CALCUL DES STRUCTURES ACIER

----------------------------------------------------------------------------------------------------------------------------------------
NORME: NF EN 1993-1:2005/NA:2007/AC:2009, Eurocode 3: Design of steel structures.
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------------------
FAMILLE:
PIECE: 200 Arbalétrier_CM66_200 POINT: 1 COORDONNEE: x = 0.00 L = 0.00
m
----------------------------------------------------------------------------------------------------------------------------------------
CHARGEMENTS:
Cas de charge décisif: 25 G+Q+1.25Ex (1+2+3)*1.00+5*1.25
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
S 275 ( S 275 ) fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE LA SECTION: 2 UPN 200


h=20.0 cm gM0=1.10 gM1=1.10
b=16.0 cm Ay=34.50 cm2 Az=34.00 cm2 Ax=64.40 cm2
tw=0.9 cm Iy=3820.00 cm4 Iz=701.73 cm4 Ix=23.80 cm4
tf=1.1 cm Wply=456.00 cm3 Wplz=161.64 cm3
----------------------------------------------------------------------------------------------------------------------------------------
EFFORTS INTERNES ET RESISTANCES ULTIMES:
N,Ed = 50.80 kN My,Ed = -0.92 kN*m Mz,Ed = 0.84 kN*m Vy,Ed = 0.21 kN
Nc,Rd = 1610.00 kN My,Ed,max = -0.92 kN*m Mz,Ed,max = 0.84 kN*m Tau,y,max,Ed = 0.06 MPa
Nb,Rd = 334.97 kN My,c,Rd = 114.00 kN*m Mz,c,Rd = 40.41 kN*m Vz,Ed = 1.03 kN
MN,y,Rd = 113.89 kN*m MN,z,Rd = 40.37 kN*m Tau,z,max,Ed = 0.30 MPa
Tt,Ed = -0.00 kN*m
Classe de la section = 1
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:

en y: en z:
Lz = 5.54 m Lam_z = 1.93
Lcr,z = 5.54 m Xz = 0.21
kzy = 0.54 Lamz = 167.77 kzz = 1.09
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
Contrôle de la résistance de la section:
N,Ed/Nc,Rd = 0.03 < 1.00 (6.2.4.(1))
My,Ed/MN,y,Rd = 0.01 < 1.00 (6.2.9.1.(2))
Mz,Ed/MN,z,Rd = 0.02 < 1.00 (6.2.9.1.(2))
(My,Ed/MN,y,Rd)^ 1.00 + (Mz,Ed/MN,z,Rd)^1.00 = 0.03 < 1.00 (6.2.9.1.(6))
Tau,y,max,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6.(4))
Tau,z,max,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6.(4))
Contrôle de la stabilité globale de la barre:
Lambda,z = 167.77 < Lambda,max = 210.00 STABLE
N,Ed/(Xz*N,Rk/gM1) + kzy*My,Ed,max/(XLT*My,Rk/gM1) + kzz*Mz,Ed,max/(Mz,Rk/gM1) = 0.18 < 1.00
(6.3.3.(4))
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
CALCUL DES STRUCTURES ACIER
----------------------------------------------------------------------------------------------------------------------------------------
NORME: NF EN 1993-1:2005/NA:2007/AC:2009, Eurocode 3: Design of steel structures.
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------------------
FAMILLE:
PIECE: 201 Arbalétrier_CM66_201 POINT: 1 COORDONNEE: x = 0.00 L = 0.00
m
----------------------------------------------------------------------------------------------------------------------------------------
CHARGEMENTS:
Cas de charge décisif: 25 G+Q+1.25Ex (1+2+3)*1.00+5*1.25
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
S 275 ( S 275 ) fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE LA SECTION: 2 UPN 200


