System Description
DCS 600 CraneDrive
II F 1-i
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
How the DCS 600 CraneDrive Documentation
Volume II F Volume II F1
System works
System Description System Description
DCS 600 Crane DCA 600 Enclosed
3ADW000072 3ADW000121
This is to give you an overview how the system of
information for DCS 600 CraneDrive converters is
built up. The shaded part indicates the volume within
the total system you are just now working with. In
Volume III addition you see all other available documents for the
Technical Data same system.
3ADW000165
Volume V F2 Volume VI F1
CraneDrive Installation Man.
Firmware
DCS(F)manual
600 DCA 600 ... List of contents
3ADW000080
DCS 600 3ADW000091
3AST000953R0125
II F SYSTEM DESCRIPTION
1 DCS 600 CraneDrive ................................... II F 1-1
II F 1-ii
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
1 DCS 600 CraneDrive - the power converter
❖ state-of-the-art technology
❖ flexible design
❖ user-friendly
They also comply with the relevant EMC standards for Moreover, the accessories listed below can be used
Australia and New Zealand and are C-Tick marked. to individually customize the drive package in ac-
cordance with the application intended
DCS 600 CraneDrive converter units are suitable for ❋ External field supply units
standard and system drive applications. ❋ Additional I/O boards (isolated)
❋ Interface modules for various communication pro-
Appropriate PC programs ensure that the drives are tocols
engineered for user-friendly operator control. ❋ EMC filter
❋ PC programs
II F 1-1
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Basic functions Design and commissioning tools
All units are provided with the same digital control DriveWindow
boards and software. The DCS 600 CraneDrive flexi- PC program for commissioning and maintenance un-
bility allows the user to configure functions of the drive der Windows® for:
easily, suitable for different applications. Functions of Parameter setting
the DCS 600 CraneDrive are normally activated by Fault detection
parameters. Trending
Data logger
The basic software includes the following options: Fault logger
• Processing the speed reference with a speed ramp Local operation (Drives Panel)
generator (S-ramp capability, accel/decel ramp)
• Processing the speed feedback CDP 312 removable control and display panel with
• Speed controller plain text display for:
• Torque reference processing Drive control signal
• Current controller Parameter setting
• Field weakening Fault detection
• Automatic/manual field reversal Parameter uploading and downloading
• Autotuning of current controller Local operation
• Speed monitor
• Drive control logic
• Remote/local operation Monitoring functions
• Electrical disconnect (category 0) Self-test
• Electronic circuits are not sensitive to line phase Fault logger
sequence Motor protection
• Electrical and mechanical brake control In the event of:
• Motor overload supervision • Speed feedback error
• Dual field • Overtemperature
• Programmable analogue outputs • Overload
• Field supply • Overspeed
• Master follower via fibre optics • Zero speed
• Armature overcurrent
Controlling and operating • Armature ripple
via I/O's • Armature overvoltage
analogue and digital inputs and outputs • Minimum field current
• Field overcurrent
via bus systems Power converter protection
e.g.: Profibus, Modbus Plus, AF100 etc. • Overtemperature
• Software errors (watchdog function)
via HMI (Human Machine Interface) Incorrect supply protection
Outputs: • Mains overvoltage and undervoltage
Alarms • Auxiliary undervoltage
Faults • Incorrect mains phase sequence (only inform.)
Status information
Parameter setting
Local control of the drive
II F 1-2
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
The cost effective crane
drive with safety and per-
formance already built in.
CraneDrive functions
• Mechanical brake control
• Fast stop
• Torque proving
• Speed monitor
• Torque monitor
• Joystick interface
• Limit switch supervision
II F 1-3
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
II F 1-4
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
≤ 1000V
2
EMC filter
Fig. 2/1:
Earth-fault monitor
≤ 690V
PC + F2 Q1 F3
MultiDrive
DriveWindow socket F1
T2 T3
NDPI
-NDPA-02 Panel Monitoring
(PCMCIA) K3
-NDPC-12 K1 Power
CDP 312 LED bar
-NISA-03 (ISA)
Rev D or later NLM D supply
X3 K5
L1
NDBU95 L3
X3
X2
12-Pulse link T90
U1 V1 U1 V1 W1
DCS 6..-....-.1-15..... (.... -.1-18.....)
AMC-DC X99
CH3 POW 1 U1 V1 W1 X1 X1
DCS 600 Armature converter
CON 2
X33 X37 X37
V260
CH0
FEX 1 FEX 2
DSP X12 X12
to other drives
PIN 1x
CH2 X10 X11
X13 X13
based on the DCS 600 power converter modules. This
control DC motors. It consists of individual components,
system of components and complete standard cabinets to
The DCS 600 CraneDrive power converter range is a
X12 M
PIN 20xB X14 X14
X2
µP X13
X16
DCF 503A
DCF 601 / 602
Three-phase field supply
X12 PIN 41
PIN 51
X16 X1 X2 X17 X16 X14 *
(24V) X13 PIN 41 C1 D1 X1 X1
/ 504A
C1 D1
A92 C1 D1
7 8
* connection see Technical data
with the system; its main components are shown in the diagram above.
This overview has been designed to help you to familiarize yourself
X4,5 X6 X4 X3 X3 X5 X2 X1 Legend
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
3 5 2
CON x - short designation of components
8 8 7
to the PLC digital input / output analogue input / output
T
DCS 600 CraneDrive Components Overview
II F 2-1
chapter provides a brief description of the DCS 600
CraneDrive components available for matching the drive
DCF 600 Field supply converter
The DCF 600 field supply converter range is a system of the modified power interface board SDCS-PIN-1x (if
components and complete standard cabinets to control used) and the reduced range of current and voltage types
the field supply of DC motors. It consists of individual (see table 2.2/2). The function for field supply will be
components, based on the DCS 600 power converter selected by software parameters.
modules. The difference to the armature converter is only Note: Armature and field converters use the same firmware.
dcf6_sys_h.dsf
analogue input / output
X4
DCF 506
X11
X12
M
DCS 600
optical fibre
X16
Legend
digital input / output
alternative
M
Earth-fault monitor
7.1
K5
EMC filter
U1 V1 W1
C1 D1
K3
L1
Q1
F1
≤ 600V
X17
IOE 1
7
X2 X1
ied
2
di f
PIN 20xB
mo
PIN 1x
POW 1
X99
IOB 3
X2
F2
X37
X12
X13
X12
X13
T2
≤ 690V
X1
5
X4 X3
DCF 6..-....-.1-15.....
3
Monitoring
CZD-0x
X37
LED bar
X14
X3
X12
X13
X3
NLMD
X1
8
X4,5 X6
IOB 2x
V260
8
X16
CON 2
µP
X3
X17
Rev D or later
MultiDrive
CDP 312
socket
Follower
NDPI
Panel
- Master/
X1 X2
X33
X11
X2
to the PLC
Field Bus
(24V)
Adapter
X16
Module
Nxxx
X10
(PCMCIA)
DriveWindow
AMC-DC
DSP
-NISA-03 (ISA)
PC +
8
4
CH3
CH2
CH0
-NDPA-02
-NDPC-12
-Advant
control
7
3
PLC
NDBU95
to other drives
Fig. 2/2: DCS 600 CraneDrive Components overview for field supply converters
II F 2-2
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
2.1 Environmental Conditions
90
100
80
90
70
80
60
50 70
1000 2000 3000 4000 5000 m 30 35 40 45 50 55°C
Fig. 2.1/1: Effect of the site elevation above sea level Fig. 2.1/2: Effect of the ambient temperature on the
on the converter’s load capacity. converter module load capacity.
Regulatory Compliance North American Standards
The converter module and enclosed converter components are designed for use In North America the system components fulfil
in industrial environments. In EEA countries, the components fulfil the require- the requirements of the table below.
ments of the EU directives, see table below.
Harmonized Standards Rated Standards
European Union Directive Manufacturer's Assurance supply Converter module Enclosed converter
Conver ter module Enclosed conver ter
voltage
Machinery Directive
Declaration of EN 60204-1 EN 60204-1 to 600 V UL 508 C UL/CSA types: on request
98/37/EEC Power Conversion
Incor poration [IEC 60204-1] [IEC 60204-1]
93/68/EEC Equipment
EN 60146-1-1 EN 60204-1 CSA C 22.2 No. 14-95
Low Voltage Directive [IEC 60146-1-1] [IEC 60204-1] Industrial Control
73/23/EEC Declaration of Conformity EN 50178 [IEC --] EN 60439-1 Equipment,
93/68/EEC see additional [IEC 60439-1] Industrial Products
IEC 60664 Available for converter
Declaration of Conformity modules including field
EN 61800-3 ➀ EN 61800-3 ➀ exciter units.
(Provided that all [IEC 61800-3] [IEC 61800-3]
EMC Directive installation instructions Types with UL mark:
89/336/EEC concerning cable • see UL Listing
93/68/EEC ➀ in accordance
selection, cabling and ➀ in accordance with www.ul.com /
with 3ADW 000 032/ certificate no.
