plastic fans production and fan balancing machines for precise parts production.
f IP 24 air curtains
f FAN HEATERS

4 5
COMPANY PROFILE
Final Assembly Line Department Electronic Department

3 Independent Air Curtain Assembly


lines, producing all OLEFINI products,
equipped with CE testing stations for
Automated Electronics
Safety compliance.
production line, for Assembly
and Final Inspection before release
to production.

Quality Test Department Mechanical Workshop Department


Central Air Curtain Safety Inspection
Station for final Stage TESTS and DATA
Acquisition purposes according to:

LOW VOLTAGE DIRECTIVE


2006/95/EC

ELECTROMAGNETIC COMPATIBILITY
2004/108/EC
MOULD production & repair line equipped with:
f WIRE EDM machine f Radial Machine
f SPARK EDM machine f Cutter Machine

6 7
COMPANY PROFILE

Sheet Metal Department R&D Department

PRO Engineer Software station for


MOULD design connected with a 4 AXIS
CNC mill with a long up to 3 meters table
for big Moulds production.

Sheet metal production line equipped with:


f CNC Folding machine f Suitable software for programming f Welding station
f Spot welder machine punching machine f CNC punching machine

Electrical heater Department Warehouse

Electrical heaters production


line for Air curtains.

Warehouse for storing from spare parts and components up to finished products ready for delivery.
8 9
OPERATION WAYS

11
ECO SYSTEM

New ECO System. fDoor switch with configurable f Overheat alarm sensor, fan issue alarm Over the network each air curtain can be
time delays. sensor, and error codes to help periodic under the complete control of the building’s
Maximum energy saving, ultimate comfort. OLEFINI’s air curtains are capable of maintenance and cleaning. central control unit. And of course all the
altering their operation when the door is Since our units are designed to offer their sensor values, fault status, alarms, status
OLEFINI offers a new electronic control
opened or closed. It is possible to set the air services at 24/7 for years, you can be of operation, etc will be visible or adjustable
system for the entire line of Air Curtain remotely.
curtain to completely stop when the door is assured that when the time comes to have
products. closed, or even have the air curtain work in the unit maintained, a fault indicator will f Master/Slave connection between
The new system called "ECO" is capable a mode similar to space heater in the winter. guide the technician to the source of issue. multiple units on the same door.
of further reducing the electricity bill by All that with a touch of a button.
f BMS networking supported, Whenever there is a need to cover a very
applying intelligent control on the unit’s fan f With Electric heaters based on MODBUS (optional) wide opening, OLEFINI’s ECO air curtains
or Hot water or Cold water. can be cascaded with a very easy and
and heater elements. The operation of the OLEFINI Air Curtains can now be connected
Most of OLEFINI’s air curtain models can be to BMS systems. We have adopted the cost efficient method. A simple cable is
unit is now smoother and more efficient. configured with electric heaters or with Hot/ all that is needed to cascade one or more
Modbus protocol for BMS connected air
Cold water elements. Depending on the given units together to work in a Master - Slave
curtains. Each air curtain can be equipped
The key features of the new line project, an air curtain can operate with the
with its own network card (supplied as an configuration. In this situation, only one
building’s chiller, boiler, heat pump, or just
of products are: electricity when needed. option) and it will present itself on a Modbus control panel is needed and all connected air
BMS network. curtains can respond identically to the user’s
f Fine-tuned control for maximum commands.
f Wireless (IR) user panel
environment comfort.
and Wired panel with bright display.
The intelligent control system try to
The new ECO system comes with an
maintain a good level of separation between
improved and very easy to use wired panel.
the inside and outside of the building and at
The user can adjust the air curtain
the same time, and whenever it is possible,
with a touch of a button or even leave the ROOM DOOR
the air flow is reduced to lower the noise THERMOSTAT SWITCH
air curtain work completely automatically if
level and offer more comfort.
necessary. I/O BOX
I/O BOX UTP CABLE
It is very intuitive and easy to use.
Where the user can adjust specific levels
according to his/her preference.
LEH-33 (MASTER) KEH-38 (SLAVE)

12 13
UD SYSTEM ΑIR CURTAIN CONTROLS

UP-DOWN
Air Curtain Systems.
Multi speed control
OLEFINI offers the Up-Down system for some models of Air Curtain Wired & Infrared Wired & Infrared Wired & Infrared
products. remote controls remote controls remote controls
for for for
The Up-Down system, is capable of adjusting the air curtain’s fan speed and IP24 Simple IP24 Electrically IP24 Hot Water
heater level according to the user’s preferences.
units: Heated units: Heated units:
The key features of the Up-Down line of products are: f General f General f General
f Industrial f Industrial f Industrial
Smooth fan speed control
The air curtain’s fan speed can be controlled from the user panel and adjusted
in small steps in order to provide maximum confort and low noise.
Door switch operation
If a door switch is connected the Up-Down is capable of stoping it’s operation
when the door is closed and the air curtain’s help is not needed.
Wireless (IR) user panel Wired & Infrared Panel & Infrared
The Up-Down Air Curtains feature a build in user panel (on the unit) and remote controls for remote controls
a wireless remote control (IR). User can issue commands either from the “ECO” Series units for “ECO” Series
build in panel, or the wireless remote control with a touch of a button. The (Simple, Electrically (Simple, Electrically Heated
air curtain provides indication of it’s operating state with bright LEDs, and Heated & Water & Water Heated):
audible signals. Heated): f Commercial
f Commercial f General
f General f Industrial
f Industrial Panel & Infrared f Recessed
f “C” Series remote controls for
f Recessed U-D Simple units:
f Plastic

14 15
AIR CURTAINS
COMMERCIAL
for maximum door height from2,5m up to 4,0m
SIMPLECOMMERCIAL
“w” SERIES (door height up to 2,5 m)

Infrared
Remote
motor
position: Control
LEFT
RIGHT
0,7m OPERATION WAYS OPTIONAL
0,8m
f New eco control system (ECO) f Filter
ht m o tor
t o r r ig si d f Vertical mount
le f e
1,0m f Door switch
MAXIMUM DOOR WIDTH

f Inox body (430 stainless steel)


motor f Inox grill & body
position:
MIDDLE (430 or 316 stainless steel)
f Energy Saving
1,2m f Barrier to Insects,
Dust Odours, WORKING CONDITIONS:
TECHNICAL DETAILS

1,4m
TYPE L or R-11w L or R-12w L or R-13w K-14w K-15w K-16w K-17w K-18w
Pollutants & Humidity f Max Temperature 50οC (environment) Max door width (m) 0.7 0.8 1.0 1.2 1.4 1.6 1.8 2.0
f Slim Line Design f Max Humidity 80%
Max door height (m) 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

1,6m
Max Outlet velocity (m/sec) 10 / 9 / 8 10 / 9 / 8 10 / 9 / 8 10 / 9 / 8 10 / 9 / 8 10 / 9 / 8 10 / 9 / 8 10 / 9 / 8
f Easy Installation f Non-toxic environment Max Air volume (m3/h) 1000/900/800 1150/1035/900 1300/1170/1050 1400/1260/1100 1700/1530/1350 2000/1800/1600 2200/1800/1600 2500/2250/2000
f Low Noise Level Motor power input (W) 120 120 120 240 240 240 240 240

1,8m
Capacitor (μF) 4 4 4 4 4 4 4 4
f Motor position: Noise level in 1 m [dB(A)] 54 / 45 54 / 45 54 / 45 60 / 53 60 / 53 60 / 53 61 / 55 61 / 55
Center, Left, Right L: Total length (mm)
W: Total width (mm)
847
166
945
166
1045
166
1206
166
1406
166
1606
166
1806
166
2006
166

2,0m

DIMENSIONS
H: Height (mm) 172 172 172 172 172 172 172 172
l: Outlet length (mm) 700 800 900 1160 1360 1560 1760 1960
w: Outlet width (mm) 54 54 54 54 54 54 54 54
h: Outlet height (mm) 64 64 64 64 64 64 64 64
Weight (kgr) 8 9.5 11 15 17 19 22 24
Power supply (V/Hz/N~) 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1
FOR USE IN: SMALL SHOPS, JEWELRIES, HAIRDRESSER SALONS, HEALTH SPAS, BARS, CAF- Motor speed (rpm) 1300 / 900 1300 / 900 1300 / 900 1300 / 900 1300 / 900 1300 / 900 1300 / 900 1300 / 900
ETERIAS, PASTRY SHOP, BREWERIES, SMALL HOTELS, BANKS, SCHOOLS, SUPER MARKETS, cross flow fan Ingress Protection IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20

FOOD FACTORIES, MEAT FACTORIES, FISH MONGER SHOPS, SMALL COLD STORAGE PLANTS Φ 100 diameter *Company OLEFINI reserves the right to alter given product specifications without further notice.