h=20.0 cm gM0=1.10 gM1=1.10
b=16.0 cm Ay=34.50 cm2 Az=34.00 cm2 Ax=64.40 cm2
tw=0.9 cm Iy=3820.00 cm4 Iz=701.73 cm4 Ix=23.80 cm4
tf=1.1 cm Wply=456.00 cm3 Wplz=161.64 cm3
----------------------------------------------------------------------------------------------------------------------------------------
EFFORTS INTERNES ET RESISTANCES ULTIMES:
N,Ed = 44.89 kN My,Ed = -1.29 kN*m Mz,Ed = -1.00 kN*m Vy,Ed = -0.47 kN
Nc,Rd = 1610.00 kN My,Ed,max = -1.29 kN*m Mz,Ed,max = 1.62 kN*m Tau,y,max,Ed = -0.14 MPa
Nb,Rd = 334.97 kN My,c,Rd = 114.00 kN*m Mz,c,Rd = 40.41 kN*m Vz,Ed = 1.24 kN
MN,y,Rd = 113.91 kN*m MN,z,Rd = 40.38 kN*m Tau,z,max,Ed = 0.36 MPa
Tt,Ed = 0.01 kN*m
Classe de la section = 1
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:

en y: en z:
Lz = 5.54 m Lam_z = 1.93
Lcr,z = 5.54 m Xz = 0.21
kzy = 0.54 Lamz = 167.77 kzz = 1.07
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
Contrôle de la résistance de la section:
N,Ed/Nc,Rd = 0.03 < 1.00 (6.2.4.(1))
My,Ed/MN,y,Rd = 0.01 < 1.00 (6.2.9.1.(2))
Mz,Ed/MN,z,Rd = 0.02 < 1.00 (6.2.9.1.(2))
(My,Ed/MN,y,Rd)^ 1.00 + (Mz,Ed/MN,z,Rd)^1.00 = 0.04 < 1.00 (6.2.9.1.(6))
Tau,y,max,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6.(4))
Tau,z,max,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6.(4))
Contrôle de la stabilité globale de la barre:
Lambda,z = 167.77 < Lambda,max = 210.00 STABLE
N,Ed/(Xz*N,Rk/gM1) + kzy*My,Ed,max/(XLT*My,Rk/gM1) + kzz*Mz,Ed,max/(Mz,Rk/gM1) = 0.18 < 1.00
(6.3.3.(4))
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!

CALCUL DES STRUCTURES ACIER


----------------------------------------------------------------------------------------------------------------------------------------
NORME: NF EN 1993-1:2005/NA:2007/AC:2009, Eurocode 3: Design of steel structures.
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------------------
FAMILLE:
PIECE: 202 contrev vertical_202 POINT: 3 COORDONNEE: x = 1.00 L = 4.80
m
----------------------------------------------------------------------------------------------------------------------------------------
CHARGEMENTS:
Cas de charge décisif: 26 G+Q-1.25Ex (1+2+3)*1.00+5*-1.25
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
S 275 ( S 275 ) fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE LA SECTION: 2 UPN 200


h=20.0 cm gM0=1.10 gM1=1.10
b=16.0 cm Ay=34.50 cm2 Az=34.00 cm2 Ax=64.40 cm2
tw=0.9 cm Iy=3820.00 cm4 Iz=701.73 cm4 Ix=23.80 cm4
tf=1.1 cm Wply=456.00 cm3 Wplz=161.64 cm3
----------------------------------------------------------------------------------------------------------------------------------------
EFFORTS INTERNES ET RESISTANCES ULTIMES:
N,Ed = -2.88 kN My,Ed = 0.58 kN*m Mz,Ed = 9.12 kN*m Vy,Ed = -3.57 kN
Nt,Rd = 1610.00 kN My,pl,Rd = 114.00 kN*m Mz,pl,Rd = 40.41 kN*m Tau,y,max,Ed = -1.04 MPa
My,c,Rd = 114.00 kN*m Mz,c,Rd = 40.41 kN*m Vz,Ed = -0.22 kN
MN,y,Rd = 114.00 kN*m MN,z,Rd = 40.41 kN*m Tau,z,max,Ed = -0.07 MPa
Tt,Ed = 0.00 kN*m
Classe de la section = 1
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:

en y: en z:

----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
Contrôle de la résistance de la section:
N,Ed/Nt,Rd = 0.00 < 1.00 (6.2.3.(1))
My,Ed/MN,y,Rd = 0.01 < 1.00 (6.2.9.1.(2))
Mz,Ed/MN,z,Rd = 0.23 < 1.00 (6.2.9.1.(2))
(My,Ed/MN,y,Rd)^ 1.00 + (Mz,Ed/MN,z,Rd)^1.00 = 0.23 < 1.00 (6.2.9.1.(6))
Tau,y,max,Ed/(fy/(sqrt(3)*gM0)) = 0.01 < 1.00 (6.2.6.(4))
Tau,z,max,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6.(4))
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!

