PowerPact™ H-, J-, and L-Frame Circuit Breakers

Catalog Numbering

Catalog Numbering

– J L L 3 6 250 T – ––––
Accessory Suffix Code (See Table 2)
Frame Poles Amperage
I-Line™ Phasing
H H-Frame 2 2P 060 60 A
Trip Unit — ABC (3P)
J J-Frame 3 3P 100 100 A
6 CBA (3P)
L L-Frame 4 4P 150 150 A Micrologic™ Electronic Trip Units 1 AB (2P)
250 250 A
Terminations U31 LI Standard Protection 2 AC (2P)
400 400 A
Brand U33 LSI Standard Protection 3 BA (2P)
L Lugs Line/Load Side 600 600 A
_ Square D™ U43 LSI plus Ammeter 4 BC (2P)
M Lugs Line Side 000 Switch or
N Schneider Frame only U44 LSIG plus Ammeter 5 CA (2P)
P Lugs Load Side
Electric U53 LSI plus Energy Management 6 CB (2P)
F Bus Bar Voltage
A I-Line U54 LSIG plus Energy Management
S Rear Connected 6 600 Vac M37 Magnetic Only (L-Frame Only)
N Plug-in M38 Motor Protector Circuit Breaker
D Drawout S40 400 A Molded Case Switch (L-Frame Automatic Switch)
K Reverse I-Line S60 600 A Molded Case Switch (L-Frame Automatic Switch)
F40 400 A L-Frame Only (No Trip Unit)
F60 600 A L-Frame Only (No Trip Unit)
Performance Level (kA) (See Table 1)
Thermal-Magnetic Trip Units
— Standard Fixed Trip Unit (Suitable for reverse connection)
F06 60 A H-Frame Only (No trip unit)
F15 150 A H-Frame Only (No trip unit)
F25 250 A J-Frame Only (No trip unit)
T Complete Circuit Breaker (Frame + removable trip unit)
S15 150 A Molded Case Switch (H-Frame automatic switch)
S17 175 A Molded Case Switch (J-Frame automatic switch)
S25 250 A Molded Case Switch (J-Frame automatic switch)
C 100% Rated Continuous Current Rating1
M71 30 A H-Frame Motor Circuit Protector (MCP)
M72 50 A H-Frame Motor Circuit Protector (MCP)
M73 100 A H-Frame Motor Circuit Protector (MCP)
M74 150 A H-Frame Motor Circuit Protector (MCP)
M75 250 A J-Frame Motor Circuit Protector (MCP)
D81 500 Vdc 150–175 A J-Frame Molded Case Circuit Breaker
D82 500 Vdc 200–250 A J-Frame Molded Case Circuit Breaker
R 100% Rated Continuous Current Rating Complete Circuit Breaker
(Frame + removable trip unit)

1 100% ratings valid for:


3P H/J frame unit mount only
3P/4P L-frame 250 A and 400 A unit mount
3P L-frame 250 A and 400 A I-Line
Table 1: Interrupting Rating
UL/CSA/NOM IEC 647-2 Icu/Ics
240 Vac 480 Vac 600 Vac 250 Vdc1 500 Vdc2 220/240 Vac 380/440/415 Vac 500/525 Vac 690 Vac 250 Vdc1 500 Vdc3
D 25 kA 18 kA 14 kA 20 kA — 25/25 kA 18/18 kA 14/14 kA — 20 kA 20 kA

G 65 kA 35 kA 18 kA 20 kA 20 kA 65/65 kA 35/35 kA 18/18 kA — 20 kA 20 kA

J 100 kA 65 kA 25 kA 20 kA — 100/100 kA 65/65 kA 25/25 kA — 20 kA 20 kA

L 125 kA 100 kA 50 kA 20 kA — 125/125 kA 100/100 kA 50/50 kA — 20 kA 20 kA

R 200 kA 200 kA 100 kA — — 150 kA 125 kA 75 kA 20 kA — —


1 250 Vdc ratings only available with PowerPact H or J circuit breakers with thermal-magnetic trip units (not including MCP).
2 UL 500 Vdc ratings only available with PowerPact J circuit breakers with thermal-magnetic trip units (not including MCP).
3 IEC 500 Vdc rating only available on PowerPact J-frame circuit beakers.