18 19
ELECTRICALLY HEATED COMMERCIAL HOT WATER HEATED COMMERCIAL
“w” SERIES (door height up to 2,5 m) WORKING CONDITIONS:
(door height up to 2,5 m)

f Max Temperature 50οC


(environment)
f Max Humidity 80%

n
f Non-toxic environment

ctio

he
ater supply conne

at e
Infrared
f Energy Saving

xchanger
Remote
f Energy Saving f Barrier to Insects, Dust
Control
f Barrier to Insects, Dust Odours, Pollutants & Humidity Odours,
f Slim Line Design f Easy Installation Pollutants & Humidity

”w
motor f Slim Line Design
position: f Low Noise Level

1/2
LEFT f Easy Installation

ns
f 6, 9, 12 or 15kW thermal load* motor
RIGHT po ct
position:

io
(depends on the models size) f Low Noise Level TECHNICAL DETAILS

tu
1,0m
ul we e LEFT
r s u p pl y c o n n

ts
n

b
Motor position: Center, Left, Right ar
me f 1/2” water supply
MAXIMUM DOOR WIDTH

f
h e a ti RIGHT
n g ele TYPE L or RWΗ-13w ΚWΗ-14w ΚWΗ-15w ΚWΗ-16w ΚWΗ-17w ΚWΗ-18w
f Room Thermostat f Door Switch connection Max door width (m) 1.0 1.2 1.4 1.6 1.8 2.0
1,0m

MAXIMUM DOOR WIDTH


motor
position: Infrared f Motor position: Max door height (m) 2.5 2.5 2.5 2.5 2.5 2.5
MIDDLE TECHNICAL DETAILS Remote Max Outlet velocity (m/sec)
Center, Left, Right Max Air volume (m /h)
7.0 / 5.5 7.0 / 5.5 7.0 / 5.5 7.0 / 5.5 7.0 / 5.5 7.0 / 5.5
motor

1,2m
3
900 / 710 1000 / 790 1200 / 950 1400 / 1100 1600 / 1250 1800 / 1400 position:
TYPE L or REΗ-13w ΚΕΗ-14w ΚΕΗ-15w KΕΗ-16w ΚΕΗ-17w ΚΕΗ-18w Control f Door switch Motor power input (W) 120 240 240 240 240 240
MIDDLE
OPTIONAL
1,2m
Max door width (m) 1.0 1.2 1.4 1.6 1.8 2.0 Capacitor (μF) 4 4 4 4 4 4
f Room Thermostat Capacity (lt)

1,4m
0.73 0.75 0.91 1.0 1.24 1.4
Max door height (m) 2.5 2.5 2.5 2.5 2.5 2.5 f Filter Noise level in 1 m [dB(A)] 54 / 50 54 / 50 54 / 50 54 / 50 54 / 50 54 / 50
Max Outlet velocity (m/sec) 9.0 / 7.0 9.0 / 7.0 9.0 / 7.0 9.0 / 7.0 9.0 / 7.0 9.0 / 7.0
f Vertical mount
1,4m
Max Air volume (m3/h) 1150 / 900 1280 / 990 1500 / 1200 1750 / 1400 2000 / 1600 2300 / 1800 L: Total length (mm) 1100 1206 1406 1606 1806 2006
OPTIONAL W: Total width (mm) 274 274 274 274 274 274

1,6m

DIMENSIONS
Motor power input (W) 120 240 240 240 240 240 f Inox body H: Height (mm) 172 172 172 172 172 172
Capacitor (μF) 4 4 4 4 4 4 f Filter
(430 or 316 stainless steel) l: Outlet length (mm) 900 1160 1360 1560 1760 1960

1,6m
Noise level in 1 m [dB(A)] 54 / 43 55 / 45 56 / 50 56 / 50 59 / 52 59 / 52
f Vertical mount w: Outlet width (mm) 54 54 54 54 54 54

1,8m
L: Total length (mm)
W: Total width (mm)
1100
274
1206
274
1406
274
1606
274
1806
274
2006
274
f Inox grill & body h: Outlet height (mm) 64 64 64 64 64 64
f Inox body
DIMENSIONS

(430 or 316 stainless steel) Weight without water (kgr) 19 22 25 28 31 35

1,8m
H: Height (mm) 172 172 172 172 172 172
(430 or 316 *Air Inlet Temperature +150C *Water Inlet Temperature +700C Flow rate 0.6 (lt/sec) [ 0.3 lt/sec for R,L ]

2,0m
l: Outlet length (mm) 900 1160 1360 1560 1760 1960
Heating power (kW) 8.4 / 7.3 9.3 / 8.0 11.1 / 9.6 13.0 / 11.2 14.8 / 12.7 16.6 / 14.2
w: Outlet width (mm) 54 54 54 54 54 54 stainless steel) Air outlet temperature (0C) 42.2 / 44.7 42.5 / 44.7 42.2 / 44.7 42.1 / 44.6 42.0 / 44.6 41.9 / 44.5

2,0m
h: Outlet height (mm) 64 64 64 64 64 64
Weight (kgr) 21 24 27 30 33 37 f Inox grill & body Water outlet temperature (0C) 63.2 / 64.1 66.2 / 66.8 65.5 / 66.1 63.7 / 65.5 64.0 / 64.8 63.8 / 64.2
Pressure drop (water) ΔP (kPa) 4.2 3.2 3.4 3.7 3.9 4.1
Thermal power (kW) 6/9 9 9 12 12 / 15 12 / 15 (430 or 316 *Air Inlet Temperature +150C *Water Inlet Temperature +900C Flow rate 0.6 (lt/sec) [ 0.3 lt/sec for R,L ]
Max current cons. (A)(per phase) 9 / 13 13 13 17.5 17.5 / 22 17.5 / 22
T outlet - Τ inlet (0C) 20-26 / 28-36 28-36 27-35 25-33 16-21 / 20-25 16-21 / 20-25
stainless steel) Heating power (kW) 11.6 / 10.0 12.8 / 11.0 15.3 / 13.2 17.8 / 15.4 20.3 / 17.5 22.8 / 19.5
Power supply (V/Hz/N~) 400 / 50 / 3L+N 400 / 50 / 3L+N 400 / 50 / 3L+N 400 / 50 / 3L+N 400 / 50 / 3L+N 400 / 50 / 3L+N Air outlet temperature (0C) 52.5 / 55.7 52.5 / 55.8 52.4 / 55.7 52.5 / 55.6 52.1 / 55.6 52.0 / 55.5
Motor speed (rpm) 1310 / 1000 1310 / 1000 1310 / 1000 1310 / 1000 1310 / 1000 1310 / 1000 Water outlet temperature (0C) 80.5 / 81.8 84.8 / 85.5 83.7 / 84.6 82.7 / 83.7 81.7 / 82.9 80.7 / 82.0
Heating stages 4 4 4 4 4 4 Pressure drop (water) ΔP (kPa) 4.0 3.1 3.3 3.5 3.7 3.9
Ingress Protection IP20 IP20 IP20 IP20 IP20 IP20
*Company OLEFINI reserves the right to alter given product specifications without further notice.

