Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Project : Show Village- Experience and Sales Centre Job ref.

Part of structure Ventilation (Outdoor/Extract) Air Calculations 5218217


PC file ref.
Calc. by GCB Checked by SFP Date 26/08/2023 MEC-CALC-001/ 0
Outside Air Based on ASHRAE 62.1-2022 Exhaust Air Based on ASHRAE 62.1-2022 Alternate Approach
Actual No. of Alternate
Occupants Total Outside Air Total Outside Air Approach for
from Arch. Default Values based on Actual based on Default Outdoor
Outdoor
Plans, People Area Demand
Occupancy Occupancy Zone Air Airflow Airflow Over-ride Total Exhaust
Space names as per Total Area, A Height, N1 Occupancy Category as Outdoor Air Outdoor Outdoor Airflow Control Occupancy Category as Air Changes Total (Max. with rounded
Sr.No. Spce Name/Tag Distribution Manual Used, Served By Nature of use / Exhaust Rate Exhaust Rate Total Exhaust ASHRAE Served By Remarks
Load calculation 2
(m ) H (m) (If this is not defined by ASHRAE Rate Air Rate Rp x N1 + Ra x
Voz or Vot Ventilation defined by ASHRAE No. of Units Per hour Exhaust up value)
Number of effectiveness overriding for Air Vot operation Value?
known Standard 62.1 Rp Ra Occupant A Required? Standard 62.1
Occupants V x N2 Balancing
ASHRAE Density (N2 to be used if
Based on purpose
default values N1 is zero)
are used) ASHRAE, N2
L/s*person l/s.m² # / 100 m² l/s l/s Ez l/s l/s l/s L/s*unit L/s*m² l/s No. l/s l/s