EMC filters or dedicated 3ADW 000 032
3ADW 000 091 E196914
transformer are followed.)
• or on request
> 600 V EN / IEC xxxxx see EN / IEC types: on request
to table on the left (for details see table on the
1000 V Available for converter left)
modules
including field exciter
units.
II F 2-3
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
2.2 DCS 600 Power Converter Modules
The power converter modules are modular in construc- volved, e.g. a field supply for the motor, or an interface
tion. They are based on the housing, which contains board to connect the converter to an overriding control
the power section with the RC snubber circuit. There system. A control/display panel is available for the
are 4 different sizes, depending on current and voltage. operator. It can be mounted to the power converter
All units are forced cooled. module or installed in the cabinet's door by means of a
mounting kit.
The power section is controlled by the unit’s electronic
system, which is identical for the entire product range. Accessories such as external fuses, line reactors and the
Parts of the unit’s electronic system can be installed in like are available, for putting together a complete drive
the unit, depending on the particular application in- system.
II F 2-4
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Converter type y→ y=4 (400 V) y=5 (500 V) y=6 (600 V) y=7 (690 V)
x=1 → 2-Q IDC [A] IAC [A] P [kW] P [kW] P [kW] P [kW]
x=2 → 4-Q 4Q 2Q 4Q 2Q 4Q 2Q 4Q 2Q 4Q 2Q 4Q 2Q
DCS60x-0025-y1 25 25 20 20 10 12 13 15
DCS60x-0050-y1 50 50 41 41 21 23 26 29
DCS60x-0050-61 50 50 41 41 31 35
DCS60x-0075-y1 75 75 61 61 31 35 39 44
DCS60x-0100-y1 100 100 82 82 42 47 52 58
DCS60x-0110-61 110 100 90 82 69 70
DCS60x-0140-y1 140 125 114 102 58 58 73 73
DCS60x-0200-y1 200 180 163 147 83 84 104 104
DCS60x-0250-y1 250 225 204 184 104 105 130 131
DCS60x-0270-61 270 245 220 200 169 172
DCS60x-0350-y1 350 315 286 257 145 146 182 183
DCS60x-0450-y1 450 405 367 330 187 188 234 235 281 284
DCS60x-0520-y1 520 470 424 384 216 219 270 273
DCS60x-0680-y1 680 610 555 500 282 284 354 354
DCS60x-0820-y1 820 740 670 605 340 344 426 429
DCS60x-1000-y1 1000 900 820 738 415 418 520 522
DCS60x-0903-y1 900 900 734 734 563 630 648 720
DCS60x-1203-y1 1200 1200 979 979 498 558 624 696
DCS60x-1503-y1 1500 1500 1224 1224 623 698 780 870 938 1050 1080 1200
DCS60x-2003-y1 2000 2000 1632 1632 830 930 1040 1160 1400 1600
DCF60x-0025-y1 25 25 20 20 10 12 13 15
DCF60x-0050-y1 50 50 41 41 21 23 26 29
DCF60x-0075-y1 75 75 61 61 31 35 39 44
DCF60x-0100-y1 100 100 82 82 42 47 52 58
DCF60x-0200-y1 200 180 163 147 83 84 104 104
DCF60x-0350-y1 350 315 286 257 145 146 182 183
DCF60x-0450-y1 450 405 367 330 187 188 234 235
DCF60x-0520-y1 520 470 424 384 216 219 270 273
Table 2.2/2: Table of DCS 600 / DCF 600 units - construction types C1, C2, A5
Converter type y→ y=4 (400 V) y=5 (500 V) y=6 (600 V) y=7 (690 V) y=8 (790 V) y=9 (1000V) y=1 (1190V)
IDC [A] IAC [A] P [kW] P [kW] P [kW] P [kW] P [kW] P [kW] P [kW] ➀
2-Q converters
DCS601-1903-y1 1900 1550 1740
DCS601-2053-y1 2050 1673 1190 1430 1640
DCS601-2503-y1 2500 2040 1160 1450 1750 2000 2300
DCS601-3003-y1 3000 2448 1395 1740 2090 2400 2750
DCS601-2053-y1 2050 1673 2390
DCS601-2603-y1 2600 2121 3030 on request
DCS601-3303-y1 3300 2693 1540 1925 2310 2660 3040 3850 on request
DCS601-4003-y1 4000 3264 1870 2330 2800 3220 3690 4670 on request
DCS601-4803-y1 4800 3917 3360 3860 4420
DCS601-5203-y1 5200 4243 2430 3030
4-Q converters
DCS602-1903-y1 1900 1550 1560
DCS602-2053-y1 2050 1673 1070 1280 1470
DCS602-2503-y1 2500 2040 1040 1300 1560 1800 2060
DCS602-3003-y1 3000 2448 1250 1560 1880 2150 2470
DCS602-2053-y1 2050 1673 2390
DCS602-2603-y1 2600 2121 3030 on request
DCS602-3303-y1 3300 2693 1375 1720 2060 2370 2720 3440 on request
DCS602-4003-y1 4000 3264 1670 2080 2500 2875 3290 4170 on request
DCS602-4803-y1 4800 3917 3000 3450 3950
DCS602-5203-y1 5200 4243 2170 2710
➀ These converters are equipped with additional components. More information on request
Table 2.2/3: Table of DCS 600 units - construction type A6 / A7
II F 2-5
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Construction type C1 Construction type C2 Construction type A5 Construction type A6 Construction type A7
left busbar connection
Converter type ➁ Dimensions Weight Clearances Construct. Power loss Fan Semiconductor
HxWxD top/bottom/side type at 500V connection Fuses
[mm] [kg] [mm] PV [kW]
DCS60x-0025-y1 420x273x195 7.1 150x100x5 C1a < 0.2 230 V/1 ph external
DCS60x-0050-y1 420x273x195 7.2 150x100x5 C1a < 0.2 230 V/1 ph external
DCS60x-0050-61 420x273x195 7.6 150x100x5 C1a - 230 V/1 ph external
DCS60x-0075-y1 420x273x195 7.6 150x100x5 C1a < 0.3 230 V/1 ph external
DCS60x-0100-y1 469x273x228 11.5 250x150x5 C1b < 0.5 230 V/1 ph external
DCS60x-0110-61 469x273x228 11.5 250x150x5 C1b - 230 V/1 ph external
DCS60x-0140-y1 469x273x228 11.5 250x150x5 C1b < 0.6 230 V/1 ph external
DCS60x-0200-y1 505x273x361 22.3 250x150x5 C2a < 0.8 230 V/1 ph external
DCS60x-0250-y1 505x273x361 22.3 250x150x5 C2a < 1.0 230 V/1 ph external
DCS60x-0270-61 505x273x361 22.8 250x150x5 C2a - 230 V/1 ph external
DCS60x-0350-y1 505x273x361 22.8 250x150x5 C2a < 1.3 230 V/1 ph external
DCS60x-0450-y1 505x273x361 28.9 250x150x10 C2a < 1.5 230 V/1 ph external
DCS60x-0520-y1 505x273x361 28.9 250x150x10 C2a < 1.8 230 V/1 ph external
DCS60x-0680-y1 652x273x384 42 250x150x10 C2b < 1.6 230 V/1 ph external
DCS60x-0820-y1 652x273x384 42 250x150x10 C2b < 2.0 230 V/1 ph external
DCS60x-1000-y1 652x273x384 42 250x150x10 C2b < 2.5 230 V/1 ph external
II F 2-6
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
2.3 DCS 600 Overload Capability
To match a drive system’s components as efficiently as possible to the driven
machine’s load profile, the armature power converters DCS 600 can be dimensio-
ned by means of the load cycle. Load cycles for driven machines have been defi-
ned in the IEC 146 or IEEE specifications, for example.
The currents for the DC I to DC IV types of load (see diagram on the following page) for the power converter
modules are listed in the table below.
