Professional Documents
Culture Documents
Real Time Detection and Control of Loss of Synchronism Using Energy Function Criterion and Phase Sequence Exchange Technique
Real Time Detection and Control of Loss of Synchronism Using Energy Function Criterion and Phase Sequence Exchange Technique
Abstract—Transient instability is a well-known problem in a this change and gets activated. On activation, PSE reverses the
power grids. The severe faults in the power grid may lead to phase sequence across the line and thereby prevents the system
blackout, if proper out-of-step protection is not implemented. from getting out of step, without implementing conventional
Phase sequence exchange (PSE) is a newly developed emergency
control technique, in which power electronic devices are used to emergency control.
change the phase sequence, thereby reducing the power angle of Many countries interconnect their regional grid to form
an equivalent dual power supply system by 120° and preventing a central grid functioning at one frequency. India has also
the system from becoming unstable. This paper proposes a fast synchronously connected its regional grids in order to encour-
and accurate technique for controlling PSE devices by generating age one nation one grid. These interconnections may undergo
switching signals using local measurement after detection of
unstable swings and shows the effectiveness of PSE in stabilizing unstable power swing due to some severe disturbance, which
a multi-machine system. The proposed technique uses energy results in the splitting of the grid, and at last, the islanded grid
function for determining unstable swing. The proposed technique may collapse. These splitting can be avoided by stabilizing the
has been tested on the IEEE 39-bus test system on a real-time system using the PSE technique.
digital simulator (RTDS), and the results show that the proposed References [7], [8] propose the mechanism for implement-
control technique for the PSE device is effective.
Index Terms—Energy function, phase sequence exchange, tran- ing phase sequence exchange technology to improve stability
sient instability, control technique, local measurement, unstable of AC transmission system. The design of a solid state device
swing. for PSE was proposed in [9], [10], and a scheme to reduce the
impulse current and torque produced by PSE is suggested in
I. I NTRODUCTION [11]. Reference [12] proposes the use of PSE technique in a
unstable swings are damped and the system is prevented from where n is the total number of line belonging to the critical
splitting. cutset.
2022 IEEE PES Innovative Smart Grid Technologies – Asia (ISGT Asia) 531
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY KANPUR. Downloaded on September 23,2023 at 14:14:37 UTC from IEEE Xplore. Restrictions apply.
The kinetic energy, VKE , that causes the system to split, where Vi is the voltage of bus i, Vj is the voltage of bus j
is the same as that of an equivalent infinite-bus one-generator with respect to bus Vi , Il is current in line l joining bus i and
system with inertia constant Meq and angular speed ωeq [15] j and Zl is the impedance of line l. When the condition for
and, hence, VKE can be expressed as, unstable swing is detected, the switching signal is transmitted
1 to the PSE devices on lines of the critical cutset. After the
2
VKE = Meq (ωeq ) (7) operation of PSE, the phase angle of the line gets reduced by
2
120◦ , and its total potential energy gets reduced and becomes
where δm δm −120◦
MA MB dδl VP El = (Pl − Pls )dδl + (Pl − Pls )dδl (10)
Meq = , ωeq = ωA − ωB = δ◦ δm
M A + MB dt
which is simplified as,
MA = Mi , MB = Mi δm −120◦
i∈area A i∈area B
VP El = (Pl − Pls )dδl (11)
Mi is the inertia constant of generator i, ωA and ωB are the δ◦
generator speeds in area A and area B, respectively. Hence, As a result, the system’s total energy reduces below its critical
the kinetic energy given by (7) can be written as follows: value (2), which prevents the system from losing synchronism.
2 The above technique is summarized by the flow chart as shown
1 dδl
VKE = Meq (8) in Fig.4.
2 dt
For the system to have an unstable swing, its kinetic energy Start
must be greater than zero when potential energy within any
line of critical cutset attains its maximum value, which occurs
Fault clearing
at point d, as shown in Fig. 3. Potential energy in a line given
by (3) attains its maximum value when Pl = Pls . Kinetic
energy of a system given by (8) directly depends on | dδ dt | and
l Real-time monitoring of and Activate all the PSE
devices in the Critical
hence, it will be greater than zero for | dδ
dt
l
| > 0. For positive at the cut-set lines
cutset lines
(t) (t−τ ) (t) (t−τ )
slope, |δl | > |δl |, where δl | and δl is the sample
of δl measured at the instants t and t − τ , t is the current Yes
sampling instant and τ is the sampling period. Yes
No No
Pre-Fault Stop
a
III. S IMULATION R ESULTS
d The effectiveness of the presented control technique was
Fault tested on the IEEE 39-bus 10-machine test system [14]. The
single line diagram of the test system is shown in Fig. 5. The
simulation were carried out on RTDS platfom.
In order to create a severe disturbance, a three-phase fault
of duration 0.26s was simulated at bus 17 of Fig. 5, which
Fig. 3. Pl -δl curve of critical cutset line
made the system attain an unstable swing. It can be verified
by Fig. 6 that the power angle of lines 2-1 and 8-9 gradually
increases due to additional kinetic energy gained by the system
C. Control Technique during the fault period, which splits the system into the two
From the above discussion, the condition for unstable swing areas along these lines, forming a critical cutset. The power
(t) flow along these lines corresponds to the unstable swing, as
is as follows: when Pl = Pls system is unstable if |δl | >
(t−τ )
|δl |. Pl and δl of a cutset line continuously monitored. shown in Fig. 7.