20 21
SIMPLECOMMERCIAL
“AP” SERIES (door height up to 4,0 m)

NEW
MODEL
f Energy Saving
f Barrier to Insects,
Dust Odours,
Pollutants & Humidity
f Controlled Microclimate
MAXIMUM DOOR WIDTH

motor f Modern Design OPERATION WAYS


position: f Easy Installation f New eco control K
MIDDLE system (ECO) I
f Low Noise Level 74

1,2m f Door switch


f Room Thermostat

1,4m
216

L 303
OPTIONAL
1,6m f Inox body (430 stainless steel)
TECHNICAL DETAILS
1,8m ad
ju s
t a b l e a i r fl a p s opening
TYPE
Max door width (m)
AP-34
1.20
AP-35
1.40
AP-36
1.60
AP-37
1.80
AP-38
2.00

2,0m
Max door height (m) 4.00 4.00 4.00 4.00 4.00
cover Max Outlet velocity (m/sec) 12 / 11 / 9 12 / 11 / 9 12 / 11 / 9 12 / 11 / 9 12 / 11 / 9
Max Air volume (m3/h) 2125/1950/1598 2570/2355/1925 2990/2740/2240 3430/3145/2575 3850/3530/2890
Motor power input (W) 350 660 660 660 660
Wired WORKING CONDITIONS: Capacitor (μF) 8 15 15 15 15
Infrared Remote f Max Temperature 50οC (environment) Noise level in 1 m [dB(A)] 54 / 43 54 / 43 54 / 43 54 / 43 54 / 43
Remote L: Unit length (mm) 1185 1390 1585 1790 1985

DIMENSIONS
Control f Max Humidity 80% Κ: Mounting distance (mm) 500 600 700 600 600
Control f Non-toxic environment
Ι: Mounting distance (mm) - - - 1200 1300
Weight (kgr) 26 29 32 35 39
Power supply (V/Hz/N~) 230 / 50 / N 230 / 50 / N 230 / 50 / N 230 / 50 / N 230 / 50 / N
Motor speed (rpm) 1310/1000 1310/1000 1310/1000 1310/1000 1310/1000
Noise Levels dB(A) 1m 58/51 59/52 60/52 61/54 61/54
FOR USE IN: SMALL SHOPS, JEWELRIES, HAIRDRESSER SALONS, HEALTH SPAS, BARS, Weight (Kgr) 25 28 31 34 38
CAFETERIAS, PASTRY SHOP, BREWERIES, SMALL HOTELS, BANKS, SCHOOLS, SUPER MARKETS, FOOD FACTORIES, cross flow fan
MEAT FACTORIES, FISH MONGER SHOPS, SMALL COLD STORAGE PLANTS Φ 120 diameter *Company OLEFINI reserves the right to alter given product specifications without further notice.

22 23
SIMPLE COMMERCIAL “X” SERIES (door height up to 3,0 m)

motor
position:
OPERATION WAYS
MIDDLE f New eco control system (ECO)
air fl a ps
1,0m l um
i num

1,2m

a
f Energy Saving control panel
f Barrier to Insects, Dust Odours, “ECO”
1,4m Pollutants & Humidity
f Modern Design

1,6m f Easy Installation


f Low Noise Level
TECHNICAL DETAILS
1,8m f Inox body (430 stainless steel)
f Inox body (316 stainless steel) optional TYPE X10 X12 X14 X16 X18 X20

2,0m
Max door width (m) 1.0 1.2 1.4 1.6 1.8 2.0
f Competitive price
Max door height (m) 3.0 3.0 3.0 3.0 3.0 3.0
Max Outlet velocity (m/sec) 9/7/5 9/7/5 9/7/5 9/7/5 9/7/5 9/7/5
Max Air volume (m3/h) 1560/1210/850 1810/1410/1000 2160/1680/1200 2595/2020/1440 2800/2170/1550 3090/2400/1770
MAXIMUM
DOOR
WIDTH

Motor power input (W) 240 240 240 300 660 660
Capacitor (μF) 4 4 4 8 8 or 15 8 or 15
L: Total length (mm) 1080 1220 1510 1670 1820 2020

DIMENSIONS
W: Total width (mm) 202 202 202 202 202 202
Infrared H: Height (mm) 203 203 203 203 203 203
Remote Control w: Outlet width (mm)
Power supply(V/Hz/N~)
54
230 / 50 / 1
54
230 / 50 / 1
54
230 / 50 / 1
54
230 / 50 / 1
54
230 / 50 / 1
54
230 / 50 / 1
Motor speed (rpm) 1370 / 1100 1370 / 1100 1370 / 1100 1370 / 1100 1370 / 1100 1370 / 1100
Ingress Protection IP20 IP20 IP20 IP20 IP20 IP20
Weight (Kgr) 11 13 15 17 21 22
Noise Levels dB(A) 1m 56/50 56/50 57/52 57/52 60/55 60/55
FOR USE IN: SMALL SHOPS, JEWELRIES, HAIRDRESSER SALONS, HEALTH SPAS,
cross flow fan CAFETERIAS, PASTRY SHOP, BREWERIES, SMALL HOTELS, BANKS, SUPER MARKETS,
Φ 100 diameter FOOD & MEAT FACTORIES, FISHMONGER SHOPS, SMALL COLD STORAGE PLANTS *Company OLEFINI reserves the right to alter given product specifications without further notice.

24 25
SIMPLE or ELECTRICALLY HEATED
COMMERCIAL
“PLASTIC” SERIES (door height up to 3,0 m)
adju
sta
b

le
a ir
fl a p OPERATION WAYS
f UD operation, f Room thermostat WORKING CONDITIONS:
15 different speeds with (electrically heated models) f Max Temperature 50οC (environment)
infrared remote control (U.D.) f Door switch f Max Humidity 80%
*only in “SIMPLE” models
f Non-toxic environment

l
p a ne TECHNICAL DETAILS
ol

r
TYPE K43 K43UD K44 K44 UD K46 K46 UD KEH-43 KEH-44 KEH-46

nt
motor f Energy Saving
MAXIMUM DOOR

co
position: Max door width (m) 1.0 1.0 1.2 1.2 1.6 1.6 1.0 1.2 1.6
f Barrier to Insects, Infrared Max door height (m) 3.0 3.0 3.0 3.0 3.0 3.0 2.5 2.5 2.5
MIDDLE
Dust Odours, Remote Max Outlet velocity (m/sec) 10.0 / 7.0 10.0 / 4.0 10.0 / 7.0 10.0 / 4.0 10.0 / 7.0 10.0 / 4.0 8.5 / 7.0 8.5 / 7.0 8.5 / 7.0

1,0m
Max Air volume (m3/h) 2435 / 1700 2435 / 970 2800 / 1660 2800 / 1100 3790 / 2650 3790 / 1500 2070 / 1825 2355 / 1940 3221 / 2840
Pollutants & Humidity Control Motor power (W) 240 240 240 240 300 300 240 240 300
Capacitor (μF) 4 4 4 4 8 8 4 4 8
f Slim Line Design
Noise level in 1 m [dB(A)] 55 / 50 55 / 45 55 / 52 55 / 45 56 / 53 56 / 48 58 / 56 58 / 56 58 / 56

1,2m
f Easy Installation L: Total length (mm) 1066 1066 1200 1200 1650 1650 1066 1200 1650

DIMENSIONS
W: Total width (mm) 190 190 190 190 190 190 190 190 190
WIDTH

f Low Noise Level H: Height (mm) 230 230 230 230 230 230 230 230 230
f Plastic body l: Outlet length (mm) 1066 1066 1200 1200 1650 1650 1066 1200 1650

1,6m
w: Outlet width (mm) 70 70 70 70 70 70 70 70 70
f 6, 9 or 12kW heating load Weight (kgr) 10 10 12 12 14 14 10 12 14
(depending on models size) Thermal power (kW) - - - - - - 6/9 6/9 9 / 12
Max current cons. (A) (per phase) - - - - - - 9 / 13 9 / 13 13 / 17.5
T outlet - Τ inlet (0C) - - - - - - 15-20 / 20-25 15-20 / 20-25 15-20 / 20-25
Power supply (V/Hz/N~) 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 400/50/3L+N 400/50/3L+N 400/50/3L+N
Motor speed (rpm) 1300 / 900 1300 / 900 1300 / 900 1300 / 900 1300 / 900 1300 / 900 1300 / 900 1300 / 900 1300 / 900
FOR USE IN: SMALL SHOPS, JEWELRIES, HAIRDRESSER SALONS, HEALTH SPAS, BARS, Heating stages - - - - - - 4 4 4
Ingress Protection IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20
CAFETERIAS, PASTRY SHOP, BREWERIES, SMALL HOTELS, BANKS, SCHOOLS, SUPER MARKETS, cross flow fan
FOOD FACTORIES, MEAT FACTORIES, FISH MONGER SHOPS, SMALL COLD STORAGE PLANTS Φ 110 diameter *Company OLEFINI reserves the right to alter given product specifications without further notice.