CALCUL DES STRUCTURES ACIER


----------------------------------------------------------------------------------------------------------------------------------------
NORME: NF EN 1993-1:2005/NA:2007/AC:2009, Eurocode 3: Design of steel structures.
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------------------
FAMILLE:
PIECE: 203 POINT: 3 COORDONNEE: x = 1.00 L = 4.80
m
----------------------------------------------------------------------------------------------------------------------------------------
CHARGEMENTS:
Cas de charge décisif: 26 G+Q-1.25Ex (1+2+3)*1.00+5*-1.25
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
S 275 ( S 275 ) fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE LA SECTION: 2 UPN 200


h=20.0 cm gM0=1.10 gM1=1.10
b=16.0 cm Ay=34.50 cm2 Az=34.00 cm2 Ax=64.40 cm2
tw=0.9 cm Iy=3820.00 cm4 Iz=701.73 cm4 Ix=23.80 cm4
tf=1.1 cm Wply=456.00 cm3 Wplz=161.64 cm3
----------------------------------------------------------------------------------------------------------------------------------------
EFFORTS INTERNES ET RESISTANCES ULTIMES:
N,Ed = 74.83 kN My,Ed = -0.99 kN*m Mz,Ed = -6.44 kN*m Vy,Ed = 2.73 kN
Nc,Rd = 1610.00 kN My,pl,Rd = 114.00 kN*m Mz,pl,Rd = 40.41 kN*m Tau,y,max,Ed = 0.79 MPa
Nb,Rd = 1610.00 kN My,c,Rd = 114.00 kN*m Mz,c,Rd = 40.41 kN*m Vz,Ed = -0.85 kN
MN,y,Rd = 113.75 kN*m MN,z,Rd = 40.32 kN*m Tau,z,max,Ed = -0.25 MPa
Tt,Ed = 0.01 kN*m
Classe de la section = 1
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:

en y: en z:

----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
Contrôle de la résistance de la section:
N,Ed/Nc,Rd = 0.05 < 1.00 (6.2.4.(1))
My,Ed/MN,y,Rd = 0.01 < 1.00 (6.2.9.1.(2))
Mz,Ed/MN,z,Rd = 0.16 < 1.00 (6.2.9.1.(2))
(My,Ed/MN,y,Rd)^ 1.00 + (Mz,Ed/MN,z,Rd)^1.00 = 0.17 < 1.00 (6.2.9.1.(6))
Tau,y,max,Ed/(fy/(sqrt(3)*gM0)) = 0.01 < 1.00 (6.2.6.(4))
Tau,z,max,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6.(4))
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!

CALCUL DES STRUCTURES ACIER


----------------------------------------------------------------------------------------------------------------------------------------
NORME: NF EN 1993-1:2005/NA:2007/AC:2009, Eurocode 3: Design of steel structures.
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------------------
FAMILLE:
PIECE: 204 contrev vertical_204 POINT: 1 COORDONNEE: x = 0.00 L = 0.00
m
----------------------------------------------------------------------------------------------------------------------------------------
CHARGEMENTS:
Cas de charge décisif: 25 G+Q+1.25Ex (1+2+3)*1.00+5*1.25
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
S 275 ( S 275 ) fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE LA SECTION: 2 UPN 200


