Professional Documents
Culture Documents
Impedancia Transformadores Trifasicos 3
Impedancia Transformadores Trifasicos 3
Table 1—Impedance Data for Three-Phase Transformers With Primaries of Up to 15 000 V and
Secondaries of 600 V or Less
Suggested X/R
kVA Ratio for Normal Range of Percent
Θ
3Θ Calculation Impedance (see notes)
NOTES:
1 — Underlined values are from ANSI C57.12.10-1977 [1], ANSI C57.12.22-1980 [2], and NEMA
210-1976 [10].
2 — Network transformers (with three-position swithches) have 5.0%Z for 300–1000 kVA, 7.0% Z
for 1500–2500 kVA, (with two-position switches) 4.0% Z for 500–750 kVA. See ANSI C57.12-
40-1982 [3].
3 — Three-phase banks with three single-phase transformers may have values as low as 1.2%.
Table 2—Data for Three-Phase Transformers With Secondaries of 2400 V or More (750–60 000 kVA)
Primary Primary Standard Percent Impedance
kV kV BIL (see notes)
NOTES:
1 — Actual values are generally within ± 7.5% of the standard values [1].
2 — Add 0.5% for load tap changing [8].
3 — Lower values are usually for OA 55 °C or OA 55/65 °C rise transformers.
4 — Higher values are usually for OA 65 °C rise transformers.
5 — X/R values are similar to those in Table 1. Consult manufacturer or use the values in [4] for
transformers rated over 2500 kVA.