26 27
AIR CURTAINS
GENERAL
for maximum door height from 3,0m up to 4,0m
SIMPLEGENERAL
“w” SERIES (door height up to 4,0 m)

“E
CO
” co
ntrol p an el
WORKING CONDITIONS:
f Max Temperature 50οC (environment)
motor
position: f Max Humidity 80%
LEFT
RIGHT f Non-toxic environment

1,0m
MAXIMUM DOOR WIDTH

ter
OPERATION WAYS
motor

mo
position: fNew eco control system (ECO)
MIDDLE

de
1,2m

si
f Energy Saving
ig ht TECHNICAL DETAILS
f Barrier to Insects, Dust Odours, l e ft o r r
1,4m Infrared
Remote
Pollutants & Humidity
f Controlled Microclimate OPTIONAL
TYPE
Max door width (m)
L or R-33w
1.0
K-34w
1.2
K-35w
1.4
K-36w
1.6
K-37w
1.8
K-38w
2.0

1,6m
Max door height (m) 4.0 4.0 4.0 4.0 4.0 4.0
Control f Slim Line Design f Filter Max Outlet velocity (m/sec) 13 / 12 / 11 13 / 12 / 11 13 / 12 / 11 13 / 12 / 11 13 / 12 / 11 13 / 12 / 11
Max Air volume (m3/h) 2510/2315/2125 2800/2580/2370 3370/3110/2850 3930/3625/3330 4500/4430/3800 5065/4675/4285
f Easy Installation f Vertical mount Motor power input (W) 350 350 660 660 660 660

1,8m f Conventional
or Infrared Remote Control
f Inox body (430 or 316 stainless steel)
f Inox grill & body (430 or 316 stainless steel)
Capacitor (μF)
Noise level in 1 m [dB(A)]
L: Total length (mm)
8
63 / 62
1149
8
66 / 64
1242
8 or 15
66 / 64
1442
8 or 15
66 / 64
1642
8 or 15
67 / 64
1842
8 or 15
67 / 64
2042

2,0m f Motor position: Center, Left, Right f Door switch


W: Total width (mm) 212 212 212 212 212 212

DIMENSIONS
H: Height (mm) 205 205 205 205 205 205
l: Outlet length (mm) 900 1199 1400 1601 1802 2003
w: Outlet width (mm) 76 76 76 76 76 76
h: Outlet height (mm) 64 64 64 64 64 64
Weight (kgr) 19 22 24 26 28 30
Power supply (V/Hz/N~) 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1
FOR USE IN: DEPARTMENTS STORES, LARGE HOTELS, LARGE FAST FOODS, Motor speed (rpm) 1370 / 1050 1370 / 1050 1370 / 1050 1370 / 1050 1370 / 1050 1370 / 1050
LARGE SUPER MARKETS, COLD STORAGE PLANTS, AIRPORTS, BUSS STATIONS cross flow fan Ingress Protection IP20 IP20 IP20 IP20 IP20 IP20

& in general LARGE, CROWED & FREQUENTLY VISITED PLACES Φ 120 diameter *Company OLEFINI reserves the right to alter given product specifications without further notice.

30 31
ELECTRICALLY HEATED GENERAL HOT WATER HEATED GENERAL
“w” SERIES (door height up to 3,5 m) (door height up to 3,5 m)

he

at
Infrared WORKING CONDITIONS:

exc
motor

w
i n g e le m e n t s

OPTIONAL Remote f Max Temperature 50οC

ha ng er
position:
Infrared

i o n t o p v ie
LEFT f Filter Control (environment)
RIGHT Remote
Max Humidity 80%
1,0m
f
f Vertical mount
Control
f Door switch
f Non-toxic environment
motor
1,6m
f Inox body

ct
position:
at

1/2
LEFT

ne
TECHNICAL DETAILS
he

(430 stainless steel)


w

on
i RIGHT


on
at ct
1,8m
ar

Inox grill & body


1,0m
ul c f
er s e
u p pl y c o n n
TYPE L or RWΗ-33w ΚWΗ-34w ΚWΗ-35w ΚWΗ-36w ΚWΗ-37w ΚWΗ-38w
MAXIMUM DOOR WIDTH

ly
tub (430 or 316 stainless steel)

MAXIMUM DOOR WIDTH


sup p po w er Max door width (m) 1.0 1.2 1.4 1.6 1.8 2.0
motor Max door height (m) 3.5 3.5 3.5 3.5 3.5 3.5
position: TECHNICAL DETAILS f Energy Saving Max Outlet velocity (m/sec) 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5 motor
MIDDLE f Energy Saving Max Air volume (m3/h) 1740 / 1450 1950 / 1625 2340 / 1950 2730 / 2275 3125 / 2600 3515 / 2930 position:
f Barrier to Insects, Dust Odours, MIDDLE
1,2m
Motor power input (W) 350 350 660 660 660 660
TYPE L or REΗ-33w ΚΕΗ-34w ΚΕΗ-35w ΚΕΗ-36w ΚΕΗ-37w ΚΕΗ-38w f Barrier to Insects,
Pollutants & Humidity
1,2m
Max door width (m) 1.0 1.2 1.4 1.6 1.8 2.0 Capacitor (μF) 8 8 8 or 15 8 or 15 8 or 15 8 or 15
Max door height (m) 3.5 3.5 3.5 3.5 3.5 3.5
Dust Odours, Capacity (lt) 0.8 0.8 1.0 1.2 1.4 1.6
f Slim Line Design
1,4m
Max Outlet velocity (m/sec) 12.0 / 10.0 12.0 / 10.0 12.0 / 10.0 12.0 / 10.0 12.0 / 10.0 12.0 / 10.0 Pollutants & Humidity Noise level in 1 m [dB(A)] 65 / 62 65 / 62 65 / 62 65 / 62 65 / 62 65 / 62

1,4m
L: Total length (mm) 1149 1242 1442 1642 1842 2042
Max Air volume (m3/h) 2320 / 1930 2590 / 2160 3110 / 2600 3630 / 3024 4150 / 3460 4675 / 3895 f Easy Installation f Slim Line Design W: Total width (mm) 277 277 277 277 277 277

DIMENSIONS
Motor power input (W) 350 350 660 660 660 660
f Low Noise Level
1,6m
Capacitor (μF) 8 8 8 or 15 8 or 15 8 or 15 8 or 15 f Easy Installation H: Height (mm) 205 205 205 205 205 205

1,6m
l: Outlet length (mm) 900 1199 1400 1601 1802 2003
Noise level in 1 m [dB(A)] 62 / 60 65 / 62 65 / 62 65 / 62 66 / 62 66 / 60 f 9, 12, 15 or 18kW thermal load* f Low Noise Level w: Outlet width (mm) 76 76 76 76 76 76
L: Total length (mm) 1149 1242 1442 1642 1842 2042
(depends on the models size) h: Outlet height (mm)

1,8m
64 64 64 64 64 64
W: Total width (mm) 277 277 277 277 277 277 f Water valve connections
DIMENSIONS

1,8m
Weight without water (kgr) 26 30 32 35 37 39
H: Height (mm) 205 205 205 205 205 205 f Motor position: f 1/2” water supply connection *Air Inlet Temperature +150C *Water Inlet Temperature +700C Flow rate 0.6 (lt/sec) [ 0.3 lt/sec for R,L ]
l: Outlet length (mm) 900 1199 1400 1601 1802 2003
Center, Left, Right Heating power (kW) 12.5 / 11.3 14.1 / 12.8 17.0 / 15.4 20.0 / 17.9 22.4 / 20.3 25.1/ 22.8

2,0m
w: Outlet width (mm) 76 76 76 76 76 76 f Motor position:

2,0m
Air outlet temperature (0C) 35.8 / 37.7 36.1 / 37.9 36.1 / 37.9 36.1 / 37.9 35.9 / 37.7 35.7 / 37.6
h: Outlet height (mm) 64 64 64 64 64 64 f Room thermostat
Weight (kgr) 28 31 34 37 39 41 Center, Left, Right Water outlet temperature (0C) 59.9 / 60.8 64.3 / 64.8 63.1 / 63.8 60.7 / 62.7 60.9 / 61.7 59.8 / 60.8
Thermal power (kW) 9 / 12 12 / 15 12 / 15 12 / 15 15 / 18 15 / 18 f Door switch Pressure drop (water) ΔP (kPa) 3.6 2.9 3.1 3.3 3.4 3.6
Max current cons. (A) (per phase) 13 / 17.5 17.5 / 22 18 / 22 18 / 22 22 / 26 22 / 26 *Air Inlet Temperature +150C *Water Inlet Temperature +900C Flow rate 0.6 (lt/sec) [ 0.3 lt/sec for R,L ]
T outlet - Τ inlet (0C) 18-20 / 20-24 16-18 / 18-20 15-17 / 17-19 14-16 / 16-18 15-17 / 19-22 14-16 / 17-20 Heating power (kW) 17.2 / 15.6 19.5 / 17.7 23.4 / 21.2 28.0 / 24.6 30.9 / 28.0 34.6 / 31.4
Power supply (V/Hz/N~) 400/50/3L+N 400/50/3L+N 400/50/3L+N 400/50/3L+N 400/50/3L+N 400/50/3L+N Air outlet temperature (0C) 43.7 / 46.3 44.1 / 46.6 44.1 / 46.6 39.8 / 46.5 43.8 / 46.3 43.6 / 46.1
Motor speed (rpm) 1380 / 1150 1380 / 1150 1380 / 1150 1380 / 1150 1380 / 1150 1380 / 1150 Water outlet temperature (0C) 75.9 / 77.2 82.0 / 82.8 80.4 / 81.3 77.0 / 79.9 77.3 / 78.5 75.9 / 77.2
Heating stages 4 4 4 4 4 4 Pressure drop (water) ΔP (kPa) 3.5 2.8 2.9 3.1 3.3 3.5
Ingress Protection IP20 IP20 IP20 IP20 IP20 IP20
*Company OLEFINI reserves the right to alter given product specifications without further notice.