Pl obtained from a local measurement at one end of the line, When the absolute value of the slope of power angle of
while δl is calculated by measuring voltage and current at one any of these lines (8-9, 2-1) is non-zero when the power flow
end of a line and knowing the line impedance using along that line attains its pre-fault steady-state value, the PSE
devices in these lines get activated. As soon as the PSE device
Vj = Vi + jIl Zl (9) gets triggered, the power angle across these lines gets reduced
532 2022 IEEE PES Innovative Smart Grid Technologies – Asia (ISGT Asia)
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY KANPUR. Downloaded on September 23,2023 at 14:14:37 UTC from IEEE Xplore. Restrictions apply.
200
2-1
150 8-9
100
(Deg)
50
l
0
-50
-100
0 2 4 6 8 10
time(s)
Fig. 8. Power angle curve across the critical cutset line 2-1 and 8-9 after
PSE operation
20
2-1
Fig. 5. Single line diagram of IEEE 39-bus 10-machine test system [14] 8-9
P (p.u.) 10
200
8-9 0
l
2-1
100
-10
(Deg)
0
-20
0 2 4 6 8 10
l
time(s)
-100
Fig. 9. Power flow in the critical cutset line 2-1 and 8-9 after PSE operation
-200
0 1 2 3 4 5
The collected results demonstrate the effective performance
time(s)
of the proposed control technique for PSE devices. The suc-
Fig. 6. Power angle curve across the critical cutset line 2-1 and 8-9, illustrating cessful real-time testing using RTDS shows that the proposed
an unstable swing scheme can work effectively on an existing power system.
As the implemented control technique requires local measure-
ment, which avoids long-distance communication, it is fast and
20
8-9 reliable.
2-1
10 IV. C ONCLUSION
This paper presents an accurate control technique to
Pl (p.u.)
2022 IEEE PES Innovative Smart Grid Technologies – Asia (ISGT Asia)
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY KANPUR. Downloaded on September 23,2023 at 14:14:37 UTC from IEEE Xplore. Restrictions apply.
533
TABLE I [8] S. Huang, H. Li, Y. Li, and Y. Zhang, “The Condition of Phase
S ET OF PSE D EVICES ACTIVATED FOR FAULTS AT D IFFERENT LOCATION Sequence Exchange Technology Applied to Stability Control and
Optimal Control Strategy,” Transactions of China Electrotechnical
Society,DO10.19595/j.cnki.1000-6753.tces.200457, Sep. 2020.
Fault Bus.no Fault duration(s) Active PSE device [9] Y. Li, S. Huang, H. Li, Y. Huang, X Xiao and Y Luo, “Design and
2 0.31 1-2 , 8-9 Test of a Novel Power Electronic Device for Phase Sequence Exchange
3 0.351 1-2 , 8-9 Technology,” in International Journal of Electrical Power Energy
18 0.32 1-2 , 8-9 Systems, vol 125, DOI 10.1016/j.ijepes.2020.106550, Feb. 2021.
14 0.36 1-2 , 8-9 [10] Y. Li, S. Huang, H. Li, J. Li and H. Wu, “Improvement and Dy-
15 0.29 1-2 , 8-9 namic Simulation Test of a Power Electronic Device Applied to Phase
16 0.20 1-2 , 8-9 Sequence Exchange Technology,” in IEEE Transactions on Industrial
17 0.26 1-2 , 8-9 Electronics. DOI: 10.1109/TIE.2021.3066930.
18 0.313 1-2 , 8-9 [11] Y. Li, S. Huang, H. Li, J. Zhang, G. Huang and Y. Luo, “A New Phase
24 0.25 1-2 , 8-9 Sequence Exchanging Control Method for Reducing Impulse Current
5 0.57 10-32 and Voltage,” in IEEE Access, vol. 7, pp. 164734-164745, 2019.
8 0.45 10-32 [12] Y. Li, S. Huang, H. Li and J. Zhang, “Application of phase sequence
7 0.45 10-32 exchange in emergency control of a multi-machine system,” in Interna-
10 0.3 10-32 tional Journal of Electrical Power and Energy Systems, vol. 121, DOI
11 0.3 10-32 10.1016/j.ijepes.2020.106136, October. 2020.
13 0.38 10-32 [13] Y. Li, H. Li, S. Huang, J. Li and H. Wu, “A Local Measurement-based
27 0.23 29-38 Phase Sequence Exchange Emergency Control Approach,” in IEEE
26 0.15988 29-38 Transactions on Industrial Electronics, doi: 10.1109/TIE.2022.3142446.
28 0.159 29-38 [14] S. Chakrabarti and E. Kyriakides, “Optimal Placement of Phasor Mea-
38 0.1402 29-38 surement Units for Power System Observability,” in IEEE Transactions
on Power Systems, vol. 23, no. 3, pp. 1433-1440, Aug. 2008.
[15] A. A. Fouad and S. E. Stanton, “Transient Stability of a Multi-Machine
Power System. Part II: Critical Transient Energy,” in IEEE Transactions
The presented technique activates the PSE device only on Power Apparatus and Systems, vol. PAS-100, no. 7, pp. 3417-3424,
July 1981.
when the system becomes unstable and loses synchronism. [16] K. R. Padiyar and K. Uma Rao, “Discrete control of TCSC for
Hence implementing the presented approach would avoid stability improvement in power systems,” Proceedings of International
unnecessary switching of PSE. This control technique requires Conference on Control Applications, 1995, pp. 246-251.
real-time monitoring of power flow and power angle of the line
on which PSE devices are pre-installed (cutset lines). Real-
time testing results using RTDS show that it can be applied
to practical systems. The performance of PSE can further
increase by implementing a prediction algorithm to predict
the unstable swing and activating the PSE device, as it will
result in more reduction in the potential energy of the system.
R EFERENCES
534 2022 IEEE PES Innovative Smart Grid Technologies – Asia (ISGT Asia)
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY KANPUR. Downloaded on September 23,2023 at 14:14:37 UTC from IEEE Xplore. Restrictions apply.