Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 29

Jumlah Fixture Unit

No. Lantai
WC UR LV FC
RUSUN CIPAYUNG
Lantai - 1 3 2 2 0
1 - Load per fixture unit 3 5 1 2
- Subtotal 9 10 2 0
Lantai - 2 11 0 11 0
2 - Load per fixture unit 3 5 1 2
- Subtotal 33 0 11 0
Lantai - 3 11 0 11 0
3 - Load per fixture unit 3 5 1 2
- Subtotal 33 0 11 0
Lantai - 4 11 0 11 0
4 - Load per fixture unit 3 5 1 2
- Subtotal 33 0 11 0
Lantai - 5 11 0 11 0
5 - Load per fixture unit 3 5 1 2
- Subtotal 33 0 11 0
Lantai - 6 10 0 10 0
6 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 7 10 0 10 0
7 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 8 10 0 10 0
8 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 9 10 0 10 0
9 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 10 10 0 10 0
10 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 11 10 0 10 0
11 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 12 10 0 10 0
12 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 13 10 0 10 0
13 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 14 10 0 10 0
14 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 15 10 0 10 0
15 - Load per fixture unit 3 5 1 2
- Subtotal 30 0 10 0
Lantai - 16 8 0 8 0
16 - Load per fixture unit 3 5 1 2
- Subtotal 24 0 8 0
Lantai - 17 8 0 8 0
17 - Load per fixture unit 3 5 1 2
- Subtotal 24 0 8 0

Jumlah Fixture Unit


No. Lantai
WC LV SH KS
RUSUN CIPAYUNG
KAMAR 74 1 1 1 1
1 - Load per fixture unit 3 1 2 2
- Subtotal 3 1 2 2
Lantai - 54 1 1 1 1
2 - Load per fixture unit 3 1 2 2
- Subtotal 3 1 2 2
ixture Unit Subtotal
Laju aliran dimensi pipa
Beban Fixture
SH KS (Lt/men) (mm)
Unit

0 0
2 2 21 52 25
0 0
11 11
2 2 88 152 40
22 22
11 11
2 2 88 152 40
22 22
11 11
2 2 88 152 40
22 22
11 11
2 2 88 152 40
22 22
10 10
2 2 80 150 40
20 20
10 10
2 2 80 150 40
20 20
10 10
2 2 80 150 40
20 20
10 10
2 2 80 150 40
20 20
10 10
2 2 80 150 40
20 20
10 10
2 2 80 150 40
20 20
10 10
2 2 80 150 40
20 20
10 10
2 2 80 150 40
20 20
10 10
2 2 80 150 40
20 20
10 10
2 2 80 150 40
20 20
8 8
2 2 64 146 40
16 16
8 8
2 2 64 146 40
16 16

2160

Subtotal
Beban Fixture
Unit

8
TOTAL
PEM
KAPA
TOTAL BEBAN ALAT PLAMBING 208
PEMAKAIAN SERENTAK 80% 166.4 225
KAPASITAS POMPA BOSSTER 2 X 113 Lt/men
Jumlah Fixture Unit
No. Lantai 2 - 17
WC LV

kamar 1 1

- Load per fixture unit 4 1

1 - Subtotal 4 1

total beban alat plumbing 64 16

diameter pipa tegak 80 mm 50 mm


Ukuran pipa Ukur
Unit alat
tegak air
plumbing yang
kotoran atau
dihubungkan
buangan (mm)
Jumlah Fixture Unit 32 40
FD KS Panjang
1 1 32 2 9
1 2 40 8 15 45
1 2 40 10 9 30
16 32 50 12 9 20
50 mm 65 mm 50 20 7 15
65 42 9
80 10 9
80 30
80 60
100 100
100 200
100 500
125 200
125 500
125 1100
150 350
150 620
150 960
150 1900
200 600
200 1400
200 2200
200 3600
250 1000
250 2500
250 3800
250 5600
Ukuran pipa cen yang disyaratkan

50 65 80 100 125 150 200


Panjang ukur maksimum pipa ven (m)

30 90
30 60 180
18 60 150
15 24 120
10 30 75 300
9 27 75 270
6 20 54 210
10 24 105
9 20 90
6 15 60
7 15 60 120 390
5 9 35 90 330
7 30 75 300
6 20 60 210
15 45 150 390
12 30 120 360
9 24 105 330
7 18 75 240
22 35 300
15 30 150
9 24 105
7 18 75