Unit type IDC I IDC II IDC III IDC IV
contin- 100 % 150 % 100 % 150 % 100 % 200 %
uous 15 min 60 s 15 min 120 s 15 min 10 s
400 V / 500 V [A] [A] [A] [A]
DCS 60x-0025-41/51 25 24 36 23 35 24 48
DCS 60x-0050-41/51 50 44 66 42 63 40 80
DCS 60x-0075-41/51 75 60 90 56 84 56 112
DCS 60x-0100-41/51 100 71 107 69 104 68 136
DCS 601-0140-41/51 125 94 141 91 137 90 180
DCS 602-0140-41/51 140 106 159 101 152 101 202
DCS 601-0200-41/51 180 133 200 132 198 110 220
DCS 602-0200-41/51 200 149 224 146 219 124 248
DCS 601-0250-41/51 225 158 237 155 233 130 260
DCS 602-0250-41/51 250 177 266 173 260 147 294
DCS 601-0350-41/51 315 240 360 233 350 210 420
DCS 602-0350-41/51 350 267 401 258 387 233 466
DCS 601-0450-41/51 405 317 476 306 459 283 566
DCS 602-0450-41/51 450 352 528 340 510 315 630
DCS 601-0520-41/51 470 359 539 347 521 321 642
DCS 602-0520-41/51 520 398 597 385 578 356 712
DCS 601-0680-41/51 610 490 735 482 732 454 908
DCS 602-0680-41/51 680 544 816 538 807 492 984
DCS 601-0820-41/51 740 596 894 578 867 538 1076
DCS 602-0820-41/51 820 664 996 648 972 598 1196
DCS 601-1000-41/51 900 700 1050 670 1005 620 1240
DCS 602-1000-41/51 1000 766 1149 736 1104 675 1350
DCS 60x-1203-41/51 1200 888 1332 872 1308 764 1528
DCS 60x-1503-41/51 1500 1200 1800 1156 1734 1104 2208
DCS 60x-2003-41/51 2000 1479 2219 1421 2132 1361 2722
DCS 60x-2053-51 2050 1550 2325 1480 2220 1450 2900
DCS 601-2503-41/51 2500 1980 2970 1880 2820 1920 3840
DCS 602-2503-41/51 2500 2000 3000 1930 2895 1790 3580
DCS 601-3003-41/51 3000 2350 3525 2220 3330 2280 4560
DCS 602-3003-41/51 3000 2330 3495 2250 3375 2080 4160
DCS 60x-3303-41/51 3300 2416 3624 2300 3450 2277 4554
DCS 60x-4003-41/51 4000 2977 4466 2855 4283 2795 5590
DCS 60x-5203-41/51 5200 3800 5700 3669 5504 3733 7466
600 V / 690 V
DCS 60x-0050-61 50 44 66 43 65 40 80
DCS 601-0110-61 100 79 119 76 114 75 150
DCS 602-0110-61 110 87 130 83 125 82 165
DCS 601-0270-61 245 193 290 187 281 169 338
DCS 602-0270-61 270 213 320 207 311 187 374
DCS 601-0450-61 405 316 474 306 459 282 564
DCS 602-0450-61 450 352 528 340 510 313 626
DCS 60x-0903-61/71 900 684 1026 670 1005 594 1188
DCS 60x-1503-61/71 1500 1200 1800 1104 1656 1104 2208
DCS 601-2003-61/71 2000 1479 2219 1421 2132 1361 2722
DCS 60x-2053-61/71 2050 1520 2280 1450 2175 1430 2860
DCS 601-2503-61/71 2500 1940 2910 1840 2760 1880 3760
DCS 602-2503-61/71 2500 1940 2910 1870 2805 1740 3480
DCS 601-3003-61/71 3000 2530 3795 2410 3615 2430 4860
DCS 602-3003-61/71 3000 2270 3405 2190 3285 2030 4060
DCS 60x-3303-61/71 3300 2416 3624 2300 3450 2277 4554
DCS 60x-4003-61/71 4000 3036 4554 2900 4350 2950 5900
DCV 60x-4803-61/71 4800 3734 5601 3608 5412 3700 7400
790 V
DCS 60x-1903-81 1900 1500 2250 1430 2145 1400 2800
DCS 601-2503-81 2500 1920 2880 1820 2730 1860 3720
DCS 602-2503-81 2500 1910 2865 1850 2775 1710 3420
DCS 601-3003-81 3000 2500 3750 2400 3600 2400 4800
DCS 602-3003-81 3000 2250 3375 2160 3240 2000 4000
DCS 60x-3303-81 3300 2655 3983 2540 3810 2485 4970
DCS 60x-4003-81 4000 3036 4554 2889 4334 2933 5866
DCS 60x-4803-81 4800 3734 5601 3608 5412 3673 7346 Table 2.3/1:
1000 V Power converter module
DCS 60x-2053-91 2050 1577 2366 1500 2250 1471 2942 currents with corresponding
DCS 60x-2603-91 2600 2000 3000 1900 2850 1922 3844 load cycles.
DCS 60x-3303-91 3300 2551 3827 2428 3642 2458 4916 The characteristics are
DCS 60x-4003-91 4000 2975 4463 2878 4317 2918 5836 based on an ambient tem-
1190 V Data on request perature of max. 40°C and
x=1 → 2-Q; x=2 → 4-Q an elevation of max. 1000 m
a.s.l.
II F 2-7
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Types of load
15 min
DC II IDC II for 15 min and extruders, conveyor belts
1,5 * IDC II for 60 s 150% 100%
DC III * IDC III for 15 min and extruders, conveyor belts 15 min
1,5 * IDC III for 120 s
150% 100%
* Load cycle is not identical with menu item Duty cycle in DCSize !
Table 2.3/2: Definition of the load cycles
II F 2-8
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
2.4 Field Supply
General data
• Currents from 6 to 520 A. All field power converters (except for the SDCS-FEX-
• Minimum field current monitor. 1) are controlled by the armature converter via a serial
• Integrated or external field power converter or in a link with a speed of 62.5 kBaud. The link serves to
completely separate cabinet. parameterize, control and diagnose the field power
• 2-phase or 3-phase model. converter and thus provides an exact control. Moreo-
• Fully digital control (except SDCS-FEX-1). ver, it enables you to control an internal (SDCS-FEX-
2A) and an external (DCF 601/602/503A/504A) or
We recommend integrating an autotransformer in the
two external field supply units (2 x DCF 601/602/
field power converter's supply to adjust the AC input
503A/504A). The respective software function required
voltage to the field voltage, to reduce the voltage and
is available in every DC power converter.
current ripple of the field.
SDCS-FEX-1 SDCS-FEX-2A
• Diode bridge. • Half controlled thyristor/diode bridge (1-Q)
• 6 A rated current. • Microprocessor control, with the electronic system
• Internal non adjustable minimum field current being supplied by the armature converter.
monitor. • Construction and components have been designed
• Construction and components have been designed for an insulation voltage of 600 V AC.
for an insulation voltage of 600 V AC. • Fast-response excitation is possible with an appro-
• Output voltage UA: priate voltage reserve; de-excitation takes place by
field time constant.
100% + TOL
U A = UV * * 0.9 • Output voltage UA:
100%
100% + TOL
TOL = tolerance of line voltage in % U A = UV * * 0.9
UV = Line voltage 100%
TOL = tolerance of line voltage in %
• Recommendation:
UV = Line voltage
Field voltage ~ 0.9 * UV
• Recommendation:
Field voltage 0.6 to 0.8 * UV
SDCS-FEX-1
SDCS-FEX-2A
II F 2-9
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
DCF 503A DCF 600
• Half controlled thyristor/diode bridge (1-Q). This field power converter is used mainly for armature
• Microprocessor control with the control electronics converters with rated currents of 2050 to 5200 A. It is
being supplied separately (115...230 V/1-ph). a modified armature circuit converter.
• Construction and components have been designed • Output voltage UA respectively Udmax 2-Q :
for an insulation voltage of 690 V AC. see table 2.2/1.
• Output voltage UA: • Recommendation:
Field voltage 0.5 to 1.1 * UV
100% + TOL
U A = UV * * 0.9 • The three-phase field supply converters DCF 600
100% needs a separate active overvoltage protection unit
TOL = tolerance of line voltage in % DCF 506 for protecting the power part against too
UV = Line voltage
high voltages.
• Recommendation: The overvoltage protection unit DCF 506 is suita-
Field voltage 0.6 to 0.8 * UV ble for 2-Q converters DCF 601 and for 4-Q
converters DCF 602.
DCF 504A
Assignment Field supply converter to Overvol-
• Fully controlled antiparallel thyristor bridges (4-Q).
• With this unit fast response excitation / de-excita- tage protection unit
tion and field reversal is possible. For fast response
excitation an appropriate voltage reserve is neces- Field supply converter Overvoltage Protection
sary. for motor fields
In steady-state condition, the fully controlled bridge
DCF60x-0025-51
runs in half controlled mode to keep the voltage ... DCF506-0140-51
ripple as low as possible. With a fast changing field DCF60x-0140-51
current, the bridge runs in fully controlled mode.
