Rated voltage 220-240V ~ 50/60Hz

Model Definition: Cooling capacity 1500 / 1650W @ 35℃ / 35℃


3500 3500
A I XB-015-000-031 Inside temp. Inside temp. Rated power Consumption 700 / 780W @ 35℃ / 35℃
35℃ 4 60Hz 35℃ 4 60Hz 3.0 / 3.4A @ 35℃ / 35℃
Rated current
031: Product ID 3000 25℃ 3 60Hz 3000 25℃ 3 60Hz
000: No heater 35℃ 2 50Hz 35℃ 2 50Hz EER 2.1 / 2.1
015: Cooling Capacity 1500W 25℃ 1 50Hz 25℃ 1 50Hz 3
2500 2500 Inner circulation air flow rate 500m /h
B: Refrigerant = R134a

Power Consumption( W)
Cooling Capacity( W)
X: 230VAC 50/60HZ Power Supply Display LED
I : Industry Application
2000 2000 Heater NA
A: Air Conditioner
Operating temperature range -15℃ ~ +55℃
1500 1500 Max. noise level 65dB(A) @ 1.0m away

4 4 IP55 - between external


IP protection level
1000 2 1000 3 and internal interface
3 2 Net weight 32Kg
1 1
500 500 Outer dimension 745x445x200 (mm,HxWxD)
445 Refrigerant type R134a
0 0 Certification CE
25 35 45 55 25 35 45 55
Outdoor type powder coating,
Surface treatment
standard color: RAL7035
Ambient temp. ( ℃) Ambient temp. ( ℃)
Lifetime 10 years

482
468
60 260 60

96
114
106

782
745

768
106
Ambient Air intake

114
Cold Air Supply
M5-PE

96
45 P/N: 733031 Ver. : A
200 Name:
1500W AC Air Con.
Ambient Side Inner Side Model:

Page 1 of 2 AIXB-015-000-031
Figure 1 - Installation tips if extra cowling needed by customer Figure 2 - Mounting interface with cabinet door Figure 3 - Wiring interface with customer circuit

Cowling

inner side of cabinet

1 2 3 4 5 6 7 8 9 10

450 - M5
22

11 12

96
Cold Air Supply

No. symbol Definition

114
1 T/R+ T/R+ port for RS485 communication
Shadow area : Cutout size of cabinet door
Ambient Air intake 2 T/R- T/R - port for RS485 communication

106
3 NC Normally Closed port for alarming signal output

768

750
4 COM Common Port for Alarming signal output

5 NO Normally open port for alarming signal output

106
6
CONTROL Control signal input : on / off dry switch type
7

114
8 / /

9 / /
Cowling
10 / /

96
11 L Pole : AC - L

12 N Pole : AC - N

Display explanation :
60 260 60 LED will show inner air temp. at normal working,
Separating plate to avoid

while also show alarming code when alarming triggered.


ambient air short cutting

468

Status bar : with indicator light

Keep lighting when do parameter setting


Keep blinking when unit carry out self testing process

Keep lighting under normal cooling operation

Blue dashed rectangle : Air conditioner projected dimension on door (782x482mm) Keep lighting under normal heating operation

Keep lighting when external cycle fan start working

Keep blinking for alarming triggered

P/N: 733031 Ver. : A


Note:
Name:
It is not recommended to add extra cowling
1500W AC Air Con.
While if customer insist on doing that ,please follow below rules: Model:
1. The louvers for ambient air intake and discharge must keep 70% above open area for having sufficient air flow
2. A separating plate must be added to avoid air short cut between intake & exhaust air
Page 2 of 2
AIXB-015-000-031