Data Sheet For Flexible FR-LSH Wires

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Customer :

DATA SHEET FOR FR-LSH WIRES AS PER IS 694


( 2.5 Sq.mm to 4 Sq.mm )
Sr 1C x 2.5 1C x 4 1C x 6
Description Unit
No. SQMM SQMM SQMM
1 Description Y FR-LSH Y FR-LSH Y FR-LSH

FR-LSH PVC Insulated FR-LSH PVC Insulated FR-LSH PVC Insulated


2 Type of cable
Unsheathed cable Unsheathed cable Unsheathed cable

IS 694/2010 With upto IS 694/2010 With upto IS 694/2010 With upto


3 Reference design Standards
date amendment date amendment date amendment

4 Conductor size mm2 2.5 4 6


5 Rated Voltage Volts 1100 1100 1100
6 No of Core Nos 1 1 1
7 Conductor

Annealed Plain Copper Annealed Plain Copper Annealed Plain Copper


a Material
Conductor Conductor Conductor

b Reference Standards IS 8130/2013 Class -5 IS 8130/2013 Class -5 IS 8130/2013 Class -5

c Shape of conductor Bunched Circular Bunched Circular Bunched Circular


Conductor d.c.Resistance Corrected to
d Ohm/Km 7.98 4.95 3.30
20°C

e AC Resistance at 85°C for Information only Ohm/Km 9.576 5.94 3.96

Cuurent Rating in normal operation


f Ampere 22 29 37
condition
8 Insulation
a Reference Standards IS 5831/1984 IS 5831/1984 IS 5831/1984

PVC Type-D With FR-LSH PVC Type-D With FR-LSH PVC Type-D With FR-
b Material composition
properties properties LSH properties

c Thickness (Nominal) as per IS mm 0.7 0.8 0.8


Red , Yellow , Blue , Black Red , Yellow , Blue & As per customer
d Core identification
& Green Green requirment
The insulation will withstand conductor
e oC 70oC 70oC 70oC
operating temp.
9 Overall dimeter of cable (Maximum) mm 4.1 4.8 5.3

10 Test for FR-LSH Properties :-


Oxygen Index @ ambient temp. as per
a % Not Less than 29 Not Less than 29 Not Less than 29
ASTM-2863

Temperature Index as per ASTMD-2863 by


b °C Not Less Than 250 Not Less Than 250 Not Less Than 250
graph plotation method

Smoke density rating As per Shall not be more than Shall not be more than Shall not be more than
c %
ASTM-2843 60% 60% 60%

Shall not be more than Shall not be more than Shall not be more than
d Acid gas generation As per IEC 754-I %
20% by weight 20% by weight 20% by weight
Customer :
DATA SHEET FOR FR-LSH WIRES AS PER IS 694
( 2.5 Sq.mm to 4 Sq.mm )
Sr 1C x 2.5 1C x 4 1C x 6
Description Unit
No. SQMM SQMM SQMM
1 Description Y FR-LSH Y FR-LSH Y FR-LSH
11 PACKING:
a Material Rolls Rolls Rolls
Length of cable per roll Sizes 25 sq.mm
b and above may be supplied in drums of Meter 90/100/180 Meter in Rolls 90/100/180 Meter in Rolls 100 Meter in Rolls
1000 Meter ± 5%

c Order qty tolarance ± 2 Rolls or ± 5% ± 2 Rolls or ± 5% ± 2 Rolls or ± 5%

12 Marking on Cable

RALLISON 1100 V S/C X RALLISON 1100 V S/C X 4 RALLISON 1100 V S/C X


2.5 SQMM Y FR-LSH SQMM Y FR-LSH IS:694 6 SQMM Y FR-LSH
a By Printing
IS:694 ISI LOGO CM/L- ISI LOGO CM/L- IS:694 ISI LOGO CM/L-
0003195763 BATCH NO 0003195763 BATCH NO 0003195763 BATCH NO

Note: 5 % of Ordered quantity may be supplied in Assorted Non-Standard length but shall not be less
Note: In case of any dispute/typographical error interpretation of the IS specification shall prevail.

You might also like