8
05/2012 ™ © 2011–2012 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
General Information

Table 6: Circuit Breakers


Circuit Breaker 150 A H-Frame 250 A J-Frame 400 A L-Frame 600 A L-Frame
Circuit Breaker Type HD HG HJ HL HR JD JG JJ JL JR LD LG LJ LL LR LD LG LJ LL LR
Number of poles1 2, 3 3 2, 3 3 3, 4 3, 4
Amperage Range (A) 15-150 70-250 70-400 200-600
UL 489 Circuit Breaker Ratings
240 Vac 25 65 100 125 200 25 65 100 125 200 25 65 100 125 200 25 65 100 125 200
480 Vac 18 35 65 100 200 18 35 65 100 200 18 35 65 100 200 18 35 65 100 200
UL/CSA/NOM
600 Vac 14 18 25 50 100 14 18 25 50 100 14 18 25 50 100 14 18 25 50 100
(kA rms)
250 Vdc2 20 20 20 20 --- 20 20 20 20 --- --- --- --- --- --- --- --- --- --- ---
500 Vdc2, 3 --- --- --- --- --- --- 20 --- --- --- --- --- --- --- --- --- --- --- --- ---
IEC 947-2 Circuit Breaker Ratings
220/240 Vac 25 65 100 125 150 25 65 100 125 150 25 65 100 125 150 25 65 100 125 150
380/415 Vac 18 35 65 100 125 18 35 65 100 125 18 35 65 100 125 18 35 65 100 125
Ultimate breaking capacity 440/480 Vac 18 35 65 100 125 18 35 65 100 125 18 35 65 100 125 18 35 65 100 125
(Icu) 500/525 Vac 14 18 25 50 75 14 18 25 50 75 14 18 25 50 75 14 18 25 50 754
(kA rms) 690 Vac --- --- --- --- 20 --- --- --- --- 20 --- --- --- --- 20 --- --- --- --- 20
250 Vdc2 --- --- --- --- --- 20 20 20 20 --- --- --- --- --- --- --- --- --- --- ---
500 Vdc2, 3 --- --- --- --- --- 20 20 20 20 --- --- --- --- --- --- --- --- --- --- ---
Service breaking capacity (Ics) % Icu 100% 100% 100% 100%
Insulation Voltage Vi 750 Vac 750 Vac 750 Vac 750 Vac
Impulse Withstand Voltage Vimp 8 kVac 8 kVac 8 kVac 8 kVac
Operational Voltage Ve 690 Vac 690 Vac 690 Vac 690 Vac
Sensor Rating In 150 A 250 A 400 A 600 A
Utilization Category --- A A A A
Operations (Open-Close Cycles)
Without Current 4000 5000 5000 5000
With Current 4000 1000 1000 1000
Protection and Measurements
Short-circuit protection Magnetic only                    
Thermal-magnetic           --- --- --- --- --- --- --- --- --- ---
Electronic                    
Overload/short-circuit
with neutral protection (Off-0.5-1-OSN)5                    
protection
with ground fault protection                    
with zone selective interlocking (ZSI)6                    
Display / I, V, f, P, E, THD measurements / interrupted-current
                   
measurement
Front display module (FDM121)                    
Operating assistance                    
Counters                    
Options
Histories and alarms                    
Metering Com                    
Device status/control com                    
Dimensions / Weight / Connections

Dimensions 3P Height 6.4 (163) 7.5 (191) 13.38 (340) 13.38 (340)
(Unit Mount) Width 4.1 (104) 4.1 (104) 5.51 (140) 5.51 (140)
in. (mm) Depth 3.4 (86) 3.4 (86) 4.33 (110) 4.33 (110)
Weight 3P - lb. (Kg) 4.8 (2.2) 5.3 (2.4) 13.2 (6.0) 13.7 (6.2)
Unit Mount    
I-Line™    
Rear Connection    
Connections / Terminations
Plug-In    
Drawout    
Optional Lugs    
1 H and J-frame breakers with Micrologic™ trip units available only with 3P. The HJ, HL and the J-Frame 2P breakers are 3P modules.
2 DC not available with PowerPact H, J or L-frame circuit breakers with Micrologic trip units.
3 500 Vdc specific catalog numbers, ungrounded UPS systems only.
4 Ics for 600 A L-frame circuit breaker at 525 V is 19 kA.

