PACKAGED AIR CONDITIONER DATA SHEET E


V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80101-A, PAC-80102-B / ACCU-80101-A, ACCU-80102-B
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE ELEC. ROOM
5 LOCATION TECHNICAL SERVICE(LAB) BUILDING ELEC. ROOM
6 TYPE AIR COOLED, WALL MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 3.1
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80103-A / ACCU-80103-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE OFFICE
5 LOCATION TECHNICAL SERVICE(LAB) BUILDING OFFICE
6 TYPE AIR COOLED, CEILING MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 5.9
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80104-A / ACCU-80104-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE MEETING ROOM
5 LOCATION TECHNICAL SERVICE(LAB) BUILDING MEETING ROOM
6 TYPE AIR COOLED, CEILING MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 3.6
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80601-A / ACCU-80601-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE SAFETY INDUCTION ROOM
5 LOCATION GUARD HOUSE SAFETY INDUCTION ROOM
6 TYPE AIR COOLED, CEILING MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 4.8
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80602-A / ACCU-80602-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE GUARD ROOM
5 LOCATION GUARD HOUSE GUARD ROOM
6 TYPE AIR COOLED, CEILING MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 4.8
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80603-A / ACCU-80603-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE HALL
5 LOCATION GUARD HOUSE HALL
6 TYPE AIR COOLED, CEILING MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 1.3
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS

PAC-80301-A ~ PAC-80305-A, PAC-80306-B ~ PAC-80307-B /


1 ITEM NO (INDOOR / OUTDOOR)
ACCU-80301-A ~ ACCU-80305-A, ACCU-80306-B ~ ACCU-80307-B

2 QUANTITY 7 SETS 20% DUTY x 5SETS, 20% STAND-BY x 2SETS


3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE SWITCHGEAR ROOM
5 LOCATION SUBSTATION SWITCHGEAR ROOM
6 TYPE AIR COOLED, FLOOR MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 50.5
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 400/3/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80801-A, PAC-80802-B / ACCU-80801-A, ACCU-80802-B
2 QUANTITY 2 SETS 100% DUTY, 100% STAND-BY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE MCC PANEL ROOM
5 LOCATION DEHYDRATOR BUILDING MCC PANEL ROOM
6 TYPE AIR COOLED, FLOOR MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 20.0
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 400/3/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80803-A, PAC-80804-B / ACCU-80803-A, ACCU-80804-B
2 QUANTITY 2 SETS 100% DUTY, 100% STAND-BY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE INSTRUMENT ROOM
5 LOCATION DEHYDRATOR BUILDING INSTRUMENT ROOM
6 TYPE AIR COOLED, FLOOR MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 6.3
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80805-A / ACCU-80805-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE OFFICE
5 LOCATION DEHYDRATOR BUILDING OFFICE
6 TYPE AIR COOLED, CEILING MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 1.3
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80201-A / ACCU-80201-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE MAINTENANCE SHOP
5 LOCATION CONTROL BUILDING MAINTENANCE SHOP
6 TYPE AIR COOLED, FLOOR MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 12.1
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 400/3/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) above 34* / *
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
SIZE (W x D x H)
*x*x*
45 OTHERS Indoor Unit (mm)
*x*x*
OutDoor Unit
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE. MFR
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. ISOLATOR SWITCH FOR OUTDOOR UNIT SHALL BE


PROVIDED.
7. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.
- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
8. COMMISSIONING SPARE PART SHALL BE PROVIDED (FILTER
DRIER CORE, REFRIGERANT, ETC.)
9. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
10. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
11. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80202-A / ACCU-80202-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE OFFICE
5 LOCATION CONTROL BUILDING OFFICE
6 TYPE AIR COOLED, CEILING MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 1.6
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE. MFR
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. ISOLATOR SWITCH FOR OUTDOOR UNIT SHALL BE


PROVIDED.
7. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.
- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
8. COMMISSIONING SPARE PART SHALL BE PROVIDED (FILTER
DRIER CORE, REFRIGERANT, ETC.)
9. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
10. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
11. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-80203-A / ACCU-80203-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE REST ROOM
5 LOCATION CONTROL BUILDING REST ROOM
6 TYPE AIR COOLED, CEILING MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 1.6
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE. MFR
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. ISOLATOR SWITCH FOR OUTDOOR UNIT SHALL BE