h=20.0 cm gM0=1.10 gM1=1.10
b=16.0 cm Ay=34.50 cm2 Az=34.00 cm2 Ax=64.40 cm2
tw=0.9 cm Iy=3820.00 cm4 Iz=701.73 cm4 Ix=23.80 cm4
tf=1.1 cm Wply=456.00 cm3 Wplz=161.64 cm3
----------------------------------------------------------------------------------------------------------------------------------------
EFFORTS INTERNES ET RESISTANCES ULTIMES:
N,Ed = -20.27 kN My,Ed = -1.49 kN*m Mz,Ed = 6.43 kN*m Vy,Ed = 2.57 kN
Nt,Rd = 1610.00 kN My,pl,Rd = 114.00 kN*m Mz,pl,Rd = 40.41 kN*m Tau,y,max,Ed = 0.75 MPa
My,c,Rd = 114.00 kN*m Mz,c,Rd = 40.41 kN*m Vz,Ed = 1.01 kN
MN,y,Rd = 113.98 kN*m MN,z,Rd = 40.40 kN*m Tau,z,max,Ed = 0.30 MPa
Tt,Ed = 0.01 kN*m
Classe de la section = 1
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:

en y: en z:

----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
Contrôle de la résistance de la section:
N,Ed/Nt,Rd = 0.01 < 1.00 (6.2.3.(1))
My,Ed/MN,y,Rd = 0.01 < 1.00 (6.2.9.1.(2))
Mz,Ed/MN,z,Rd = 0.16 < 1.00 (6.2.9.1.(2))
(My,Ed/MN,y,Rd)^ 1.00 + (Mz,Ed/MN,z,Rd)^1.00 = 0.17 < 1.00 (6.2.9.1.(6))
Tau,y,max,Ed/(fy/(sqrt(3)*gM0)) = 0.01 < 1.00 (6.2.6.(4))
Tau,z,max,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6.(4))
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!

CALCUL DES STRUCTURES ACIER


----------------------------------------------------------------------------------------------------------------------------------------
NORME: NF EN 1993-1:2005/NA:2007/AC:2009, Eurocode 3: Design of steel structures.
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------------------
FAMILLE:
PIECE: 205 contrev vertical_205 POINT: 3 COORDONNEE: x = 1.00 L = 4.80
m
----------------------------------------------------------------------------------------------------------------------------------------
CHARGEMENTS:
Cas de charge décisif: 25 G+Q+1.25Ex (1+2+3)*1.00+5*1.25
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
S 275 ( S 275 ) fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE LA SECTION: 2 UPN 200


h=20.0 cm gM0=1.10 gM1=1.10
b=16.0 cm Ay=34.50 cm2 Az=34.00 cm2 Ax=64.40 cm2
tw=0.9 cm Iy=3820.00 cm4 Iz=701.73 cm4 Ix=23.80 cm4
tf=1.1 cm Wply=456.00 cm3 Wplz=161.64 cm3
----------------------------------------------------------------------------------------------------------------------------------------
EFFORTS INTERNES ET RESISTANCES ULTIMES:
N,Ed = 97.37 kN My,Ed = -0.61 kN*m Mz,Ed = 9.61 kN*m Vy,Ed = -3.72 kN
Nc,Rd = 1610.00 kN My,pl,Rd = 114.00 kN*m Mz,pl,Rd = 40.41 kN*m Tau,y,max,Ed = -1.08 MPa
Nb,Rd = 1610.00 kN My,c,Rd = 114.00 kN*m Mz,c,Rd = 40.41 kN*m Vz,Ed = -0.78 kN
MN,y,Rd = 113.58 kN*m MN,z,Rd = 40.26 kN*m Tau,z,max,Ed = -0.23 MPa
Tt,Ed = 0.00 kN*m
Classe de la section = 1
----------------------------------------------------------------------------------------------------------------------------------------

PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:

en y: en z:

----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
Contrôle de la résistance de la section:
N,Ed/Nc,Rd = 0.06 < 1.00 (6.2.4.(1))
My,Ed/MN,y,Rd = 0.01 < 1.00 (6.2.9.1.(2))
Mz,Ed/MN,z,Rd = 0.24 < 1.00 (6.2.9.1.(2))
(My,Ed/MN,y,Rd)^ 1.00 + (Mz,Ed/MN,z,Rd)^1.00 = 0.24 < 1.00 (6.2.9.1.(6))
Tau,y,max,Ed/(fy/(sqrt(3)*gM0)) = 0.01 < 1.00 (6.2.6.(4))
Tau,z,max,Ed/(fy/(sqrt(3)*gM0)) = 0.00 < 1.00 (6.2.6.(4))
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!