17
© 2011–2012 Schneider Electric ™ 05/2012
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Circuit Breakers

Table 13: PowerPact J-Frame 250 A Unit-Mount Thermal-Magnetic Circuit Breakers with Factory Sealed Trip Unit
(Suitable for Reverse Connection)

Adjustable AC Interrupting Rating

Current Magnetic Trip D G J1 L1 R1


Rating
@ 40 C Standard Standard Standard Standard Standard
100% 100% 100% 100% 100%
Hold Trip (80%) (80%) (80%) (80%) (80%)
Rated2 Rated2 Rated2 Rated2 Rated2
Rated Rated Rated Rated Rated

J-Frame, 250 A, 2P, 600 Vac 50/60Hz, 250 Vdc


150 A3 750 A 1500 A JDL26150 JDL26150C JGL26150 JGL26150C JJL26150 JJL26150C JLL26150 JLL26150C — —
175 A3 875 A 1750 A JDL26175 JDL26175C JGL26175 JGL26175C JJL26175 JJL26175C JLL26175 JLL26175C — —
200 A4 1000 A 2000 A JDL26200 JDL26200C JGL26200 JGL26200C JJL26200 JJL26200C JLL26200 JLL26200C — —
225 A4 1125 A 2250 A JDL26225 JDL26225C JGL26225 JGL26225C JJL26225 JJL26225C JLL26225 JLL26225C — —
250 A4 1250 A 2500 A JDL26250 JDL26250C JGL26250 JGL26250C JJL26250 JJL26250C JLL26250 JLL26250C — —

J-Frame, 250 A, 3P, 600 Vac 50/60Hz, 250 Vdc


150 A3 750 A 1500 A JDL36150 JDL36150C JGL36150 JGL36150C JJL36150 JJL36150C JLL36150 JLL36150C JRL36150 JRL36150C
175 A3 875 A 1750 A JDL36175 JDL36175C JGL36175 JGL36175C JJL36175 JJL36175C JLL36175 JLL36175C JRL36175 JRL36175C
200 A4 1000 A 2000 A JDL36200 JDL36200C JGL36200 JGL36200C JJL36200 JJL36200C JLL36200 JLL36200C JRL36200 JRL36200C
225 A4 1125 A 2250 A JDL36225 JDL36225C JGL36225 JGL36225C JJL36225 JJL36225C JLL36225 JLL36225C JRL36225 JRL36225C
250 A4 1250 A 2500 A JDL36250 JDL36250C JGL36250 JGL36250C JJL36250 JJL36250C JLL36250 JLL36250C JRL36250 JRL36250C
1 UL Listed/CSA Certified as current limiting circuit breakers.
2 100% rated circuit breakers have copper lugs and can be used with copper wire only.
3 Standard Lug Kit: AL175JD Terminal Wire Range: 4–4/0 AWG Al or Cu
4 Standard Lug Kit: AL250JD Terminal Wire Range: 3/0 AWG–350 kcmil Al or Cu

25
© 2011–2012 Schneider Electric ™ 05/2012
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Trip Units

Table 48: Trip Unit Availability

H-, J-Frame L-Frame

Trip Unit Type Trip Unit Trip Unit


Trip
Unit Trip

5 .2 E
.9 5 .9 6
0 .9 4 .9 7
>11
>30 .9 3 .9 8
.9 2
% Ir 1
.9 Io )
>30
A Ir (4x

M icor lo g ic
5
3 6
2 .5

Unit
8
2 10
1 .5 x Ir )
Is d(

1250 2500

Distribution Protection 250A


T-M N/A
Thermal-Magnetic
ln lm (= li)

3.2

8 16
30 35 40 4 4 6 8 tr
25 45 2 3 10

Distribution Protection 20
15 60
50 1
.5 16
16
2
1.5 15
12

Micrologic™ 3.2 Ir (A) tr @ 6 Ir Ii (x In) Ir Ii

Micrologic 3.3
LI 200 225 250
175
150
300
350
2
1
4
8
16

16
3
2
4
5
6

10
8

125 450 .5 16 1.5 12


Ir (A) Tr @ 6 Ir Ii (x In) Ii

3.2S
3.3S
Micrologic
Distribution Protection 25
20
30 35 40
45
50
3
2
4
5 6

10
8 3
2
4 6 8
10
12 tsd
tr

15 60 1.5 12 1.5 15

LSI Micrologic 3.2S Ir (A) Isd (x In) Ii (x In) Ir Isd Ii

Micrologic 3.3S
200 225 250 5 5
4 6 4 6 tr
Fixed ST and LT delays 175
150
125
300

450
350
3
2
1.5 12
8
10
3
2
1.5 12
10
8

tsd
Ir (A) Isd (x In) Ii (x In)
Ir Isd Ii

Distribution Protection
Micrologic 5.2 A 25
30
35
40
45 Micrologic 5.3 A 5.3 A
LSI + Ammeter 20
15 60
50
Micrologic
6
4 8
225
3 10 200 250
2 12 175 300
1.5 15
Ii (x In) 150 350
125 400

