Project : Show Village- Experience and Sales Centre Job ref.
Part of structure Ventilation (Outdoor/Extract) Air Calculations 5218217
PC file ref. Calc. by GCB Checked by SFP Date 26/08/2023 MEC-CALC-001/ 0 Outside Air Based on ASHRAE 62.1-2022 Exhaust Air Based on ASHRAE 62.1-2022 Alternate Approach Actual No. of Alternate Occupants Total Outside Air Total Outside Air Approach for from Arch. Default Values based on Actual based on Default Outdoor Outdoor Plans, People Area Demand Occupancy Occupancy Zone Air Airflow Airflow Over-ride Total Exhaust Space names as per Total Area, A Height, N1 Occupancy Category as Outdoor Air Outdoor Outdoor Airflow Control Occupancy Category as Air Changes Total (Max. with rounded Sr.No. Spce Name/Tag Distribution Manual Used, Served By Nature of use / Exhaust Rate Exhaust Rate Total Exhaust ASHRAE Served By Remarks Load calculation 2 (m ) H (m) (If this is not defined by ASHRAE Rate Air Rate Rp x N1 + Ra x Voz or Vot Ventilation defined by ASHRAE No. of Units Per hour Exhaust up value) Number of effectiveness overriding for Air Vot operation Value? known Standard 62.1 Rp Ra Occupant A Required? Standard 62.1 Occupants V x N2 Balancing ASHRAE Density (N2 to be used if Based on purpose default values N1 is zero) are used) ASHRAE, N2 L/s*person l/s.m² # / 100 m² l/s l/s Ez l/s l/s l/s L/s*unit L/s*m² l/s No. l/s l/s
SHOW VILLAGE-EXPERIENCE AND SALES CENTRE
Exhaust conisdered 50% of provided 1 GF-MEETING ROOM Main Meeting room 16.0 3.0 10 Conference / Meeting 2.5 0.3 50.0 8 29.8 24.8 1.0 29.8 30 No OA-AHU-SC-MZ-01 15.0 No 15.0 OA-AHU-SC-MZ-01 fresh air GF - CO-WORKING Exhaust conisdered 50% of provided 2 Co working space 38.0 3.0 12 Office Space 2.5 0.3 5.0 2 41.4 17.0 1.0 41.4 45 No OA-AHU-SC-MZ-01 22.5 No 25.0 OA-AHU-SC-MZ-01 SPACE fresh air Exhaust conisdered 50% of provided 3 MEETING ROOM-01 Meeting Room-1 9.0 3.0 4 Conference / Meeting 2.5 0.3 50.0 5 12.7 15.5 1.0 12.7 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01 fresh air Exhaust conisdered 50% of provided 4 MEETING ROOM-02 Meeting Room-2 9.0 3.0 3 Conference / Meeting 2.5 0.3 50.0 5 10.2 15.5 1.0 10.2 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01 fresh air Exhaust conisdered 50% of provided 5 MEETING ROOM-03 Meeting Room-3 9.0 3.0 3 Conference / Meeting 2.5 0.3 50.0 5 10.2 15.5 1.0 10.2 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01 fresh air Exhaust conisdered 50% of provided 6 MANAGER ROOM-01 Manager Room-01 10.0 3.0 3 Office Space 2.5 0.3 5.0 1 10.5 8.5 1.0 10.5 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01 fresh air Exhaust conisdered 50% of provided 7 MANAGER ROOM-02 Manager Room-02 10.0 3.0 3 Office Space 2.5 0.3 5.0 1 10.5 8.5 1.0 10.5 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01 fresh air GF - MALE PRAYER 8 Prayer