32 33
HOT-COLD WATER HEATED GENERAL
“w” SERIES (door height up to 3,5 m)

motor side
MIDDLE
1,2m WORKING CONDITIONS:
f Max Temperature 50οC (environment)

1,4m OPERATION WAYS


DOOR WIDTH

f Max Humidity 80%


f New eco control system ECO
f Non-toxic environment
1,6m
MAXIMUM

TECHNICAL DETAILS
1,8m r TYPE ΚWΗC-34w ΚWΗC-35w ΚWΗC-36w ΚWΗC-37w ΚWΗC-38w

e
Max door width (m) 1.2 1.4 1.6 1.8 2.0

ng
2,0m
Infrared Max door height (m) 3.5 3.5 3.5 3.5 3.5

ter heat excha


Max Outlet velocity (m/sec) 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5
Remote Max Air volume (m3/h) 1950 / 1625 2340 / 1950 2730 / 2275 3125 / 2600 3515 / 2930
Control Motor power input (W) 350 350 350 350 350
Capacitor (μF) 8 8 8 8 8
Capacity (lt) 0.8 1.0 1.2 1.4 1.6
f Energy Saving Noise level in 1 m [dB(A)] 65 / 62 65 / 62 65 / 62 65 / 62 65 / 62
L: Total length (mm) 1249 1450 1651 1852 2053
f Barrier to Insects, Dust Odours, a
W: Total width (mm) 277 277 277 277 277

DIMENSIONS
Pollutants & Humidity
dw
H: Height (mm) 205 205 205 205 205
f Slim Line Design l: Outlet length (mm) 1199 1400 1601 1802 2003
ol
c w: Outlet width (mm) 76 76 76 76 76
f Easy Installation h: Outlet height (mm) 64 64 64 64 64
Weight without water (kgr) 30 32 35 37 39
f Low Noise Level
*Air Inlet Temperature +150C *Water Inlet Temperature +900C Flow rate 0.6 (lt/sec)

y
tr a
f Water valve connections Heating power (kW) 18.5 / 17.0 22.0 / 20.0 26.0 / 23.0 29.0 / 26.0 32.5 / 29.5
Remote n Air outlet temperature (0C) 42.0 / 45.0 42.5 / 45.0 42.0 / 45.0 42.0 / 45.0 42.0 / 44.0
f 1/2” water supply connection
Control tio
sa
Water outlet temperature (0C) 82.5 / 83.0 81.0 / 82.0 80.0 / 81.0 78.0 / 79.0 77.0 / 78.0
f Motor position: Center co n d e n
Pressure drop (water) ΔP (kPa) 3.5 / 3.5 3.7 / 3.7 4.0 / 4.0 4.0 / 4.0 4.5 / 4.5
*Air Inlet Temperature 280C / 55% RH *Water Inlet Temperature 70C - Water Outlet Temperature 120C
Heating power (kW) 5.0 / 4.0 7.0 / 6.0 9.0 / 8.0 10.5 / 9.5 12.0 / 11.0
Air outlet temperature (0C) 22.0 / 21.0 21.0 / 20.0 21.0 / 20.0 20.5 / 20.0 20.0 / 19.5
FOR USE IN: Flow rate (lt/sec) 0.6 / 0.6 0.8 / 0.8 1.0 / 1.0 1.2 / 1.0 1.4 / 1.2
Pressure drop (water) ΔP (kPa) 4.3 / 3.6 8.0 / 6.5 12.5 / 10.0 19.0 / 16.0 26.0 / 22.0
DEPARTMENTS STORES, LARGE HOTELS, LARGE FAST FOODS, LARGE SUPER MARKETS, COLD STORAGE PLANTS,
AIRPORTS, BUSS STATIONS & in general LARGE, CROWED & FREQUENTLY VISITED PLACES *Company OLEFINI reserves the right to alter given product specifications without further notice.

34 35
SIMPLE GENERAL
CASSETTE TYPE
(door height up to 4,0 m)

key for lock

motor side
MAXIMUM DOOR WIDTH

CENTER
1,2m
1,4m
1,6m WORKING CONDITIONS: Infrared

1,8m
f Max Temperature 50οC (environment) Remote
f Max Humidity 80% Control

2,0m
f Non-toxic environment
TECHNICAL DETAILS

ap
ir fl
TYPE RS-34 RS-35 RS-36 RS-37 RS-38
OPERATION WAYS

ea
Max door width (m) 1,2 1,4 1,6 1,8 2,0

bl
f New eco control system “ECO” ta 460
Max door height (m) 4,0 4,0 4,0 4,0 4,0
s Max Outlet velocity (m/sec) 11 / 10 / 9 11 / 10 / 9 11 / 10 / 9 11 / 10 / 9 11 / 10 / 9
f Door switch
a dju 405
100 100 Max Air volume (m3/h) 2600/2360/2130 3110/2825/2545 3620/3290/2960 4130/3750/3380 4632/4210/3790
Motor power input (W) 350 660 660 660 660
Capacitor (μF) 8 8 or 15 8 or 15 8 or 15 8 or 15

225
60 60 60 60 Noise level in 1 m [dB(A)] 66 / 64 66 / 64 66 / 64 67 / 64 67 / 64
L: Unit length (mm) 1255 1455 1655 1855 2055

DIMENSIONS
525 Κ: Mounting distance (mm) 1055 1255 1455 1655 1855
Ι: Total Unit length (mm) 1375 1575 1775 1975 2175
Weight (kgr) 32.5 38 43 47 52
FOR USE IN: DEPARTMENTS STORES, LARGE HOTELS, LARGE FAST FOODS, Power supply (V/Hz/N~) 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1
LARGE SUPER MARKETS, COLD STORAGE PLANTS, AIRPORTS, BUSS STATIONS cross flow fan Motor speed (rpm) 1370 / 1050 1370 / 1050 1370 / 1050 1370 / 1050 1370 / 1050

& in general LARGE, CROWED & FREQUENTLY VISITED PLACES Φ 120 diameter *Company OLEFINI reserves the right to alter given product specifications without further notice.