Distribution Protection 4 5
6

Micrologic 5.2 E Micrologic 5.3 E 3 8


tr

LSI + Energy Monitoring 2


1.5
Ii (x In)
12
10 tsd

Ir Isd Ii

Distribution Protection
Micrologic 6.3 A
35

Micrologic 6.2 A 30 40 Ig tg
6.3 A
6.2E

25 45

LSIG + Ammeter 20
15
6
60
50 Micrologic
4 8 225
3 10 200 250
2 12 175 300 Ir tr Isd tsd Ii(xIn) Ig tg
1.5 15
Ii (x In) 150 350
125 400

Distribution Protection 4 5
6 tr

Micrologic 6.2 E Micrologic 6.3 E 3


2 10
8

LSIG + Energy Monitoring 1.5


Ii (x In)
12
tsd

Ir Isd Ii

Motor Circuit Protection Standard

M Energy Efficient
Energie Efficace
N/A
Magnetic Only Energia Eficiente

1.3 M
Micrologic

Motor Protection
N/A Micrologic 1.3M
Micrologic 1 M 3200
2800
36004000
4400
2400
4800
2000
Isd (A)

2.2 M
50
2.3M
Micrologic Micrologic
Ii=3750
163
155 172

Motor Protection 145


137
114
181
210
217

Micrologic 2.2 M FLA (A) Class.


Isd (x FLA) FLA Isd
Micrologic 2.3 M
Micrologic 2 M 250
230
270
290
310
210 330
190 348
FLA (A) Class. Isd (x FLA)
FLA Isd

56
05/2012 ™ © 2011–2012 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

Section 11—Wiring Diagrams

Unit-Mount Circuit Breakers


Power Micrologic™ Trip Unit1 Remote Operation

Upstream CB Vac (+)

06114460
Vac (+)
3P or 4P NSX cord

Z1
Z2
Z3
Z4
Z5
N LA LB LC
SDE 81
06114459

BPO BPF
+ -
HL

82 84

D2

C2

A4

A2

B4

B2
Z1

Z2
T1 MN MX
Q T2 auto
I 0 I
Z3
Z4

Z5
or manu
V

A1
L1
D1

C1
Vac (-)
manu SDE

Vac (-)

Motor Operator
3P + N
N LA LB LC NSX cord
Z1
Z2
Z3
Z4
Z5

06114461

Downstream CB
Vac (220/240 V)
+ -
HL

BSCM
Z1

Z2

B4

Q I V T1

T2
Z3
Z4
Z5

ENVT
Q
auto 0 I
manu
ENCT
A1

H2 T1
Vac
H1 T2

Schematic of the communicating motor operator .

Communicating Motor Operator


Continued on next page

136
05/2012 ™ © 2011–2012 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Wiring Diagrams

Unit-Mount Circuit Breakers (continued)


Indication Contacts

Open Closed Fault Fault Closed Open

102
104
134

124
32

22

12

82
84

92
94
34

24

14

WH
06114462

RD

YE
VT
OF3 OF2 OF1 SDE SD CAF2 CAF1 CAO1

WH
RD

GY
131
31

21

121

101
81

91
11

The diagram is shown with circuits de-energized, relays in normal position, and all devices open, connected, and charged.
Terminal connections shown as O must be connected by the customer.

Micrologic™ Trip Unit A or E Remote Operation


Communication MN Undervoltage Release
A/E H (WH), L(BL): data or
-(BK), +(RD): 24 Vdc power supply MX Shunt Release
ZSI (Zone Selective Interlocking) Motor Operator
Z1: ZSI OUT SOURCE A4 Opening Order
Z2: ZSI OUT A2 Closing Order
A/E Z3: ZSI IN SOURCE B4, A1 Power Supply to Motor Operator
Z4: ZSI IN ST (short time) L1 Manual Position (manu)
Z5: ZSI IN GF (ground fault) B2 Overcurrent Trip Switch Interlocking (mandatory for correct operation)
(Z3, Z4, and Z5 for L-frame circuit breaker only) BPO Opening Pushbutton
ENCT: External Neutral Current Transformer: BPF Closing Pushbutton
-Shielded cable with 1 twisted pair (T1, T2) Communicating Motor Operator
-Shielding earthed at CT end only
A/E Connection L = 12 in. (30 cm) max. B4, A1 Motor Operator Power Supply
-Maximum length of 33 ft (10 m) BSCM Breaker Status and Control Module
-Cable size of 22 AWG
-Recommended cable: Belden 9451SB or equivalent Indication Contacts

