Professional Documents
Culture Documents
Module 2 Install Pipes and Fittings
Module 2 Install Pipes and Fittings
Learning Competencies:
2.1. Install pipes and fittings for branches based on job specifications
following the Revised National Plumbing Code of the Philippines
(RNPCP)
and venting requirements and procedures;
2.2. Align drainage, sewer, and vent piping systems in the required locations
Multiple Choice: Write your answer on the space before each number. Write
only the letter of your answer.
_____ 1. A pipe which receives the discharge of any fixture except water
closet and conveys the same to the house drain.
a. Waste pipe d. Drainage pipe
b. Soil pipe e. Vent pipe
c. PVC pipe
_____ 3. The most common and practical shape of trap manufactured in the
form of a P.
a. Common seal trap d. Water seal trap
b. Deep seal trap e. rat trap
c. P-trap
_____ 5. Sometimes referred to as back vent. It is the portion of the vent pipe
which serves as single trap.
a. Main vent d. wet vent
b. Relief vent e. individual vent
c. Stock vent
DRAIN-WASTE-VENT SYSTEM
WASTE PIPE
A waste pipe is any pipe, which receives the discharge of any fixture
except water closet and conveys the same to the soil pipe, soil, branch or
Manner of Joints
Injudicious connection of fittings should not be permitted in plumbing
installation.
Waste Pipe and other fixtures. Waste pipe is classified into two types
depending upon the fixture it serves, namely; direct waste and Indirect
waste
SOIL PIPE
Any pipe which receives and conveys the drainage of water closets,
with or without the discharges from other fixtures to the house drain, is
referred to as soil pipe.
Branch Drains
Branch drains serve two or more fixtures or stacks within a storey.
Branch drains may connect to another branch, building drain, sewage
sump, wet vent or stack.
Use table 4.10.6B to size each portion of the branch as the load is
applied.
May never be smaller than the drain pipe connecting to branch.
Branches downstream of the third water closet must be 4 inches.
BRANCH DRAINS
BRANCH
Prohibited Fittings. “No double hub, double Tee or double Wyes branch
should be used on soil, nor horizontal lines. The drilling and tapping of
house
drains, soil, waste or vent pipes and the use of saddle hubs and bends are
prohibited.”
Grade and Change of Direction. The storm drain slope should not be less
than 2% or 20mm per meter length of the pipe. A combination of Y-fitting
and 1/8 bend or a long radius fitting should be used in any change of
directions.
Types of Trap
There are various forms of water sealed traps which could be used
depending upon the kind of fixture it is to serve. The Permissible Traps and
the Objectionable Traps will be presented for purpose of identification.
a) Common Seal Trap has a depth of 50mm between the overflow and
the dip.
b) Deep Seal Trap has a depth of 75 to 100mm between the overflow
and the dip.
Characteristics:
Performance:
Disadvantages:
Other Features: Drum Trap can also serve as terminal for soda fountains,
bar wastes and wastes and any type of indirect wastes.
Water Seal. Each fixture trap should have a water seal of not less
than 50mm and not more than 100mm.
P-TAP
This P trap has a 1-½ inch water
seal to keep sewer gases from
entering the building from the
drainage system.
A drainage / venting system is
designed to prevent positive or
negative pressures above one inch
of water column.
The P trap connects to a
horizontal trap arm.
Acid waste requires 2” water seal
The code limits the use or
prohibits the use of certain traps
Trap Clean Out. Each trap, except those in combination with fixtures in
which the trap is plainly visible and accessible should be provided with an
accessible ample size trap screw.
2. Grease Trap
Is sometimes used in residential kitchen sink although there
installation is not so necessary under normal condition when no large
amount of grease or oil is being discharged into the plumbing system.
However, where a large percentage of grease is being discharged by the
kitchen sinks as in the restaurants, clubhouses, hotels or similar places
grease trap is essential to prevent stoppage in the plumbing system caused
by grease contained in the waste discharges.
Plumbing Kto12 – Technology & Livelihood Education
Page 16 |
The grease trap should be installed as close as practical to the fixture
from which it receives the discharges and should have a leak proof cover
that is removable to permit its cleaning.
Main function of the vent pipes. The vent pipes among others, functions
as follows:
Trap Seal. This is the vertical distance between the dip and the crown weir
of the trap. Also it is the water in the trap
between the dip and the crown weir.