• Same design as DCF 503A DCF60x-0200-51
... DCF506-0520-51
DCF60x-0520-51
➀ Current reduction see also 2.1 Environmental conditions Fig.: 2.1/1 and 2.1/2
Table 2.4/1: Data field converter units
II F 2-10
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
2.5 Options for DCS 600 CraneDrive converter modules
In-/output signals
The converter can be connected in 4 different ways to addition to this an extension of I/O´s by SDCS-IOE 1
a control unit via analogue/digital links. Only one of is possible.
the four choices can be used at the same time. In
SDCS-CON-2 SDCS-CON-2
X17: X17:
1 2 1 X3: X1:
SDCS-IOB-2
Fig. 2.5/1: I/O´s via SDCS-CON-2 Fig. 2.5/2: I/O´s via SDCS-CON-2 and SDCS-IOB-2
Analogue I/O´s: standard Analogue I/O´s: standard
Digital I/O´s: not isolated digital I/O´s: all isolated by means of opto-
Encoder input: not isolated coupler/relay; the signal status
is indicated by LED
SDCS-CON-2 SDCS-CON-2
X17: X17:
X6: X7:
3 3 4
Fig. 2.5/3: I/O´s via SDCS-CON-2 and SDCS-IOB-3 Fig. 2.5/4: I/O´s via SDCS-IOB-2 and SDCS-IOB-3
Analogue I/O´s: more input capacity Analogue I/O´s: more input capacity
digital I/O´s: not isolated digital I/O´s: all isolated by means of opto-
encoder input: isolated coupler/relay; the signal status
current source for: PT100/PTC element is indicated by LED
current source for: PT100/PTC element
II F 2-11
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Description of I/O signals SDCS-CON-2 Description of I/O signals SDCS-IOB-2x & SDCS-IOB-3
Mechanical system integrated in control board Mechanical system always external, outside the module
Terminals Terminals
Screw type terminals for finely stranded wires up to 2.5 mm2 Screw type terminals for finely stranded wires up to 2.5 mm2
Functionality Functionality of SDCS-IOB-3
1 tacho input 1 tacho input
Resolution: 12 bit + sign; differential input; common mode range ±20 V Resolution: 12 bit + sign; differential input; common mode range ±20 V
3 ranges from 8...30...90...270 VDC with nmax Range 8 V- with nmax; if higher tacho voltages are in use tacho adaptation
board PS 5311 is needed.
4 analogue inputs 4 analogue inputs
Range -10...0...+10 V, 4...20 mA, 0...20 mA All as differential inputs; time constant of smoothing capacitor ≤2 ms
All as differential inputs; RE = 200 kΩ; time constant of smoothing Input 1: Range -10 V...0...+10 V; -20 mA...0...+20 mA; 4... 20 mA
capacitor ≤2 ms unipolar; RE = 200 kΩ/ 500Ω/ 500Ω; Resolution: 12 bit + sign; common
Input 1: Resolution: 12 bit + sign; common mode range ±20 V mode range ±20 V
Inputs 2, 3, 4: Resolution: 11 bit + sign; common mode range ±40 V Inputs 2+3: Range see input 1, in addition -1 V...0...+1 V
Current source for PTC element evaluation via jumper and input 2 RE = 200 kΩ/ 500Ω/ 500Ω/ 20kΩ; Resolution: 11 bit + sign; common
mode range with -1 V...0...+1 V range ±10 V, otherwise ±40 V
Input 4: Range see input 1
RE = 200 kΩ/ 500Ω/ 500Ω; Resolution: 11 bit + sign; common mode
range ±40 V
Residual current detection in combination with analogue input 4
(sum of phase currents ≠ 0)
2 outputs 2 outputs
+10 V, -10 V, IA ≤ 5 mA; sustained short-circuit-proof +10 V, -10 V; IA ≤ 5 mA; sustained short-circuit-proof
voltage supply for reference potentiometer voltage supply for reference potentiometer
1 analogue output 1 analogue output
bipolar current actual - from power section; decoupled Bipolar current actual - from power section; decoupled
IdN = ±3 V; IA≤ 5 mA, short-circuit-proof IdN = ±3 V (at gain = 1); IA≤ 5 mA; UAmax = 10 V; gain can be adjusted by
means of a potentiometer between 0.5 and 5; short-circuit-proof
2 analogue outputs 2 analogue outputs
Range -10...0...+10 V; IA ≤ 5 mA Range -10...0...+10 V; IA ≤ 5 mA; short-circuit-proof
Output signal and scaling can be selected by means of software Output signal and scaling can be selected by means of software
Resolution: 11 bit + sign Resolution: 11 bit + sign
Current source for PT 100 or PTC element
IA = 5 mA / 1.5 mA
1 pulse generator input 1 pulse generator input
Voltage supply for 5 V/12 V/24 V pulse generators (sustained short- Voltage supply, output current, input range: see SDCS-CON-2
circuit-proof) Inputs electrically isolated from 0 V (housing) by means of optocoupler
Output current with 5 V: IA ≤ 0.25 A and voltage source.
12 V: IA ≤ 0.2 A
24 V: IA ≤ 0.2 A
Input range: 12 V/24 V: asymmetrical and differential
5 V: differential
Pulse generator as 13 mA current source: differential
Line termination (impedance 120Ω), if selected
max. input frequency ≤300 kHz
Functionality of SDCS-IOB-2x
3 different designs available:
SDCS-IOB-21 inputs for 24...48 V DC; RE = 4.7 kΩ
SDCS-IOB-22 inputs for 115 V AC; RE = 22 kΩ
SDCS-IOB-23 inputs for 230 V AC; RE = 47 kΩ
Terminals
Screw type terminals up to 4 mm2
8 digital inputs 8 digital inputs
The functions can be selected by means of software. The functions can be selected by means of software.
Input voltage: 0...8 V ⇒ "0 signal", 16...60 V ⇒ "1 signal" The signal status is indicated by LED.
Time constant of smoothing capacitor: 10 ms All isolated by means of optocouplers.
RE = 15 kΩ Input voltage: IOB-21:0...8 V ⇒ "0 signal", 18...60 V ⇒"1 sig."
The signal refers to the unit housing potential. IOB-22:0...20 V ⇒ "0 signal", 60...130 V ⇒"1 sig."
Auxiliary voltage for digital inputs: +48 V DC, ≤ 50 mA, sustained short- IOB-23:0...40 V ⇒ "0 signal", 90...250 V ⇒"1 sig."
circuit-proof Filter time constant: 10 ms (channels 1...6); 2 ms (channels 7+8)
Auxiliary voltage for digital inputs: +48 V DC; ≤ 50 mA; sustained short-
circuit-proof; referenced to the unit housing potential.
7+1 digital outputs 8 digital outputs
The function can be selected by means of software. The functions can be selected by means of software.
7 outputs: relay driver with free-wheeling diode, total current limitation The signal status is indicated by LED.
≤ 160 mA; short-circuit-proof. 6 of them potential isolated by relay (N.O. contact: AC: ≤250 V/ ≤3 A /
1 relay output - on power board SDCS-POW-1 (N.O. contact: DC: ≤24 V/ ≤3 A or ≤115/230 V/ ≤0.3 A), protected by VDR component.
AC: ≤250 V/ ≤3 A / DC: ≤24 V/ ≤3 A or ≤115/230 V/ ≤0.3 A) protected 2 of them potential isolated by optocoupler, protected by zener diode
by VDR component. (open collector) 24 V DC external, IA ≤ 50 mA.
II F 2-12
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
The digital inputs of SDCS-IOE-1 (DI 9...DI 15) can
be connected to pre-defined functions (see software
group 1o). This board is normally used for stand-alone
mode / joystick operation.
SDCS-CON-2
X17:
X17:
X2: X1:
7 x digital
5
4 x analog
Pulsgeber
1 x Tacho
8 x digital
Terminals
Screw type terminals for finely stranded wires up to 2.5 mm2
Functionality of SDCS-IOE-1
7 digital inputs
The functions can be selected by means of software.
The signal status is indicated by an LED.
All isolated by means of optocouplers.
Input voltage: 0...8 V ⇒ "0 signal", 16...31 V ⇒ "1 signal"
Potentialwise arranged in two groups (DI 9...DI 12 and DI 13...DI 15)
Filter time constant: 2 ms
2 analogue inputs
No pre-defined functions
Current source for PT 100 or PTC element
IA = 5 mA / 1.5 mA
The signals are referenced to the unit housing potential
Please note:
Unless otherwise stated, all signals are referenced to a 0 V potential. Within the power
pack subassembly (SDCS-POW-1) and on all other PCBs, this potential is firmly
connected with the unit’s housing by means of plating through at the fastening
points.
II F 2-13
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Serial interfaces
There are various serial interface options available for Different SDCS-AMC 2 boards are available to adapt
operation, commissioning, diagnosis and controlling. optical cables, cable length and serial interfaces. The
For the control and display panel CDP 312 are serial different SDCS-AMC 2 boards are equipped with 10
connections X33:/X34: on the SDCS-CON-2 availa- or 5 Mbaud optical transmitter and receiver devices.
ble. Three additional serial interfaces are available on A few basic rules must be considered:
the SDCS-AMC-DC 2 board. • Never connect 5 Mbaud and 10 Mbaud devices.
These interfaces use plastic or HCS optical fibres. • 5 Mbaud can handle only plastic fibre optic.
Channel 3 is used for drive/PC interfacing. Channel 0 • 10 Mbaud can handle plastic or HCS cable.
for fieldbus module interfacing or communication to • The branching unit NDBU 95 extends the maxi-
the overriding control system. Channel 2 is used for mum distance.
Master-Follower link or for I/O extension. All three • The maximum distance and suitable configuration
serial interfaces are independent from each other. can be found in the manual Configuration Instruc-
tions NDBU 85/95; Doc no.: 3ADW000100.