ENVT: External Neutral Voltage Tap for Connection OF2/OF1 Device ON/OFF Auxiliary Switches
E
to the Neutral using a 3P Circuit Breaker OF3 Device ON/OFF Auxiliary Switches (L-Frame)
SDE Overcurrent Trip Switch
Color Code for Auxiliary Wiring
(short-circuit, overload, ground fault, earth leakage)
RD: Red VI: Violet SD Alarm Switch
WH: White GY: Gray CAF2/CAF1 Early-Make Contact (rotary handle only)
YE: Yellow OR: Orange CAO1 Early-Break Contact (rotary handle only)
BK: Black BL: Blue
GN: Green

137
© 2011–2012 Schneider Electric ™ 05/2012
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Dimensions

PowerPact J-Frame Circuit Breakers

Figure 15: 150–250 A Bus Bar PowerPact J-Frame 3P Circuit Breaker


7.52 Ø .35
48996-022-01

[191,0] Ø .20
[5,1] [8,9]
6.22 (MOUNTING HOLE) (5/16-18 TERMINAL NUT)
[158,0] .37
1.30 [9,4]
1.38 1.38
[33,0] [35,0] .57
[35,0]
[14,4]
2.06
[52,4] 4.12
[104,7]

1.38 1.00 1.37 .35


[35,0] [25,5] [34,8] [8,9]
A .70
[17,7]
2.60 SECTION B-B
[66,1] SCALE 1:1
5.57
[141,5] Trip Unit Dim. “A” Dim. “B”
5.74 Thermal-Magnetic 1.76 3.44
[145,8] and MCP [44,7] [87,4] ISOMETRIC VIEW
SCALE 1:2
6.52 Micrologic 1.69 3.49
[165,5] Electronic Trip [44,0] [88,6]
B B
19.5°
17.9° ON
OFF .48
[12,2] .16
21.5° 1.05 [4,0]
TRIPPED [26,6]
SEE DETAIL A
.73
5.00
[18,6]
3.24 2.87 3.74 [127,0]
B [95,1]
[82,4] [72,9]
.99
[25,2]
4.25 1.91 in.
Dimensions: DETAIL A
[108,0] [48,5] [mm]
SCALE 1:1

Figure 16: 150–250 A Lug-Lug PowerPact J-Frame 3P Circuit Breaker


7.52 Ø .20
48996-014-01

[191,0] [5,1]
6.22 (MOUNTING HOLE)
[158,0]
1.30
[33,0] 1.38
1.38 [35,0]
[35,0]
2.06
[52,4] 4.12
[104,7]

1.38 .86
[35,0] 1.37
[21,9] [34,8]
A

2.60
[66,1] Trip Unit Dim. “A” Dim. “B”
5.57
Thermal-Magnetic 1.76 3.44
[141,5]
and MCP [44,7] [87,4]
5.74 Micrologic 1.69 3.49
[145,8] Electronic Trip [43,0] [88,6] ISOMETRIC VIEW
6.66 SCALE 1:2
[169,2]

17.9° 19.5°
OFF ON .16
.53
[13,4] [4,0]
21.5°
TRIPPED 1.06
[27,0]
SEE DETAIL A .73
5.00 [18,6]
[127,0]
B 3.24 2.87 3.24 3.74
[82,4] [72,9] [82,4] [95,1] .99
[25,2]
1.91 in.
4.25 [48,5] Dimensions: DETAIL A
[108,0] [mm] SCALE 1:1

149
© 2011–2012 Schneider Electric ™ 05/2012
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Trip Curves

Figure 60: J-Frame 150–250 A (JD, JG, JJ, and JL) Thermal-Magnetic Trip
MULTIPLES OF RATED CURRENT

100
1.5

10

15

20

30

40

50

60
70
80
90
.5

.6
.7
.8
.9
1

6
7
8
9
10000 10000
9000 9000
JD, JG, JJ, JL MOLDED CASE CIRCUIT BREAKERS
8000 8000 CHARACTERISTIC TRIP CURVE NO. 50-5
7000 7000
6000 6000
CIRCUIT BREAKER INFORMATION
5000 5000
Circuit Breaker Continuous Maximum Number
4000 4000 Prefix Ampere Rating AC Voltage of Poles

JD, JG, JJ, JL 150–250 600 2, 3


3000 3000
This curve is to be used for application and coordination purposes only. The
EZ-AMP overlay feature at the bottom of the page should be used during
2000 2000 coordination studies.
1500 1500
All time/current characteristic curve data is based on 40°C ambient cold start.
Terminations are made with conductors of appropriate length and ratings.