36 37
ELECTRICALLY HEATED GENERAL HOT WATER HEATED GENERAL
CASSETTE TYPE wa
TYPE CASSETTE
(door height up to 3,5 m) te (door height up to 3,5 m)
r

va
lve
heat resistances
lar

w at
u

c on
b
tu WORKING CONDITIONS:

er he at e d
e n c ti o n
f Max Temperature 50οC
(environment)
f Max Humidity 80%
f Non-toxic environment

TECHNICAL DETAILS
motor side

MAXIMUM DOOR WIDTH


Infrared TYPE RSWH-34 RSWH-35 RSWH-36 RSWH-37 RSWH-38 CENTER
Remote
Control
Max door width (m)
Max door height (m)
1.2
3.5
1.4
3.5
1.6
3.5
1.8
3.5
2.0
3.5 1,2m
ox
Max Outlet velocity (m/sec) 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5 9.0 / 7.5
el
ec nb 1,4m
Max Air volume (m3/h) 1950 / 1625 2340 / 1950 2730 / 2275 3125 / 2600 3515 / 2930
tric
al c o n n e ctio Motor power input (W)
Capacitor (μF)
350
8
660
8 or 15
660
8 or 15
660
8 or 15
660
8 or 15

1,6m
Noise level in 1 m [dB(A)] 66 / 64 66 / 64 66 / 64 67 / 64 67 / 64
TECHNICAL DETAILS L: Unit length (mm) 1255 1455 1655 1855 2055

DIMENSIONS
f Energy Saving f Energy Saving Κ: Mounting distance (mm) 1055 1255 1455 1655 1855

1,8m
Ι: Total Unit length (mm) 1375 1575 1775 1975 2175
f Barrier to Insects, TYPE RSEH-34 RSEH-35 RSEH-36 RSEH-37 RSEH-38 f Barrier to Insects, Power supply (V/Hz/N~) 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1
Max door width (m) 1,2 1,4 1,6 1,8 2,0
Dust Odours, Max door height (m) 3.5 3.5 3.5 3.5 3.5 Dust Odours, Motor speed (rpm) 1370 / 1050 1370 / 1050 1370 / 1050 1370 / 1050 1370 / 1050

2,0m
Pollutants & Humidity Max Outlet velocity (m/sec) 10 / 8 10 / 8 10 / 8 10 / 8 10 / 8 Pollutants & Humidity Water volume (lt)
Weight (kgr)
0.8
36
1.0
43
1.2
48
1.4
53
1.6
58
f Controlled Microclimate Max Air volume (m3/h) 2350 / 1880 2800 / 2240 3290 / 2630 3750 / 3000 4210 / 3365
Motor power input (W) 350 660 660 660 660 f Controlled Microclimate *Air Inlet Temperature +150C *Water Inlet Temperature +70 C
0
Flow rate 0.3 (lt/sec)
Heating power (kW) 15 / 13 17 / 15 19 / 16 21 / 20 24 / 22
f Room Thermostat Capacitor (μF) 8 8 or 15 8 or 15 8 or 15 8 or 15 f 1/2” water supply Water outlet temperature (0C) 58 /59 56 / 57 54 / 56 52 / 54 51 /52
Noise level in 1 m [dB(A)] 65 / 62 66 / 64 66 / 64 67 / 64 67 / 64
f Door switch L: Unit length (mm) 1255 1455 1655 1855 2055 connection Air outlet temperature (0C) 37 / 39 36 / 38 36 / 37 35 / 37 35 / 37
DIMENSIONS

Pressure drop (water) ΔP (kPa) 4.1 4.4 4.8 5.2 5.5


Κ: Mounting distance (mm) 1055 1255 1455 1655 1855
*Air Inlet Temperature +150C *Water Inlet Temperature +900C Flow rate 0.3 (lt/sec)
Ι: Total Unit length (mm) 1375 1575 1775 1975 2175
Heating power (kW) 20 / 18 23 / 21 27 / 24 30 / 27 33 / 30
Weight (kgr) 34 40 45 50 55
Water outlet temperature (0C) 74 / 75 71 / 72 68 / 70 66 / 67 64 / 65
Power supply (V/Hz/N~) 400/50/3L+N 400/50/3L+N 400/50/3L+N 400/50/3L+N 400/50/3L+N
Air outlet temperature (0C) 45 / 48 44 / 47 44 / 46 43 / 46 42 / 45
Motor speed (rpm) 1370 / 1050 1370 / 1050 1370 / 1050 1370 / 1050 1370 / 1050
Pressure drop (water) ΔP (kPa) 3.9 4.2 4.6 4.9 5.3
Thermal power (kW) 12 12 12 15 - 18 - 21 15 - 18 - 21
Max current cons. (A) (per phase) 17.5 17.5 17.5 22 - 26 - 30.5 22 - 26 - 30.5
*Company OLEFINI reserves the right to alter given product specifications without further notice.

38 39
SIMPLE & ELECTRICALLY HEATED GENERAL
“C” SERIES (door height up to 4,0 m)

l
f Energy Saving
n p an e
f Barrier to Insects, ti o
Dust Odours,

c
ne
Pollutants & Humidity

co n
f Controlled Microclimate
f Modern Design
f Easy Installation
f 4 different external
fl a

p
face combinations ir
le a
1,2m OPERATION WAYS a dju sta b

1,6m f New eco control system “ECO”

OPTIONAL
2,0m f Concealed face lighting
Remote
f Vertical mount Control
MAXIMUM
DOOR
WIDTH

f Ability to print
different external faces
f Able to connect with a BMS system 220
TECHNICAL DETAILS
110
A
WORKING CONDITIONS: Infrared TYPE C-120 C-160 C-200 CEH-120 CEH-160 CEH-200
Max door width (m) 1.2 1.6 2.0 1.2 1.6 2.0
f Max Temperature 50οC Remote Max door height (m) 4.0 4.0 4.0 4.0 4.0 4.0
Control

324

360
(environment) Max Outlet velocity (m/sec) 18.0 / 13.0 18.0 / 13.0 18.0 / 13.0 18.0 / 13.0 18.0 / 13.0 18.0 / 13.0
Max Air volume (m3/h) 2140 / 1545 3210 / 2315 4275 / 3090 2140 / 1545 3210 / 2315 4275 / 3090
f Max Humidity 80% Motor power input (W) 420 630 840 420 630 840
f Non-toxic environment 300 255 270 245 Capacitor (μF) 12 12 12 12 12 12
B
15 A2 A1 F2 F1

DIMENSIONS
A: Total length (mm) 1300 1852 2417 1300 1852 2417

FOR USE IN:SALONS, HEALTH SPAS, BARS, B: Air outlet length (mm) 1120 1670 2237 1120 1670 2237
Power supply (V/Hz/N~) 230/50/1 230/50/1 230/50/1 400/50/3L+N 400/50/3L+N 400/50/3L+N
CAFETERIAS, PASTRY SHOP, BREWERIES, SMALL HOTELS, centrifugal fan Max Motor speed (rpm) 2700 / 1950 2700 / 1950 2700 / 1950 2700 / 1950 2700 / 1950 2700 / 1950
BANKS, SCHOOLS, SUPER MARKETS, FISH MONGER SHOPS, Φ 115 diameter Heating power (kW) - - - 15 18 18

SMALL COLD STORAGE PLANTS *Company OLEFINI reserves the right to alter given product specifications without further notice.

40 41
SIMPLE & ELECTRICALLY HEATED
GENERAL
“ANEMOESSA” SERIES a dj
ustable airfl ap
(door height up to 4,0 m)
l connection
p an e
l l e ctrica box
n e
OPTIONAL ti o

c
f Vertical mount

ne
co n
f Ability to print
different external faces
Remote ck
r lo
f Able to connect
with a BMS system Control fo

y
WORKING CONDITIONS:

ke
f Max Temperature 50οC

1,2m OPERATION WAYS (environment)


f New eco control f Max Humidity 80%

1,6m
o st a t s Non-toxic environment
system “ECO” h er m
f
t
fety
a
2,0m
s

f Energy Saving
MAXIMUM
DOOR
WIDTH

f Barrier to Insects,
Dust Odours,
Pollutants & Humidity TECHNICAL DETAILS
f Controlled Microclimate TYPE AN-120 AN-160 AN-200 ANEH-120 ANEH-160 ANEH-200
f Modern Design A
224 Max door width (m) 1.2 1.6 2.0 1.2 1.6 2.0
Max door height (m) 4.0 4.0 4.0 4.0 4.0 4.0
f Easy Installation Max Outlet velocity (m/sec) 18.0 / 13.0 18.0 / 13.0 18.0 / 13.0 18.0 / 13.0 18.0 / 13.0 18.0 / 13.0

402
Max Air volume (m3/h) 2140 / 1545 3210 / 2315 4275 / 3090 2140 / 1545 3210 / 2315 4275 / 3090
f High Velocity
Motor power input (W) 420 630 840 420 630 840
& Static Pressure Fans Infrared Capacitor (μF) 12 12 12 12 12 12
Remote

13,5
B

DIMENSIONS
17 A: Total length (mm) 1188 1746 2304 1188 1746 2304
Control B: Air outlet length (mm) 1158 1716 2274 1158 1716 2274
Power supply (V/Hz/N~) 230/50/1 230/50/1 230/50/1 400/50/3L+N 400/50/3L+N 400/50/3L+N
FOR USE IN: SALONS, HEALTH SPAS, BARS, CAFETERIAS, Max Motor speed (rpm) 2700 / 1950 2700 / 1950 2700 / 1950 2700 / 1950 2700 / 1950 2700 / 1950
Heating power (kW) - - - 15 18 21
PASTRY SHOP, BREWERIES, SMALL HOTELS, BANKS, SCHOOLS,
SUPER MAR KETS, FISH MONGER SHOPS, SMALL COLD STORAGE PLANTS *Company OLEFINI reserves the right to alter given product specifications without further notice.