CDP 312
Remark: SDCS-CON-2
SDCS-AMC-DC Classic 2
Fieldbus modules Nxxx Power supply
D400
D200
SDCS-AMC-DC 2
SDCS-AMC-DC Classic 2 PE
X2 RXD
SH SHF DG D(N) D(P)
CH 0
CH 2
CH 3
xxxxxxxx
ADAPTER
XM IT
OFF
RxD
RxD
RxD
TxD
TxD
TxD
SDCS-AMC-DC 2 board. X1 ERRO R
to the PLC
X33: electrical
X16:
FCI X34: connection
≤3m Dcs6_com1b.dsf
AC80
optical fibre
PC
AC800M
Interface
- Master-Follower link
Control Operation
Fig. 2.5/6: Options for serial communication
R R F
D U L
0 50 100 150
1 Y N T
SDCS-CON-2
X33:/
X34:
R
D
R
U
F
L
0 50
NLMD100 150
1 Y N T
NDPI
CDP 312
SDCS-CON-2
X33:/
X34:
R
D
R
U
F
L
0 50
NLMD100 150
1 Y N T
II F 2-14
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Panel (control and display panel) Features
The CDP 312 control and display panel communicates • 16 membrane pushbuttons in three function groups
with the power converter via a serial connection in • LCD display has four lines with 20 characters each
accordance with the RS 485 standard at a transmission • Language: English
rate of 9.6 kBaud. It is an option for the converter unit. • Options for the CDP 312:
After completion of commissioning, the panel is not – Cable to separate the panel from the converter.
necessarily required for diagnostic. The basic unit has – Kit for mounting the panel in the cabinet door.
a 7-segment display indicating errors.
Parameters Function
For selecting and adjusting Selects the “functions” operating mode; can be used
all parameters and signals. to perform special functions such as uploading and
0 L 0,0 rpm 00 downloading of parameter sets.
Group
and name 17 RAMP GENERATOR
Subgroup 08 ACCEL 1
and name Status row 0 L 0,0 rpm 00
20.0 s
Value Functions to be UPLOAD <==
selected DOWNLOAD ==>
Display contrast CONTRAST
setting
Actual
Selects the display of feedback values plus the
signal group and the error memory group. Drive
for extensions
ID number Control Speed Main contactor Run status
of the location reference status 1 = Run
drive L = local rpm 0 = open 0 = Stop
selected = remote 1 = closed
Enter
is used in the following modes:
Status row 0 L 0,0 rpm 00 Parameter setting: enter new parameter value
Actual signal SPEEED ACT 0,0 rpm Actual value
name and value CONV CUR 0 A signal display: enter the current signal selec-
Cursor shows U ARM ACT 0 V tion mode
the row selected Signal selection: accept selection and return to
the feedback value signal dis-
play mode
Twin arrow keys
are used to change the group. In the parameter and Arrow keys
reference presetting modes, you can alter the param- are used to select parameters within a group. You al-
eter value or the reference setting ten times faster by ter the parameter value or the reference setting in the
means of the twin arrow keys than by means of the parameter and reference presetting modes. In the
single arrow key. feedback signal display mode, you select the line you
want.
Local/Remote
is used to select local (control
panel) or remote control. Start
starts the drive in local mode.
Reset
Fault acknowledge key. Stop
1 = last fault 0 L 0,0 rpm 00 shuts the drive down if you are in local mode.
2 = last-but-one fault
99 = last fault 1 LAST FAULT
Name of Fault Emergency stop
or alarm
3212:59:35:56 Reference
Total time after
switch-on
is used to activate the reference presetting mode.
HHHH:MM:SS.ss
On Off
in local mode switches the main contactor on. in local mode switches the main contactor off.
II F 2-15
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Operation by PC Drive control
Components required: Components required:
• Plastic optical fibre for distances up to 20 m. • Plastic optical fibre for distances up to 15 m.
• Network up to 200 drives (same as for ACS 600). • Field bus module Nxxx-xx
• HCS optical fibre cable up to 200 m. • FCI (CI810)
See separate manual Configuration Instructions • AC80 (PM825)
NDBU 85/95; Doc no.: 3ADW000100. • AC800 M
Functionality:
• DriveWindow software package➀ for commission- Functionality:
ing, diagnosis, maintenance and trouble shooting; Depends on the used module, interface e.g. to:
structure of connections see Technical Data; Doc • PROFIBUS with NPBA-12
no.: 3ADW000165. • MODBUS+ with NMBP-01
System requirements/recommendation: • AF100 with FCI (CI810)
• PC (IBM-compatible) with 486 processor or higher • AC80 (PM825) or
(min. 50 MHz). • AC800 M
• 8 MB RAM. • further modules on request
• DOS version 5.0 or later. You will find more detailed information on data ex-
• Windows 3.1, 3.11, Windows95/98; Windows change in the specific PLC or fieldbus module docu-
NT4.0. mentation.
• VGA monitor.
• CD-ROM drive.
• PCMCIA slot or PCI/PCMCIA bridge.
In addition to the options provided by the CDP 312
control and display panel, there are further functions
available, and these are described on the following page.
II F 2-16
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Operation by PC (continued)
Features
• Easy-to-use tool for com-
missioning and mainte-
nance.
• Several drives connected
and monitored at the same
time.
• Monitor, edit or save sig-
nals and parameters, clear
graphical presentation.
• High speed communica-
tion between PC and drive
• Versatile back-up func-
tions.
II F 2-17
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
2.6 Options
Line reactors
for armature (DCS 60x) and field
(DCF 60x) supply
Line Configuration C
If an isolation transformer is used, it is
Connecting possible to comply with certain con-
point
necting conditions per Configuration
B without using an additional line reac-
tor. The condition described in Con-
figuration A will then likewise be satis-
fied, since the uk is >1 %.
II F 2-18
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Line reactors L1
DCS Type Line choke Design Line choke Design
400V-690V type for Fig. type for Fig.
50/60 Hz configur. A configur. B
DCS60x-0025-41/51 ND01 1 ND401 4
DCS60x-0050-41/51 ND02 1 ND402 4
DCS60x-0050-61 ND03 1 on request -
DCS60x-0075-41/51 ND04 1 ND403 5
DCS60x-0100-41/51 ND06 1 ND404 5
DCS60x-0110-61 ND05 1 on request -
DCS60x-0140-41/51 ND06 1 ND405 5
DCS60x-0200-41/51 ND07 2 ND406 5
DCS60x-0250-41/51 ND07 2 ND407 5
DCS60x-0270-61 ND08 2 on request -
DCS60x-0350-41/51 ND09 2 ND408 5
DCS60x-0450-41/51 ND10 2 ND409 5
DCS60x-0450-61 ND11 2 on request -
DCS60x-0520-41/51 ND10 2 ND410 5
DCS60x-0680-41/51 ND12 2 ND411 5
DCS601-0820-41/51 ND12 2 ND412 5
DCS602-0820-41/51 ND13 3 ND412 5
DCS60x-1000-41/51 ND13 3 ND413 5
DCS60x-0903-61/71 ND13 3 on request -
DCS60x-1203-41/51 ND14 3 on request -
DCS60x-1503-41/51/61/71 ND15 3 on request -
DCS60x-2003-41/51 ND16 3 on request -
DCS601-2003-61/71 ND16 * 3 on request -
* with forced cooling
Table 2.6/1: Line reactors (for more information see publication Technical Data)
Fig. 4 Fig. 5
II F 2-19
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Aspects of fusing for armature circuits and field supplies of DC drives
Unit configuration Due to cost saving standard fuses are used instead of the
Protection elements such as fuses or overcurrent trips more expensive semiconductor fuses at some applica-
are used whenever overcurrents cannot entirely be tions. Under normal and stable operating conditions,
ruled out. In some configurations, this will entail the this is understandable and comprehensible, as long as
following questions: firstly, at what point should which fault scenarios can be ruled out.
protective element be incorporated? And secondly, in In the event of a fault , however, the saving may cause
the event of what faults will the element in question very high consequential costs. Exploding power semi-
provide protection against damage? conductors may not only destroy the power converter,
but also cause fires.
AC supply: public mains / plant's mains
Cabinet Adequate protection against short-circuit and earth
fault, as laid down in the EN50178 standard, is possi-
3 2
M ble only with appropriate semiconductor fuses.
.
. .
. .
4-Q resp.