PROVIDED.
7. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.
- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
8. COMMISSIONING SPARE PART SHALL BE PROVIDED (FILTER
DRIER CORE, REFRIGERANT, ETC.)
9. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
10. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
11. * ITEMS TO BE FILLED IN BY VENDOR
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


1 ITEM NO (INDOOR / OUTDOOR) PAC-85001-A / ACCU-85001-A
2 QUANTITY 1 SET 100% DUTY
3 SPECIAL REQUIREMENT LOW NOISE DESIGN
4 SERVICE OPERATOR ROOM
5 LOCATION TRUCK LOADING SHELTER OPERATOR ROOM
6 TYPE AIR COOLED, WALL MOUNTED
7 OUTSIDE DESIGN TEMPERATURE (℃) 34.0
8 DESIGN TOTAL POWER SUPPLY (kW) *
9 CONDITION MOUNTING TYPE SELF STANDING
10 POWER CONNECTION OUTDOOR UNIT
11 COOLING CAPACITY (kW) 2.8
12 FLOW RATE (CMH) *
13 REFRIGERANT R-407C OR EQUIVALENT
14 COOLING COIL PRESSURE DROP (kPa) *
15 AIR ENTERING TEMPERATURE (DB/ WB) (℃) */*
16 AIR LEAVING TEMPERATURE (DB/ WB) (℃) */*
25 AIR FLOW RATE (CMH) *
STATIC PRESSURE
26 (Pa) */*
(EXTERNAL/TOTAL)
FAN & MOTOR
27 ELECTRIC POWER (kW) *
28 ELECTRIC SERVICE (V/Φ/Hz) 230/1/50
29 MOTOR ENCLOSURE TEFC
30 TYPE OF COMPRESSOR SCROLL (INVERTER)
MAXIMUM AMBIENT
31 (℃) */*
TEMPERATURE (DB/WB)
32 APPROX PIPE LIFT (m) *
COMPRESSOR
33 COMPRESSOR POWER INPUT (kW) *
34 TYPE OF COMPRESSOR *
35 SAT. SUCTION TEMPERATURE (℃) *
36 APPROX PIPE RUN (m) *
41 MATERIAL (TUBE/FIN) COPPER / ALUMINUM
CONDENSERS AND
42 COIL FACE AREA (m2) *
FANS
43 FAN CAPACITY (CMH / Pa) */*
R
PACKAGED AIR CONDITIONER DATA SHEET E
V

PROJECT : NBL REV DATE PREP. BY CH'D BY AP'D BY.


JOB NO. : 190196 A 2021-07-16 WDI HSK SWN

DESIGN DATA

No. DESCRIPTION TECHNICAL REQUIREMENT REMARKS


44 VENDOR'S MODEL NUMBER *
45 OTHERS SIZE (W x D x H) (mm) *x*x*
46 NET/OPERATING WEIGHT (INDOOR/OUTDOOR) (kg) *
47 ATTACHED DRAWING BY VENDOR
1. OUTDOOR UNIT SHALL BE SUITABLE FOR THE CORROSIVE
ENVIRONMENT (COOLING TOWER, SEA SIDE).
48 NOTE.
- SPECIAL COATING SHOULD BE APPLIED.
- MANUFACTURER STANADRD

2. COMPRESSOR SHALL BE LOCATED IN THE OUTDOOR UNIT

3. EQUIPMENT SHALL BE SELF-CONTROLLED BY


TEMPERATURE IN THE UNIT.
4. BOTTOM SIDE DETAIL SHALL BE PROVIDED FOR SUPPORT
DESIGN

5. RUBBER PAD AND SUPPORT ANCHOR SHALL BE PROVIDED.

6. CONTROL SIGNAL SHALL BE PROVIDE AS BELOW.


- ENABLE / DISABLE
- RUNNING STATUS
- FAIL ALARM (POWER FAIL ALARM SHALL BE PROVIDED)
7. FLA (FULL LOAD AMPERE) TO BE MENTIONED ON VENDOR
PRINT.
8. MAIN POWER SUPPLY WILL BE SUPPLIED TO OUTDOOR
UNIT ONLY. INDOOR POWER CABLING FROM OUTDOOR UNIT
TO BE SCOPE OF VENDOR.
9. * ITEMS TO BE FILLED IN BY VENDOR