42 43
AIR CURTAINS
INDUSTRIAL
for maximum door height 6,0m
SIMPLE INDUSTRIAL
(door height up to 6,0 m)

to
mo
le ft or rig ht side
WORKING CONDITIONS:
f Max Temperature 50οC
Infrared
motor Remote
position: (environment)
LEFT Control OPTIONAL
MAXIMUM DOOR WIDTH

RIGHT
f Max Humidity 80%
f Filter
1,0m
f Non-toxic environment
f Vertical mount
Energy Saving f Inox body TECHNICAL DETAILS
1,2m
f
f Barrier to Insects, Dust Odours, (430 or 316)
TYPE L or R-22 L or R-23 K-24 K-26 K-28
Pollutants & Humidity OPERATION WAYS f Inox grill Max door width (m) 1.0 1.2 1.2 1.6 2.0
motor
position: f Controlled Microclimate f New eco control system “ECO” (430 or 316) Max door height (m) 6.0 6.0 6.0 6.0 6.0
MIDDLE f Slim Line Design
Max Outlet velocity (m/sec) 14 / 13 / 12 14 / 13 / 12 14 / 13 / 12 14 / 13 / 12 14 / 13 / 12

1,2m
Max Air volume (m3/h) 3050/2830/2615 3715/3425/3185 3035/2815/2600 4245/3940/3640 5580/5180/5280
f Easy Installation Motor power input (W) 660 660 660 660 660
Capacitor (μF) 12 12 8 or 15 8 or 15 15
f Conventional
1,6m
Noise level in 1 m [dB(A)] 68 / 65 68 / 65 68 / 65 68 / 65 68 / 65
or Infrared Remote Control L: Total length (mm)
W: Total width (mm)
1270
231
1491
231
1259
231
1663
231
2097
231

DIMENSIONS
f Motor position:

2,0m
H: Height (mm) 227 227 227 227 227
Center, Left or Right l: Outlet length (mm)
w: Outlet width (mm)
1015
76
1236
76
1200
76
1603
76
2044
76
f Door switch h: Outlet height (mm) 64 64 64 64 64
Weight (kgr) 24 27 27 31 36
Power supply (V/Hz/N~) 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1 230 / 50 / 1
FOR USE IN: LARGE INDUSTRIAL SPACES, Motor speed (rpm) 1370 / 1100 1370 / 1100 1370 / 1100 1370 / 1100 1370 / 1100
DOORS & PASS THROUGH OPENINGS, AIRPORTS, BUSS STATIONS, cross flow fan Ingress Protection IP20 IP20 IP20 IP20 IP20

STORAGE AREAS, LARGE COLD STORAGE PLANTS, GARAGES, STADIUMS Φ 133 diameter *Company OLEFINI reserves the right to alter given product specifications without further notice.

46 47
ELECTRICALLY HEATED INDUSTRIAL HOT WATER HEATED INDUSTRIAL
s u p pl y c o n (door height up to 5,0 m)
“CLASSIC” SERIES (door height up to 5,0 m) ’w
a ter n ec

tio

1/2

n
n
WORKING CONDITIONS:
io

to
ect

pv

nger
Infrared f Max Temperature 50οC (environment)
ply c o n n

ie w
Remote OPTIONAL f Max Humidity 80%

a
xc h
motor Control f Filter f Non-toxic environment

e
position: at
LEFT f Vertical mount he TECHNICAL DETAILS
r su p

RIGHT f Door switch motor

1,0m
TYPE L or RWΗ-22 L or RWΗ-23 ΚWΗ-24 ΚWΗ-26 ΚWΗ-28 position:
f Energy Saving
e

f Inox body (430 or 316) LEFT

MAXIMUM DOOR WIDTH


Max door width (m) 1.0 1.2 1.2 1.6 2.0
ow

f Barrier to Insects, Max door height (m) 5.0 5.0 5.0 5.0 5.0 RIGHT
1,2m 1,0m
p

TECHNICAL DETAILS Dust Odours, Max Outlet velocity (m/sec) 11.0 / 8.5 11.0 / 8.5 11.0 / 8.5 11.0 / 8.5 11.0 / 8.5
Max Air volume (m3/h) 2425 / 1870 2935 / 2270 2390 / 1845 3350 / 2570 4395 / 3395
TYPE L or REΗ-22 L or REΗ-23 L or REΗ-27 ΚΕΗ-24 ΚΕΗ-26 ΚΕΗ-28
Pollutants & Humidity Motor power input (W) 660 660 660 660 660

1,8m 1,2m
f Slim Line Design Capacitor (μF) 12 12 8 or 15 8 or 15 8 or 15
f Energy Saving Max door width (m) 1.0 1.2 1.8 1.2 1.6 2.0
MAXIMUM DOOR

Max door height (m) 5.0 5.0 5.0 5.0 5.0 5.0 Capacity (lt) 1.0 1.28 0.96 1.4 1.88
f Barrier to Insects, f Easy Installation Noise level in 1 m [dB(A)] 64 / 60 64 / 60 67 / 64 67 / 64 67 / 64
Max Outlet velocity (m/sec) 13.0 / 11.0 13.0 / 11.0 13.0 / 11.0 13.0 / 11.0 13.0 / 11.0 13.0 / 11.0
L: Total length (mm) 1270 1491 1259 1663 2097
motor Dust Odours, Max Air volume (m3/h) 2830 / 2400 3450 / 2920 5050 / 4285 2815 / 2380 3940 / 3335 5180 / 4385 f Low Noise Level motor
position: W: Total width (mm) 306 306 306 306 306 position:

DIMENSIONS
Motor power input (W) 660 660 660 660 660 660
MIDDLE Pollutants & Humidity Capacitor (μF) 12 12 15 8 or 15 8 or 15 8 or 15 f 1/2” water supply connection H: Height (mm) 227 227 227 227 227 MIDDLE
1,2m 1,2m
l: Outlet length (mm) 1015 1236 1200 1603 2044
f Slim Line Design Noise level in 1 m [dB(A)] 67 / 64 67 / 64 67 / 64 67 / 64 67 / 64 67 / 64 f Motor position:
L: Total length (mm) 1270 1491 2090 1259 1663 2097 w: Outlet width (mm) 76 76 76 76 76
f Easy Installation Center, Left, Right h: Outlet height (mm) 64 64 64 64 64
DIMENSIONS

W: Total width (mm) 306 306 306 306 306 306

1,6m 1,6m
Weight without water (kgr) 31 34 32 37 48
f 15 or 18 kW thermal load* H: Height (mm) 227 227 227 227 227 227
WIDTH

*Air Inlet Temperature +150C *Water Inlet Temperature +700C Flow rate 0.6 (lt/sec) [ 0.3 lt/sec for R,L ]
l: Outlet length (mm) 1015 1236 1803 1200 1603 2044
(depending on models size) w: Outlet width (mm) 76 76 76 76 76 76 Heating power (kW) 16.0 / 14.0 19.0 / 17.0 16.0 / 14.0 23.0 / 20.0 29.0 / 26.0

2,0m
Air outlet temperature (0C) 34 / 37 34 / 36 35 / 38 35 / 37.5 34 / 37
Motor position: Center,
2,0m
f h: Outlet height (mm) 64 64 64 64 64 64
Water outlet temperature (0C) 57 / 58 54.5 / 56 63 / 64 61 / 62 58 / 59.5
Left or Right Weight (kgr)
Thermal power (kW)
36
15 / 18
40
15 / 18
52
15 / 18
40
15 / 18
45
15 / 18
51
18 Pressure drop (water) ΔP (kPa) 3.5 3.8 2.7 3.0 3.3
f Door switch Max current cons. (A) (per phase) 22 / 26 22 / 26 22 / 26 22 / 26 22 / 26 26 *Air Inlet Temperature +150C *Water Inlet Temperature +900C Flow rate 0.6 (lt/sec) [ 0.3 lt/sec for R,L ]
T outlet - Τ inlet (0C) 17-18 / 19-20 17-18 / 19-20 17-18 / 19-20 17 / 18 17-18 / 19-20 19-20 Heating power (kW) 22.0 / 19.5 26.0 / 23.0 23.0 / 20.0 31.5 / 27.5 41.0 / 36.0
Power supply (V/Hz/N~) 400/50/3L+N 400/50/3L+N 400/50/3L+N 400/50/3L+N 400/50/3L+N 400/50/3L+N Air outlet temperature (0C) 41 / 45 41 / 45 43 / 46 42 / 46 42 / 45.5
Motor speed (rpm) 1380 / 1150 1380 / 1150 1380 / 1150 1380 / 1150 1380 / 1150 1380 / 1150 Water outlet temperature (0C) 72 / 74 68.5 / 71 81 / 82 77 / 79 73 / 75
Heating stages 4 4 4 4 4 4 Pressure drop (water) ΔP (kPa) 3.3 3.6 2.6 2.9 3.2
Ingress Protection IP20 IP20 IP20 IP20 IP20 IP20
*Company OLEFINI reserves the right to alter given product specifications without further notice.