2-Q non-regen. 2-Q regenerative
Semiconductor
fuses
M M
II F 2-20
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Conclusion for the field supply
ND30 /
F3.3 built-in
F3.1
2
FF_ASP_b.dsf
II F 2-21
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Semiconductor type F1 fuses and fuse holders for AC and DC power lines
(DCS 601 /DCS 602 - DCF 601/DCF 602)
The converter units are subdivided into two Type of converter Type Fuse holder
groups: DCS60x-0025-41/51 170M 1564 OFAX 00 S3L
– Unit sizes C1 and C2 with rated currents DCS60x-0050-41/51 170M 1566 OFAX 00 S3L
up to 1000 A require external fuses. DCS60x-0050-61 170M 1566 OFAX 00 S3L
– In unit sizes A5, A6 and A7 with rated DCS60x-0075-41/51 170M 1568 OFAX 00 S3L
DCS60x-0100-51 170M 3815 OFAX 1 S3
currents of 900 A to 5200 A, the semicon- DCS60x-0110-61 170M 3815 OFAX 1 S3
ductor fuses are installed internally (no DCS60x-0140-41/51 170M 3815 OFAX 1 S3
additional external semiconductor fuses DCS60x-0200-41/51 170M 3816 OFAX 1 S3
are needed). DCS60x-0250-41/51 170M 3817 OFAX 1 S3
DCS60x-0270-61 170M 3819 OFAX 1 S3
The table on the right assigns the AC fuse DCS60x-0350-41/51 170M 5810 OFAX 2 S3
type to the converter type. In case the con- DCS60x-0450-41/51/61 170M 6811 OFAS B 3
verter should be equipped with DC fuses DCS60x-0520-41/51 170M 6811 OFAS B 3
according to the hints use the same type of DCS60x-0680-41/51 170M 6813 OFAS B 3
DCS60x-0820-41/51 170M 6813 OFAS B 3
fuse used on the AC side now in the plus and DCS60x-1000-41/51 170M 6166 3x 170H 3006
minus line. Blade type fuses are used for all
the converters construction type C1 and C2 Table 2.6/2: Fuses and fuse holders (details see Technical Data)
except the biggest one.
II F 2-22
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Commutating reactor
Converter Reactor
≤500 V; 50/60 Hz
SDCS-FEX-2A ND 30
II F 2-23
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
EMC filters
You will find further in- The paragraphs below describe selection of the electri- • the product's actual emissions
formation in publica- cal components in conformity with the EMC Guide- The EMC Guideline expects EMC to be taken into
tion: line. account when a product is being developed; however,
Technical Guide EMC cannot be designed in, it can only be quantita-
chapter: EMC Com- The aim of the EMC Guideline is, as the name implies, tively measured.
pliant Installation and to achieve electromagnetic compatibility with other Note on EMC conformity
Configuration for a products and systems. The guideline ensures that the The conformity procedure is the responsibility of both
Power Drive System emissions from the product concerned are so low that the power converter's supplier and the manufacturer of
they do not impair another product's interference the machine or system concerned, in proportion to
immunity. their share in expanding the electrical equipment in-
In the context of the EMC Guideline, two aspects must volved.
be borne in mind:
• the product's interference immunity
First environment (residential area with light industry) with restricted distribution
satisfied
Residential area Supply transformer for a residential Light industry Supply transformer for a residential
area (rating normally ≤ 1,2 MVA) area (rating normally ≤ 1.2 MVA)
Residential area
Earthed
neutral
Earthed
neutral Earthed public 400-V Earthed public 400-V Earthed public 400-V
network with neutral network with neutral network with neutral
conductor conductor conductor
To other loads which have to be protected from the system disturbances caused by
To other loads which have to be protected from the system disturbances caused by
power converters (HF interference and commutation notches)
Line reactor +
Line reactor Y-capacitor Line reactor Line reactor
alternative
M M M M M M M M
Operation at public An isolating transformer Operation at public Operation at public An isolating transformer
low-voltage network with an earthed screen low-voltage network low-voltage network with an earthed screen
together with other and earthed iron core together with other together with other and earthed iron core
loads of all kinds. renders mains filter and loads of all kinds. loads of all kinds. renders mains filter and
line reactor superfluous. line reactor superfluous.
II F 2-24
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
For compliance with the protection objectives of the For emitted interference, the following apply:
German EMC Act (EMVG) in systems and machines, EN 61000-6-3 Specialised basic standard for emissions in light industry can
the following EMC standards must be satisfied: be satisfied with special features (mains filters, screened power
cables) in the lower rating range *(EN 50081-1).
Product Standard EN 61800-3
EN 61000-6-4 Specialised basic standard for emissions in industry
EMC standard for drive systems (PowerDriveSys-
*(EN 50081-2)
tem), interference immunity and emissions in resi-
dential areas, enterprise zones with light industry For interference immunity, the following apply:
and in industrial facilities. EN 61000-6-1 Specialised basic standard for interference immunity in residen-
tial areas *(EN 50082-1)
This standard must be complied with in the EU for
EN 61000-6-2 Specialised basic standard for interference immunity in indus-
satisfying the EMC requirements for systems and
try. If this standard is satisfied, then the EN 61000-6-1 standard
machines! is automatically satisfied as well *(EN 50082-2).
Standards Classification
Second environment (industry) with restricted distribution EN 61800-3 The following overview
utilises the terminology
Not applicable EN 61000-6-3 and indicates the action
required in accordance
satisfied on customer's request satisfied EN 61000-6-4
with Product Standard
EN 61000-6-2 EN 61800-3
satisfied For the DCS 500B series,
EN 61000-6-1
the limit values for emit-
Medium-voltage network Medium-voltage network ted interference are complied with,
Industrial zone
Supply transformer for a
Industrial zone Converter provided the action indicated is car-
residential area (rating transformer
normally ≤ 1.2 MVA) with earthed ried out. This action is based on the
Converter
transformer
term Restricted Distribution used in
Earthed iron core the standard (meaning a sales chan-
neutral Earthed 400-V network
(and earthed I > 400 A
with neutral conductor;
screen where and/or nel in which the products concerned
appropriate)
3~ ≤ 400 A U > 500 V can be placed in the stream of com-
merce only by suppliers, customers
or users which individually or jointly
possess technical EMC expertise).
alternative
alternative
alternative
II F 2-25
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Filter in a grounded line (earthed TN or TT
network)
The filters are suitable for grounded lines only, for
example in public European 400 V lines. According to
EN 61800-3 filters are not needed in insulated indus-
trial lines with own supply transformers. Furthermore
they could cause safety risks in such floating lines (IT
networks).
Converter IDC [A] Const. Filter type for y=4 Filter type for y= 5 Filter type for y=6 or 7
type
DCS60x-0025-y1 25A C1a NF3-440-25 NF3-500-25 ---
DCS60x-0050-y1 50A C1a NF3-440-50 NF3-500-50 ---
DCS60x-0075-y1 75A C1a NF3-440-64 NF3-500-64 ---
DCS60x-0100-y1 100A C1b NF3-440-80 NF3-500-80 ---
DCS60x-0140-y1 140A C1b NF3-440-110 NF3-500-110 ---
DCS60x-0200-y1 200A C2a NF3-500-320 NF3-500-320 ---
DCS60x-0250-y1 250A C2a NF3-500-320 NF3-500-320 ---
DCS60x-0270-61 250A C2a NF3-500-320 NF3-500-320 NF3-690-600 ➀
DCS60x-0350-y1 350A C2a NF3-500-320 NF3-500-320 ---
DCS60x-0450-y1 450A C2a NF3-500-600 NF3-500-600 NF3-690-600 ➀
DCS60x-0520-y1 520A C2a NF3-500-600 NF3-500-600 ---
DCS60x-0680-y1 680A C2b NF3-500-600 NF3-500-600 ---
DCS601-0820-y1 740A C2b NF3-500-600 NF3-500-600 ---
DCS602-0820-y1 820A C2b NF3-690-1000 ➀ NF3-690-1000 ➀ ---
DCS60x-1000-y1 1000A C2b NF3-690-1000 ➀ NF3-690-1000 ➀ ---
DCS60x-0903-y1 900A A5 NF3-690-1000 ➀ NF3-690-1000 ➀ NF3-690-1000 ➀
DCS60x-1203-y1 1200A A5 NF3-690-1000 ➀ NF3-690-1000 ➀ NF3-690-1000 ➀
DCS60x-1503-y1 1500A A5 NF3-690-1600 ➀ NF3-690-1600 ➀ NF3-690-1600 ➀
DCS60x-2003-y1 2000A A5 NF3-690-1600 ➀ NF3-690-1600 ➀ NF3-690-1600 ➀
≤ 3000A A6 NF3-690-2500 ➀ NF3-690-2500 ➀ NF3-690-2500 ➀
➀ Filter only available on request
Single - phase filters for field supply Converter type of dc current Filter type ➊
Many field supply units are single - phase converters for field supply unit Umax = 250 V
II F 2-26
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Commutation and line reactors Installation hints
(see also Section Line reactors in this chapter) • All metal cabinets available on the market can be
Due to the maximum power of public 400 V trans- used.