Room-Male 10.0 3.0 6 Places of religious worship 2.5 0.3 120.0 12 18.0 33.6 1.0 18.0 20 No OA-AHU-SC-MZ-01 No OA-AHU-SC-MZ-01 ROOM Heavy Use / Exhaust requirment will be 9 GF - ABLUTION - 01 Prayer Room-male Ablution 7.0 3.0 No OA-AHU-SC-MZ-01 All other locker rooms 1 15.0 1.5 10.5 No 15.0 OA-AHU-SC-MZ-01 Intermi. Oper. compensated from male prayer room GF - FEMALE PRAYER 10 Prayer Room-Female 10.0 3.0 6 Places of religious worship 2.5 0.3 120.0 12 18.0 33.6 1.0 18.0 20 No OA-AHU-SC-MZ-01 No OA-AHU-SC-MZ-01 ROOM Heavy Use / Exhaust requirment will be 11 GF - ABLUTION - 02 Prayer Room-Female Ablution 7.0 3.0 No OA-AHU-SC-MZ-01 All other locker rooms 1 15.0 1.5 10.5 No 15.0 OA-AHU-SC-MZ-01 Intermi. Oper. compensated from female prayer room Exhaust conisdered 50% of provided 12 Majlis-01 23.0 5.0 6 Multi-Purpose Assembly 2.5 0.3 120.0 28 21.9 78.4 1.0 21.9 25 No OA-AHU-SC-MZ-01 12.5 No 15.0 OA-AHU-SC-MZ-01 fresh air Exhaust conisdered 50% of provided 13 GF - OPEN DESK Majlis-01 23.0 5.0 6 Multi-Purpose Assembly 2.5 0.3 120.0 28 21.9 78.4 1.0 21.9 25 No OA-AHU-SC-MZ-01 12.5 No 15.0 OA-AHU-SC-MZ-01 fresh air Exhaust conisdered 50% of provided 14 Sales Office Space 67.0 5.0 5 Office Space 2.5 0.3 5.0 4 32.6 34.0 1.0 32.6 35 No OA-AHU-SC-MZ-01 17.5 No 20.0 OA-AHU-SC-MZ-01 fresh air Exhaust conisdered 50% of provided 15 GF Lounge 95.0 3.0 15 Multi-Purpose Assembly 2.5 0.3 120.0 114 66.0 319.2 1.0 66.0 66.0 70 No OA-AHU-SC-MZ-01 30.0 No 30.0 OA-AHU-SC-MZ-01 GF - CAFÉ AND LIFT fresh air LOBBY Space is maintained negative with 16 Feature Café 26.0 4.0 7 Coffee Station 2.5 0.3 20.0 6 25.3 24.0 1.0 25.3 30 No OA-AHU-SC-MZ-01 Kitchenettes 1.5 39.0 No 40.0 EF-SC-MZ-01 respect to Lounge area Fresh air compensating the toilet 17 GF - CORRIDOR - 01 GF_Toilet corridor 15.0 3.0 Corridors 0.0 0.3 0.0 0 4.5 4.5 1.0 4.5 220.0 220 No OA-AHU-SC-MZ-01 220.0 OA-AHU-SC-MZ-01 exhaust is added to corridor area Heavy Use / space will have fresh air compensating 18 GF - MALE TOILET Male Toilet 15.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 3 25.0 75.0 No 75.0 OA-AHU-SC-MZ-01 Intermi. Oper. air from the corridor Heavy Use / space will have fresh air compensating 19 GF - FEMALE TOILET Female Toilet 15.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 3 25.0 75.0 No 75.0 OA-AHU-SC-MZ-01 Intermi. Oper. air from the corridor Heavy Use / Fresh air will be compensated from 20 GF - ASST. TOILET Asst Toilet 7.