48 49
SIMPLE SPECIAL
TYPE 12V or 24V SUPPLY
“TRUCK” SERIES
(door height up to 2,5 m)

NEW
MODEL

f Modern Design
f Door switch
f Energy Saving
f Barrier to Insects,

AIR CURTAINS OPTIONAL Dust Odours,


Pollutants & Humidity
f Inox body (430 or 316)
f Controlled Microclimate
f Inox grill (430 or 316)

SPECIAL TYPE f Motor with IP 20


system protection

125
TECHNICAL DETAILS
TYPE DCT-12 DCT-15 DCT-18 DCT-12 DCT-15 DCT-18
135 Max door width (m) 1.2 1.5 1.8 1.2 1.5 1.8
Max door height (m) 2.5 2.5 2.5 2.5 2.5 2.5
Max Air volume (m3/h) 1635 2100 2580 1635 2100 2580
L: Total length (mm) 1204 1502 1802 1204 1502 1802

DIMENSIONS
I: Air outlet length (mm) 1150 1450 1750 1150 1450 1750
Power supply (V/Hz/N~) 12V 12V 12V 24V 24V 24V
Motor speed (rpm) 1800 1800 1800 1800 1800 1800
Max current cons. (A) 9 10 12 4 5 5.7
Max power cons. (W) 108 180 216 96 120 137
cross flow fan
Φ 80 diameter *Company OLEFINI reserves the right to alter given product specifications without further notice.

51
SIMPLE & ELECTRICALLY HEATED SIMPLE & ELECTRICALLY HEATED
SPECIAL TYPE “RV” SERIES (door height up to 4,0 m) SPECIAL TYPE “RV” vertical SERIES
NEW
(door height up to 2,8 m)

NEW
MODEL
MODEL
Application
OPTIONAL on revolving doors
f Inox body (430)
f Able to connect
with a BMS system

OPERATION WAYS
f New eco control
system “ECO”
f Modern Design
f Energy Saving
Remote f Barrier to Insects, Dust Odours,
Infrared Remote
Control Pollutants & Humidity Remote
Infrared f Controlled Microclimate
Control
Control
Remote
Control TECHNICAL DETAILS
TECHNICAL DETAILS TYPE RV-230V RVEH-230V RV-280V RVEH-280V
Max door width (m) 2.4 2.4 2.4 2.4
TYPE RV-120 RV-160 RV-200 RVEH-120 RVEH-160 RVEH-200 Max door height (m) 2.3 2.3 2.8 2.8
Max door width (m) 1.2 1.6 2.0 1.2 1.6 2.0 Max Outlet velocity (m/sec) 13.0/10.0 13.0/10.0 13.0/10.0 13.0/10.0
Max door height (m) 4.0 4.0 4.0 4.0 4.0 4.0 Max Air volume (m3/h) 3090/2380 3090/2380 3860/2970 3860/2970
Max Outlet velocity (m/sec) 18.0/13.0 18.0/13.0 18.0/13.0 18.0/13.0 18.0/13.0 18.0/13.0 Motor power input (W) 440 440 550 550
Max Air volume (m3/h) 2140/1545 3210/2315 4275/3090 2140/1545 3210/2315 4275/3090 Capacitor (μF) 3 3 3 3
Motor power input (W) 420 630 840 420 630 840

DIMENSIONS
A: Total length (mm) 2361 2361 2920 2920
Capacitor (μF) 12 12 12 12 12 12
B: Air outlet length (mm) 2296 2296 2855 2855
DIMENSIONS

A: Total length (mm) 1300 1852 2417 1300 1852 2417


Power supply (V)/Hz/N~) 230/50/1 400/50/3L+N 230/50/1 400/50/3L+N
B: Air outlet length (mm) 1120 1670 2237 1120 1670 2237
FOR USE IN: Power supply (V)/Hz/N~) 230/50/1 230/50/1 230/50/1 400/50/3L+N 400/50/3L+N 400/50/3L+N
Max Motor speed (rpm)
Thermal load (kW)
1400
-
1400
18
1400
-
1400
18
HOTELS, AIR PORTS, Max Motor speed (rpm) 2700 2700 2700 2700 2700 2700
Thermal load (kW) - - - 15 18 18
BANKS, SHOPPING CENTERS, etc. *Company OLEFINI reserves the right to alter given product specifications without further notice.

52 53
AIR CURTAINS
IP 24 for maximum door height 6,0m
IP 24 GENERAL& INDUSTRIAL
“CLASSIC” SERIES (door height up to από 3,0m up to 6,0m)

ns
tio

ec
nn
e co
r proof cabl
WORKING CONDITIONS:
le connections
wa te

f c ab f Max Temperature 50οC (environment)


Infrared
65 sy
stem prote oo f Max Humidity 80%
IP ctio pr Remote
ith n f Non-toxic environment Control

r
te
r w

wa
to

b ox
ctrical
mo

le
5 5e
e m e nts IP
g el
a tin
he Remote
Control
f
oo
r pr
wate

*Dimensions
and technicalspecifications
are the same with standard
“GENERAL & INDUSTRIAL”
purpose models. *Company OLEFINI reserves the right to alter given product specifications without further notice.

56 57
EXHIBITIONS

...is everywhere

Febrava 2015, Sao Paolo

Climatherm 2016, Athens

Mostra 2018, Milan Sodex 2014, Constantinople


www.rapidcool.ae ..
ABOUT US
Established in 1995 through a small trading office in Dubai, Rapid
Cool Group of Companies is a leading supplier of high-quality
products in the HVAC industry. Today, the group has branches
across the UAE with offices in Dubai and Sharjah along with
regional partners in the Gulf. Our team comprises of highly skilled
employees who continue to ensure high quality customer
satisfaction. Over the past two decades, Rapid Cool has been
fortunate to be part of several major developments both in the
UAE and Gulf. Rapid Coal's operations can be categorized into two
major divisions:

TRADING DIVISION
The trading division is an exclusive distributor of major HVAC
brands from Europe and USA. The product range includes
ventilation fans (local civil defense approved), ecology units,
vibration isolators & central a/c components, air curtains, acoustic
lagging and sound attenuators.

SERVICE DIVISION
Recently introduced, the service division complements Rapid
Cool's manufacturing and trading division as it focuses on
installations, maintenance and after sales. Our dedicated and
highly experienced team can attend to all types of site issues.
14. PRODUCT GUARANTEES AND
WARRANTIES
WARRANTY CERTIFICATE - # TO,
-----------------

Product: AIR CURTAIN


Model: RS-34 (10 Nos) & RS-37 (03 Nos)
Purchase Date:
-----------------

Warranty start Date: Warranty Expiry Date:


----------------------- -------------------------

Project Details:

SHEIKH KHALIFA MEDICAL CITY OUTPATIENT SPECIALITY CLINIC PROJECT MAINTENANCE AND REFURBISHMENT
Warranty Condition:
This is to certifythat the OLEFINI Air curtains supplied above are warranted against any manufacturing defects during the
warranty period indicated above (1 year from the date of project handover). This warranty is subjected to maintaining of
installation & operation limits as per the manufacturer’s recommended procedures and recommended periodic
maintenance. Warranty shall be deemed null & void due to any improper installation, misuse / mishandling, etc. Under this
warranty, Rapid Cool Trading Co. LLC will be provided the opportunity to have one of its representatives assess any damage
before processing warranty claims. This warranty does not include normal wear and tear.

Authorized Signature:

Page: 1 / 1