formers (PMAX = 1.2 MVA ⇒ IMAX = 1732 A) and due • The mounting plate must be made from steel with
to their relative voltage drop of 6% or 4% the maxi- zinc coating and without any painting. It must be
mum AC current which is available for a converter is connected with the PE busbar by several bolts/
346 A or 520 A (IDC ≤ 422 A or 633 A). cables.
• The converter, the line reactors, fuses, contactors
Isolating transformers and the EMC filter are to be placed on the mounting
An isolating transformer makes line chokes unneces- plate so that the connections are as short as possible,
sary because of its leakage inductance, and a grounded especially those from the converter via the line choke
screen between its windings saves an EMC filter. The to the filter.
screen and the iron core must be well connected with • The cables for digital signals which are longer than
the mounting plate of the converter. 3m and all cables for analogue signals must be
screened. Each screen must be connected at both
Converter transformers ends by metal clamps or comparable means directly
A converter transformer transfers a high power directly on clean metal surfaces. In the converter cubicle this
from a medium voltage network to a single large kind of connection must be made directly on the
converter or to a local low voltage network for several sheet metal close to the terminals.
converters. Furthermore it acts as isolating transformer. • The necessity of a screen for power cables depends
on the length of the cable and on the environmental
If such a converter transformer has no screen the EMC demands. If a screen is necessary then it must be
demands are nevertheless fulfilled in most cases, be- pressed by a well conducting metal clamp directly
cause the RF interference can hardly get via the medi- against the mounting plate or the PE busbar of the
um-voltage network and the transformer of the public converter cabinet.
network to the loads which must be protected against • Screened cables to the armature and to the excitation
disturbances. winding cause the lowest noise level. The armature
current cable must contain a wire for a PE connec-
tion if the copper cross section of the screen cannot
fulfil the safety demands.
• If a screen is not necessary the armature PE
current cable must be a four-wire cable.
PE
Two wires are needed as PE to discharge
the parasitic RF currents from the motor
to the EMC filter in the cabinet.
II F 2-27
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
II F 2-28
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
3 Overview of crane software
CraneDrive functions
Software DCAAxxxx
Drive Control
Software 15.6xx
Torque Control
SDCS-CON-2
Software 15.2xx
I/O handling
II F 3-1
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
3.3 Start, Stop and Fault Reactions
Power up
When the electronics power supply is switched on the
drive remains in the ON_INHIBIT state until electri-
cal disconnect input (DI4) is closed. In case of a fault
the drive remains in the FAULT state.
Normal start
Status bit RDY_FOR_ON = 1 signals that no faults are
pending and that the device is ready to close the main,
fan and field contactor.
The command DRIVE ON = 1 closes fan, field and
main contactor and activates the field control.
In stand-alone control mode the ON command is
generated internally by the first rising edge of the RUN
command (direction + reference).
Status bit RDY_FOR_RUN = 1 indicates that the field
converter is active and that the drive is ready to generate
torque.
The command START OVR = 1 activates speed and
torque control.
Status bit RUNNING = 1 indicates that the drive is in
normal operation.
Normal stop
START OVR = 0 sets the speed reference to zero and
the drive decelerates by ramp.
After the actual speed has reached zero the status bit
RUNNING is reset, the armature converter sets the
firing angle to maximum. The state RDY_FOR_RUN
is entered, when the current has reached zero.
ON = 0 sets RDY_FOR_RUN = 0 and the field current
reference to zero. The field converter sets the firing
angle to maximum. The contactors open, when the
current has reached zero.
ON = 0 internally forces RUN = 0.
Fault reaction
Depending on the actual fault the armature current
and/or field current is reduced to zero as fast as possible
with single pulses and maximum firing angle. Contac-
tors are opened when the current has reached zero.
The state TRIPPED is entered and after a successful
reset the state ON_INHIBIT.
II F 3-2
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
3.4 Crane functions
Mechanical Brake: Controls and supervises the open- Start and Stop: Supervising and
ing and closing of the brake. control logic for starting and stopping the drive,
Fast Stop: Stops the drive as fast as possible. When including torque proving.
stopped, movement in the opposite direction to the Speed Reference: Individual settings
fault is possible e.g. external detection for overload or of acceleration and deceleration ramp times. For
slack rope. smooth load handling and reduction of 'shock'
Torque Proving: Ensures that the motor is able to loading.
produce torque before brake is lifted.
Speed and Torque: Ensures a mini-
Speed Monitor: Supervises actual motor speed to be mum variation of speed independently of the load.
within given limits. It also detects overspeeds and zero
speed for control interlocks. Torque Memory: Presetting of torque when starting
the hoist with suspended load. The risk of load drop is
Torque Monitor: Supervises the correlation between thereby minimized.
requested speed & actual motor speed and direction.
Power Optimization: Automatic field weakening of
Fault Handling: Monitors internal faults, identifies hoist drive. Ensures maximum hoist speed relative to
possible causes and presents fault history. the load and thus optimizes cycle times.
Master Follower: Facilitates load sharing of two mo-
tors on the same shaft. Can also be used when dual-
redundancy is required.
Speed Correction: Coordination of two drives from an
external control system. Input for correction of speed
error when used in synchronized operations.
Shared Motion: One DCS 600 CraneDrive is able to
handle two different motors (of two different motions)
including the different field windings and brakes.
II F 3-3
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
3.5 Speed Control 3.6 Torque Control
The speed controller is located in the AMC board Flux and Torque Calculation
software. The torque control is in general an open loop control.
The flux is adjusted by the field current. The reference
Speed reference of the field current is generated by the superimposed
The source of the reference is depending on the oper- armature voltage control.
ating mode. The torque is adjusted by the armature current. The
conversion from torque to current reference is done by
Overriding control means of the calculated flux (based on the field current
system, fieldbus adapters ➔ remote mode, DDCS and saturation characteristic).
via AMC board
DriveWindow ➔ local mode, DDCS via Torque reference features
AMC board • Torque reference A with 1st order filter and load
Panel CDP312 ➔ local mode, connector share
on CON-2 • Torque reference B with torque ramp
Analogue inputs ➔ local I/O • Torque reference limiter
• Torque step
Speed reference features
• Speed reference limiter A good behaviour in the field weakening requires speed
• Variable slope rate measurement by tachometer or encoder.
• Speed correction
A simplified scheme of the torque reference chain is
Speed measurement given in diagram fig. 3.9/2.
The actual speed may be calculated from:
• Armature voltage
• Analogue tachometer
3.7 HMI (Human Machine Interface)
• Pulse encoder The HMI is performed by CDP 312 control panel
or by DriveWindow.
Controller features Both tools contain:
• PID controller • Display of drive signals
• Window control • Setting of drive parameters
• Acceleration compensation • Display fault and alarm messages
• Speed and torque adaptation • Control the drive in local operation
• Droop
• Additional torque references
• Torque limitation and gear backlash function (the
integral part of the controller is set to a suitable value
on limitation)
• Oscillation damping (band rejection filter for speed
error)
II F 3-4
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
3.8 Torque Generation
II F 3-5
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
3.9 Software diagrams
Introduction
The designation of parameters and signals consist of a
group and an index.
01.02
23.05
X
Signal
Parameter
Index
Group
Fig. 3.9/1: Parameter/signal designation
II F 3-6
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
Fig. 3.9/2:
SPEED REFERENCE CHAIN
LOCAL
FIELDBUS AI SPEED SELECT
ADAPTER AN IN 1 VALUE
ACCELERATION
COMM MODULE AN IN 2 VALUE
Datasets 1, 3, 5 LOCAL AN IN 3 VALUE
COMPENSATION SPEED CONTROL
98.02 AN IN 4 VALUE
LOCAL REF1 AN IN TACHO VALUE
Selector
MCW
0 TORQ ACC COMP REF
REF1
REF2
1.12
Datasets 2, 4, 6 SPEED REF 23.04 ACC COMP DER TIME
SPEED CORR RAMP 0
MSW ACC COMPFILT TIME
ACT1 RAMPED INCH REF 0
ACT2 DROOP RATE
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
TIS VAL MIN SPEED TIS VAL
3.08 3.08 = FB CW = Field Bus Command Word MIN SPEED
23.03 motor speed
DERIVATION TIME
CDP312 or KPS TIS MAX SPEED
DERIV. FILT TIME
DRIVES KPS TIS MIN SPEED
WINDOW
LOCAL CTRL
PANEL
DIGITAL
II F 3-7
OUTPUTS
Fig. 3.9/3:
TORQUE CONTROL CHAIN
II F 3-8
Torque control chain
TORQUE REFERENCE
FILTER SELECTOR
TORQ REF A TORQUE STEP
24.03 TORQUE LIMITER
TORQUE SELECTOR
M/F 72.02
TORQ REF 5 TORQ USED REF
0 0
72.08 TORQ REF A FTC 2.14
21 LOAD COMPENSATION TORQ
LIMITER 3
REF 4 to SUM
TORQ REF 1 4
72.03 MIN 5 6
2.09
LOAD SHARE
TORQ REF 3 20.05 MAXIMUM TORQUE
MAX
LOCAL TREF TORQMAX 2.11 MINIMUM TORQUE
20.06
TREF TORQMIN SPEED CONTROLLE R OUTPUT TC TORQMAX
TORQ REF B RAMPING +
TORQ REF 2 TC TORQMIN
AI2 or 2.10 +
Fieldbus from PID
controller
LOCAL TORQUE REF
(LOCAL REF 2)
24.01 TORQ RAMP UP
AMC
CON
Analogue inputs Analogue outputs
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
AI 1,2,3 A
AIx
A AN IN X VALUE
[AN OUT x INDEX] + D
AN IN TACHO VALUE AO1
D
D + (AO2)
A
Limiter
Current
4096== Motor nominal current Measurem.