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 1 25.0 25.0 No 25.0 OA-AHU-SC-MZ-01 Intermi. Oper. main hall Janitor closets, trash Heavy Use / Fresh air will be compensated from 21 GF - JANITORS Room Janitor room 5.0 3.0 No OA-AHU-SC-MZ-01 5.0 25.0 No 25.0 OA-AHU-SC-MZ-01 rooms, recycling Intermi. Oper. main hall Janitor closets, trash Heavy Use / space will have fresh air compensating 22 GF - WASTE ROOM Waste room 7.0 3.0 No OA-AHU-SC-MZ-01 5.0 35.0 10.0 70.0 No 70.0 EF-SC-MZ-02 rooms, recycling Intermi. Oper. air from the corridor space will have fresh air compensating 23 GF - PANTRY Pantry 5.0 4.0 No OA-AHU-SC-MZ-01 Kitchenettes 1.5 7.5 No 10.0 OA-AHU-SC-MZ-01 air from the coworking space CENTRAL MODEL Exhaust conisdered 30% of provided 24 SPACE SPACES -2 Central Model Space Part-2 300.0 4.5 40 Multi-Purpose Assembly 2.5 0.3 120.0 360 190.0 1008.0 1.0 190.0 240.0 240 No OA-AHU-SC-MZ-01 48.0 No 50.0 OA-AHU-SC-MZ-01 fresh air AND CORRDOR 02 FF - PRIVATE MEETING 25 1st VIP office 1 16.0 4.0 5 Office Space 2.5 0.3 5.0 1 17.3 8.5 1.0 17.3 20 No OA-AHU-SC-MZ-01 No 0.0 OA-AHU-SC-MZ-01 - 01 FF - PRIVATE MEETING 26 1st VIP office 2 16.0 4.0 5 Office Space 2.5 0.3 5.0 1 17.3 8.5 1.0 17.3 20 No OA-AHU-SC-MZ-01 No 0.0 OA-AHU-SC-MZ-01 - 02 Exhaust conisdered 50% of provided 27 FF - VIP LOUNGE 1st VIP Area 45.0 4.0 9 Multi-Purpose Assembly 2.5 0.3 120.0 54 36.0 151.2 1.0 36.0 40 No OA-AHU-SC-MZ-01 20.0 No 20.0 OA-AHU-SC-MZ-01 fresh air GF - EXHIBITION SPACE AND CENTRAL Exhaust conisdered 30% of provided 28 Exhibition and Central Model part-01 330.0 4.5 60 Multi-Purpose Assembly 2.5 0.3 120.0 396 249.0 1108.8 1.0 249.0 359.0 360 No OA-AHU-SC-MZ-01 72.0 No 75.0 OA-AHU-SC-MZ-01 MODEL SPACE fresh air SPACES -1 Heavy Use / Fresh air will be compensated from 29 GF - TOILET - 01 Male Toilet 5.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 1 25.0 25.0 No 25.0 OA-AHU-SC-MZ-01 Intermi. Oper. main hall Heavy Use / Fresh air will be compensated from 30 GF - TOILET - 02 Female Toilet 5.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 1 25.0 25.0 No 25.0 OA-AHU-SC-MZ-01 Intermi. Oper. main hall 31 GF - STORE - 02 Store 15.0 3.0 Corridors 0.0 0.3 0.0 0 4.5 4.5 1.0 4.5 No OA-AHU-SC-MZ-01 10.0 No 10.0 OA-AHU-SC-MZ-01 GF - SECURITY 32 EQUIPMENT ROOM Security Equipment Room 21.0 3.0 Corridors 0.0 0.3 0.0 0 6.3 6.3 1.0 6.3 10 No OA-AHU-SC-MZ-01 OA-AHU-SC-MZ-01 AND ICT ROOM GF - ELECTRICAL 33 Electrical Room 21.0 3.0 Corridors 0.0 0.3 0.0 0 6.3 6.3 1.0 6.3 10 No OA-AHU-SC-MZ-01 OA-AHU-SC-MZ-01 ROOM 34 GF - MTR ROOM MTR 8.0 3.0 Corridors 0.0 0.3 0.0 0 2.4 2.4 1.0 2.4 10 No OA-AHU-SC-MZ-01 OA-AHU-SC-MZ-01 GF - SECURITY 35 Security Control Room 10.0 3.0 1 Office Space 2.5 0.3 5.0 1 5.5 8.5 1.0 5.5 10 No OA-AHU-SC-MZ-01 OA-AHU-SC-MZ-01 CONTROL ROOM Soiled laundry storage Fresh air will be compensated from 36 GF - UPS ROOM UPS Room 12.0 3.0 Corridors 0.0 0.3 0.0 0 3.6 3.6 1.0 3.6 No OA-AHU-SC-MZ-01 5.0 60.0 No 60.0 EF-SC-MZ-03 rooms main hall Total 1242 m² 122 209 1315.0 l/s 0.0 l/s 1.1 l/s/m² 1005.0 l/s 0.8 l/s/m² 130.85%
AHU TAG OA AIR FLOW EA AIR FLOW PERCENT OF EA Remarks
OA-AHU-SC-MZ-01 1315.0 L/s OA 835.0 L/s EA 63.5% EA of OA FAHU on Mezzanine level