When a large amount of water flow rapidly through the trap, self-siphoning
is automatically developed and the water content of the trap (seal) is
absolutely discharged. This is known as trap seal loss. When the seal is lost,
Back Pressure. This condition is caused by the plus pressure which blows
the water out of the fixture. It happens usually when a large flow of water
drop and form as slug and compress the air inside the pipe. The compressed
air will find its way out through the weaker point. The trap seal will give way
and blow out of the fixture.
Deterioration of the Pipe. The destructive effects of waste and acid forming
chemical elements inside the drainage
system are minimized when the system is
adequately ventilated.
The ventilation pipes intended to protect the trap seal against siphonage
or back pressure are classified as Individual or Back Vent which sometimes
is called Unit Vent, Circuit or Loop Vent, and Wet Vent.
The main soil and waste vent is that portion of the soil pipe stack
above the highest installed fixture branch extended through the roof. It
serves as the terminal for the main vent and other vents of the plumbing
installations.
Stock. This is a general term for any vertical line of the soil waste or vent
piping.
Provisions
Main Vent
The main vent is that portion of the vent pipe system which serves as
a terminal of the smallest forms of units and grouped fixture trap
ventilation. The main vent is connected full size at their base to the main
soil or waste pipe at or below the lowest fixture branch and should extend
undiminished in size above the roof or should be reconnected with the main
soil vent at least 1 meter above the highest fixture branch. The main vent
also serves as a relief vent for any back pressure. It must be free from offsets
to allow free movement of air.
“The Building Code provides that “No water closets should discharge
into a drain less than 75 mm diameter and no main house sewer
receiving discharges from water closets should be less than 100 mm
pipe diameter.”
“Not more than 2 water closets should discharge into a 75 mm
diameter pipe.”
Individual Vent
Nominally vertical
2” or 4” trap
1 ¼” or 1 ½” vent
Minimum Permitted Size of Vent Pipe Based on the Size of the Trap Served
1 1/4 1 1/4
1 1/2 1 1/4
2 1 1/2
2 1/2 1 1/2
3 1 1/2
4 1 1/2
5 2
6 2
Distance of Vent from Trap Seal. No trap should be placed more than 1.50
meters horizontal developed length from its vent. The distance should be
Plumbing Kto12 – Technology & Livelihood Education
Page 23 |
measured along the central line of the waste or soil pipe from the vertical
inlet or the trap to the vent opening. The vent opening from the soil or waste
pipe except for water closets and similar fixtures should not be the dip of
the trap.
Unit Vents
This is that portion of the vent pipe which ventilates to fixture traps.
The principle and design is similar to that of the back vent. This type is
installed usually an apartment and hotel toilet rooms wherein the design of
fixtures are arranged back for economic consideration.
Vents not required. When bathrooms or water closets or other fixtures are
located on opposite sides of a wall or partition or directly adjacent to each
other within the prescribed distance, such fixtures may have a common soil
or waste pipe and common vent.
Size of Vent Pipes. The size of the vent pipe is determined by
considering the following:
1. The velocity of a large volume flow of water requires greater quantity of air moving
at a high velocity to maintain balanced atmospheric pressure inside the pipe.
2. Tall buildings have a higher velocity of water flow, hence, requires an ample size
of vent pipes.
3. Long rows of vent reduces the volume of air flow due to the friction between the
air and the interior surface of the pipes.
B. Foot Protection
Safety shoes with impact protection are used in
work areas where heavy objects or tools could be
accidentally dropped on the feet. Safety shoes
with puncture protection are required when
C. Hand Protection
Gloves are required to protect the hands of
workers from cuts, scrapes, punctures, burns,
chemical absorption, and exhaust temperatures.
It is crucial that the type of glove being used is
the right one for the job.
D. Hearing Protection
Appropriate ear muffs or ear plugs must be made
available as a last resort if it is not possible to make the
workplace less noisy. The requirement is a small part of
the occupational noise exposure standard which requires
employers to ensure that workers are exposed to less than
90 decibels of noise over an 8 hour period.
E. Respirators
Appropriate respirators must be worn as a last resort if
it is not
possible
to
ventilate
the work area properly.
2.
4.
3.
5.
Performance Task
Direction: Group yourselves into five groups. You are going to perform how
to perform/Install Pipes and Fittings (Drain Waste Vent) in a Single
Plumbing Unit System and in accordance with the job requirements,
specification of tools and measurements and Proper Safety Procedures.
Materials:
PVC Pipes
PVC Fittings
PVC Cement Solvent
Rags
Sand Paper
PPE
Hard hat
Safety Googles
Safety Gloves
Face Mask
Face Shield
Ear Muff
Evaluation:
Self-check:
Direction: Identify the following statement according to its uses. Write your
answer on the blank given before the number.
References