LOAD CUR ACT FILT
from TORQUE
EMF REF SEL
0 VOLT ACTUAL RL EMF VOLT ACT M M
EMF
V REF 1 1.09 Calc.
4096 = 100% of
MOTOR 1 MOTOR 2 I_MOTx_FIELD_A
FLUX REF EMF EMF ACT FILT TC
EMF
CONTROLLER 46.06
0 FLUX REF SUM Field
EMF REF Current 1.06 FIELD CUR M1
USED FEX TYPE Measurem.
FLUX/FIELD 15.05
1,2,4,5,6,7,
V ref Modification EMF CON KP 46.03 LINEARIZATION Field
0 8,9,10,11,12,13
INT EMF REF EMF CON KI 46.04 Current 1.07 FIELD CUR M2
1 V LIM P FIRST
41.19 EMF CON BLOCK FIELD EXCITER Measurem.
2 MUX V LIM N
LEV 46.05
3 V REF SLOPE FIELD CUR REF M1
MOT 1 NOM FLD CUR 41.03
AI V REF via drive logic
V COR
V REF 2
V STEP 46.11 FIELD 2 REF
FLD CUR @40% FLUX
41.14
FLUX COR
FLD CUR @70% FLUX
3,4 SECOND
41.15 FIELD EXCITER
FLD CUR @90% FLUX
FLUX REF 41.16 FIELD CUR REF M2 MOT 2 NOM FLD CUR 41.17
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
FLUX
CONTROL FLUX REF FLD WEAK
MOTOR SPEED
1.01
II F 3-9
MOTOR NOM
SPEED 99.08
MAXIMUM
FLUX
II F 3-10
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
4 Connection examples
4.1 Control connections
64.1 Stand-alone
64.10 Step Joystick
Inputs/outputs
Depending on the drive modes there are different
possibilities for inputs and outputs.
Digital Inputs
Input Signal use Description
SDCS-CON-2
Digital Inputs
Input Signal use Description
SDCS-IOE-1
DI 9 DI 9
Fast STOP N
DI 10 DI 10 Overload
configurable Slow down N
DI 11 DI 11 .....
see Group 10
DI 12 DI 12
DI 13 DI 13 Step ref 1
DI 14 DI 14 Step ref 2
DI 15 DI 15 Step ref 3
Digital Outputs
Output Signal use Description
DO 6 DIG_OUT 6 Ready
Running
DO 7 DIG_OUT 7 configurable
Fault ...
DO 8 DIG_OUT 8 see Group 14
II F 4-1
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
I/O configuration example for pot joystick operation
64.1 Stand-alone
64.10 Joystick
Inputs/outputs
Depending on the drive modes there are different
possibilities for inputs and outputs.
Digital Inputs
Input Signal use Description
SDCS-CON-2
Analogue Inputs
Input Signal use Description
SDCS-CON-2
0V
+10 V
Digital Inputs
Input Signal use Description
SDCS-IOE-1
DI 9 DI 9
DI 10 DI 10
DI 11 DI 11 Fast STOP N
Overload
DI 12 DI 12 configurable Slow down N
.....
DI 13 DI 13 see Group 10
DI 14 DI 14
DI 15 DI 15
Digital Outputs
Output Signal use Description
DO 6 DIG_OUT 6 Ready
Running
DO 7 DIG_OUT 7 configurable
Fault ...
DO 8 DIG_OUT 8 see Group 14
II F 4-2
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
I/O configuration example for radio control operation
64.1 Stand-alone
64.10 Radio Joystick
Inputs/outputs
Depending on the drive modes there are different
possibilities for inputs and outputs.
Digital Inputs
Input Signal use Description
SDCS-CON-2
DI 2 DI 2 configurable
Analogue Inputs
Input Signal use Description
SDCS-CON-2
0V
+10 V
Digital Inputs
Input Signal use Description
SDCS-IOE-1
DI 9 DI 9
DI 10 DI 10
DI 11 DI 11 Fast STOP N
Overload
DI 12 DI 12 configurable Slow down N
.....
DI 13 DI 13 see Group 10
DI 14 DI 14
DI 15 DI 15
Digital Outputs
Output Signal use Description
DO 6 DIG_OUT 6 Ready
Running
DO 7 DIG_OUT 7 configurable
Fault ...
DO 8 DIG_OUT 8 see Group 14
II F 4-3
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
I/O configuration example for fieldbus operation (Fieldbus Mode)
64.1 Not Stand-alone
98.2 Fieldbus or overriding control system
Inputs/outputs
Depending on the drive modes there are different
possibilities for inputs and outputs.
Digital Inputs
Input Signal use Description
SDCS-CON-2
PLC DI 2
DI 3
DI 2
ACK_M_CONT
configurable
of pos meas.
9 WARNING Warning
12 HW SYNC Hardware
synchronization inhibit 10 LIMIT Drive in torque limit
Digital Outputs
Output Signal use Description
Master/Follower is normally a load sharing application. The Master is speed controlled and the Follower is
It is designed for applications running two DCS 600 normally torque controlled.
CraneDrives being coupled by a motor shaft via gears,
rails, etc. This feature is useful for:
• Hoist drive - operation on one drum
The Master/Follower application is controlling the use Follower torque controlled
load distribution between the two drives. The Master is
sending control signals and references (e.g. speed or • Travel drive - weak mechanical connection
torque) through the Master/Follower link to the Fol- use Follower window controlled
lower. The Master is also reading back status informa-
tion from the Follower to ensure a safe operation. • Redundancy purpose
use emergency parameter set handled by user
The Master/Follower application can be used for both macro
hoist and travel motions, as well as in fieldbus mode
and stand-alone mode.
DCS 600
CraneDrive
Control word
Torque reference
Status word
Fig 4.1/1: Master Follower
PLC
DCS 600
CraneDrive
Control word
Torque reference
Status word
Fig 4.1/2: Master Follower with PLC control
II F 4-5
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
400V 50Hz
L1 L2 L3
F1 F30
T3 T30
K16 500V 12 500V 12
460V 11 460V 11
4.2 Wiring diagram
F3 415V 10 415V 10
400V 9 400V 9
365V 8 365V 8
350V 7 350V 7
II F 4-6
Emergency Electrical DO1 DO3 DO2 DO3 DO4 DO8 T2 6 6
Fig. 4.2/1:
265V 265V
Stop disconnect [K10] 230V 5 5
11 690V 250V 250V
12 3 4 4
1 1 10 660V 1 90V 90V
60V 3 60V 3
Overspeed relay X2:4 F4 F5
9 600V F2 2 2
Kx crane safety* 8 575V
2 4 30V 30V
crane safety * 2 2 1 1
X2:5 circuit circuit 7 525V
Other safety 115V 6 500V
functions 13 5 450V
4 415V
3 400V
Watchdog 2 380V
DO5
1 1 3 5 1 3 1 3
14 K1 K3 K30
Kx * K16 K5 K10 K3 K30 K1 KB1 KB2
2 4 6 2 4 2 4
K 10 is necessary if 1 3
current consumption L1 L3 L3
of K1 is > 3 A K5
2 4
AMC-DC 2
Power supply depending on the unit type (C1, C2, A5, C4)
(POW-1) DCS 600
CH 3
Converter 1st Field 2nd Field
AITAC AI1 AI2 AI3 AI4 module exciter unit exciter unit
X33 _ + _ + _ + _ + _ + DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 COM DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
(FEX-1/2) (DCF 503A)
X4: 3x AO
or DCF 503A
A10 SDCS-IOB-3 A9 SDCS-IOB-23
1.5/5mA current source
±10V voltage source X7:1/X7:2
X5:1...10
X3: 1 2 3 4 5 6 7 8 9 10 X6: 1 2 3 4 5 6 7 8 X4: 1 2 3 4 5 6 7 8 X5: 1 2 3 4 5 6 7 8 C1 D1 X1: 5 3 X1: 5 3
3ADW000139R0401_DCS600_CraneDrive_System description_e_d
_ _ _
PS5311 + + +
PANEL Gain
CDP 312 adjust K16 KB1 KB2
e.g. Pressure
K5 K3 K1 KB1 Kx KB2
switch at C4
(K10)
1 2 3 4 module
K5 K1 to T2.14
Digital input voltage
to F4.2
Motor 2 PLC
B1
Motor 1
if there are intermediate terminals
T M
+
II F 4-8 *139R0401A4100000*