1000 1000
900 900
800 800
700 700
600 600

500 500

400 400

MAXIMUM SINGLE-POLE TRIP TIMES 300


300
AT 25°C BASED ON NEMA AB-4 2003

200 200

150 150

10000
1000

1500

2000

3000

4000

5000

6000
7000
8000
9000
150

200

300

400

500

600
700
800
900
100 100
90 90
80 80
70 70
60 60

50 50

40 40

30 30

20 20

15 15

10 10
9 9
8 8
7 7
6 6
TIME IN SECONDS

5 5

TIME IN SECONDS
4 4

3 3

2 2

1.5 1.5

1 1
.9 LIMITS LOW LIMITS HIGH .9
.8 SETTING SETTING .8
.7 .7
.6 .6

.5 .5

.4 .4

.3 .3

.2 .2

.15 .15

MAGNETIC TRIP
.1 ADJUSTMENT RANGE .1
.09 .09
.08 .08
.07 .07
.06 .06

.05 .05

.04 .04
MAXIMUM CLEARING TIME
(AT 50 Hz) (AT 60 Hz) .03
.03

.02 1 CYCLE .02

1 CYCLE (50 Hz)


.015 .015
(60 Hz)

.01 1/2 CYCLE .01


.009 .009
.008
1/2 CYCLE (50 Hz) .008
.007 (60 Hz) .007
.006 .006

.005 .005
1

1.5

6
7
8
9
10

8000
9000
10000
.5

.6
.7
.8
.9

15

20

30

40

50

60
70
80
90
100

150

200

300

400

500

600
700
800
900
1000

1500

2000

3000

4000

5000

6000
7000

TM
MULTIPLES OF RATED CURRENT
225

175
250
200
150

Curve No. 0050TC0405


June 2004
© 2004 Schneider Electric All Rights Reserved Drawing No. 48095-050-05

172
05/2012 ™ © 2011–2012 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Trip Curves

Figure 76: J-Frame UL Listed Current -Limiting Circuit Breaker

7+(50$/0$*1(7,&02/'('&$6(&,5&8,7%5($.(56
-² )5$0(Š&855(17/,0,7,1*&,5&8,7%5($.(56
-$)5$0($7$1'9‘
---/$1'-5³$
3($./(77+528*+&855(17OS
Ip
60000
*Based on maximum values obtained throughout the circuit breaker development and UL test programs.

50000

480 V 3Ø
40000

Maximum 600 V 3Ø
Maximum* Peak Let-Through Current (Amperes)

Available
Peak Current
at 15% Power Factor
30000
240 V 3Ø

20000

10000

9000

8000

7000

6000
5000

6000

7000

8000

9000

20000

30000

40000

50000

60000

70000

80000

90000

100000

150000

200000
10000

Availability (RMS Symmetrical Amperes)

'UDZLQJ1R
$SULO
‹6FKQHLGHU(OHFWULFDOOULJKWVUHVHUYHG 5HY

189
© 2011–2012 Schneider Electric ™ 05/2012
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Trip Curves

Figure 77: J-Frame UL Listed Current-Limiting Circuit Breaker

7+(50$/0$*1(7,&02/'('&$6(&,5&8,7%5($.(56
-² )5$0(Š&855(17/,0,7,1*&,5&8,7%5($.(56
-$)5$0($7$1'9‘
---/$1'-5³$
/(77+528*+&855(17OW
I 2t
2.0
*Based on maximum values obtained throughout the circuit breaker development and UL test programs.

600 V 3Ø
Maximum* Let-Through I2t (Amperes2 Seconds x 106)

480 V 3Ø

1.0

.9

.8

.7

240 V 3Ø
.6

.5

.4

.3

.2
5000

6000

7000

8000

9000

20000

30000

40000

50000

60000

70000

80000

90000

100000

150000

200000
10000

Availability (RMS Symmetrical Amperes)

'UDZLQJ1R
$SULO
‹6FKQHLGHU(OHFWULFDOOULJKWVUHVHUYHG 5HY

190
05/2012 ™ © 2011–2012 Schneider Electric
All Rights Reserved