SHOW VILLAGE-EXPERIENCE AND SALES CENTRE


Exhaust conisdered 50% of provided
1 GF-MEETING ROOM Main Meeting room 16.0 3.0 10 Conference / Meeting 2.5 0.3 50.0 8 29.8 24.8 1.0 29.8 30 No OA-AHU-SC-MZ-01 15.0 No 15.0 OA-AHU-SC-MZ-01
fresh air
GF - CO-WORKING Exhaust conisdered 50% of provided
2 Co working space 38.0 3.0 12 Office Space 2.5 0.3 5.0 2 41.4 17.0 1.0 41.4 45 No OA-AHU-SC-MZ-01 22.5 No 25.0 OA-AHU-SC-MZ-01
SPACE fresh air
Exhaust conisdered 50% of provided
3 MEETING ROOM-01 Meeting Room-1 9.0 3.0 4 Conference / Meeting 2.5 0.3 50.0 5 12.7 15.5 1.0 12.7 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01
fresh air
Exhaust conisdered 50% of provided
4 MEETING ROOM-02 Meeting Room-2 9.0 3.0 3 Conference / Meeting 2.5 0.3 50.0 5 10.2 15.5 1.0 10.2 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01
fresh air
Exhaust conisdered 50% of provided
5 MEETING ROOM-03 Meeting Room-3 9.0 3.0 3 Conference / Meeting 2.5 0.3 50.0 5 10.2 15.5 1.0 10.2 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01
fresh air
Exhaust conisdered 50% of provided
6 MANAGER ROOM-01 Manager Room-01 10.0 3.0 3 Office Space 2.5 0.3 5.0 1 10.5 8.5 1.0 10.5 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01
fresh air
Exhaust conisdered 50% of provided
7 MANAGER ROOM-02 Manager Room-02 10.0 3.0 3 Office Space 2.5 0.3 5.0 1 10.5 8.5 1.0 10.5 15 No OA-AHU-SC-MZ-01 7.5 No 10.0 OA-AHU-SC-MZ-01
fresh air
GF - MALE PRAYER
8 Prayer Room-Male 10.0 3.0 6 Places of religious worship 2.5 0.3 120.0 12 18.0 33.6 1.0 18.0 20 No OA-AHU-SC-MZ-01 No OA-AHU-SC-MZ-01
ROOM
Heavy Use / Exhaust requirment will be
9 GF - ABLUTION - 01 Prayer Room-male Ablution 7.0 3.0 No OA-AHU-SC-MZ-01 All other locker rooms 1 15.0 1.5 10.5 No 15.0 OA-AHU-SC-MZ-01
Intermi. Oper. compensated from male prayer room
GF - FEMALE PRAYER
10 Prayer Room-Female 10.0 3.0 6 Places of religious worship 2.5 0.3 120.0 12 18.0 33.6 1.0 18.0 20 No OA-AHU-SC-MZ-01 No OA-AHU-SC-MZ-01
ROOM
Heavy Use / Exhaust requirment will be
11 GF - ABLUTION - 02 Prayer Room-Female Ablution 7.0 3.0 No OA-AHU-SC-MZ-01 All other locker rooms 1 15.0 1.5 10.5 No 15.0 OA-AHU-SC-MZ-01
Intermi. Oper. compensated from female prayer room
Exhaust conisdered 50% of provided
12 Majlis-01 23.0 5.0 6 Multi-Purpose Assembly 2.5 0.3 120.0 28 21.9 78.4 1.0 21.9 25 No OA-AHU-SC-MZ-01 12.5 No 15.0 OA-AHU-SC-MZ-01
fresh air
Exhaust conisdered 50% of provided
13 GF - OPEN DESK Majlis-01 23.0 5.0 6 Multi-Purpose Assembly 2.5 0.3 120.0 28 21.9 78.4 1.0 21.9 25 No OA-AHU-SC-MZ-01 12.5 No 15.0 OA-AHU-SC-MZ-01
fresh air
Exhaust conisdered 50% of provided
14 Sales Office Space 67.0 5.0 5 Office Space 2.5 0.3 5.0 4 32.6 34.0 1.0 32.6 35 No OA-AHU-SC-MZ-01 17.5 No 20.0 OA-AHU-SC-MZ-01
fresh air
Exhaust conisdered 50% of provided
15 GF Lounge 95.0 3.0 15 Multi-Purpose Assembly 2.5 0.3 120.0 114 66.0 319.2 1.0 66.0 66.0 70 No OA-AHU-SC-MZ-01 30.0 No 30.0 OA-AHU-SC-MZ-01
GF - CAFÉ AND LIFT fresh air
LOBBY Space is maintained negative with
16 Feature Café 26.0 4.0 7 Coffee Station 2.5 0.3 20.0 6 25.3 24.0 1.0 25.3 30 No OA-AHU-SC-MZ-01 Kitchenettes 1.5 39.0 No 40.0 EF-SC-MZ-01
respect to Lounge area
Fresh air compensating the toilet
17 GF - CORRIDOR - 01 GF_Toilet corridor 15.0 3.0 Corridors 0.0 0.3 0.0 0 4.5 4.5 1.0 4.5 220.0 220 No OA-AHU-SC-MZ-01 220.0 OA-AHU-SC-MZ-01
exhaust is added to corridor area
Heavy Use / space will have fresh air compensating
18 GF - MALE TOILET Male Toilet 15.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 3 25.0 75.0 No 75.0 OA-AHU-SC-MZ-01
Intermi. Oper. air from the corridor
Heavy Use / space will have fresh air compensating
19 GF - FEMALE TOILET Female Toilet 15.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 3 25.0 75.0 No 75.0 OA-AHU-SC-MZ-01
Intermi. Oper. air from the corridor
Heavy Use / Fresh air will be compensated from
20 GF - ASST. TOILET Asst Toilet 7.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 1 25.0 25.0 No 25.0 OA-AHU-SC-MZ-01
Intermi. Oper. main hall
Janitor closets, trash Heavy Use / Fresh air will be compensated from
21 GF - JANITORS Room Janitor room 5.0 3.0 No OA-AHU-SC-MZ-01 5.0 25.0 No 25.0 OA-AHU-SC-MZ-01
rooms, recycling Intermi. Oper. main hall
Janitor closets, trash Heavy Use / space will have fresh air compensating
22 GF - WASTE ROOM Waste room 7.0 3.0 No OA-AHU-SC-MZ-01 5.0 35.0 10.0 70.0 No 70.0 EF-SC-MZ-02
rooms, recycling Intermi. Oper. air from the corridor
space will have fresh air compensating
23 GF - PANTRY Pantry 5.0 4.0 No OA-AHU-SC-MZ-01 Kitchenettes 1.5 7.5 No 10.0 OA-AHU-SC-MZ-01
air from the coworking space
CENTRAL MODEL
Exhaust conisdered 30% of provided
24 SPACE SPACES -2 Central Model Space Part-2 300.0 4.5 40 Multi-Purpose Assembly 2.5 0.3 120.0 360 190.0 1008.0 1.0 190.0 240.0 240 No OA-AHU-SC-MZ-01 48.0 No 50.0 OA-AHU-SC-MZ-01
fresh air
AND CORRDOR 02
FF - PRIVATE MEETING
25 1st VIP office 1 16.0 4.0 5 Office Space 2.5 0.3 5.0 1 17.3 8.5 1.0 17.3 20 No OA-AHU-SC-MZ-01 No 0.0 OA-AHU-SC-MZ-01
- 01
FF - PRIVATE MEETING
26 1st VIP office 2 16.0 4.0 5 Office Space 2.5 0.3 5.0 1 17.3 8.5 1.0 17.3 20 No OA-AHU-SC-MZ-01 No 0.0 OA-AHU-SC-MZ-01
- 02
Exhaust conisdered 50% of provided
27 FF - VIP LOUNGE 1st VIP Area 45.0 4.0 9 Multi-Purpose Assembly 2.5 0.3 120.0 54 36.0 151.2 1.0 36.0 40 No OA-AHU-SC-MZ-01 20.0 No 20.0 OA-AHU-SC-MZ-01
fresh air
GF - EXHIBITION
SPACE AND CENTRAL Exhaust conisdered 30% of provided
28 Exhibition and Central Model part-01 330.0 4.5 60 Multi-Purpose Assembly 2.5 0.3 120.0 396 249.0 1108.8 1.0 249.0 359.0 360 No OA-AHU-SC-MZ-01 72.0 No 75.0 OA-AHU-SC-MZ-01
MODEL SPACE fresh air
SPACES -1
Heavy Use / Fresh air will be compensated from
29 GF - TOILET - 01 Male Toilet 5.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 1 25.0 25.0 No 25.0 OA-AHU-SC-MZ-01
Intermi. Oper. main hall
Heavy Use / Fresh air will be compensated from
30 GF - TOILET - 02 Female Toilet 5.0 3.0 No OA-AHU-SC-MZ-01 Toilets - public 1 25.0 25.0 No 25.0 OA-AHU-SC-MZ-01
Intermi. Oper. main hall
31 GF - STORE - 02 Store 15.0 3.0 Corridors 0.0 0.3 0.0 0 4.5 4.5 1.0 4.5 No OA-AHU-SC-MZ-01 10.0 No 10.0 OA-AHU-SC-MZ-01
GF - SECURITY
32 EQUIPMENT ROOM Security Equipment Room 21.0 3.0 Corridors 0.0 0.3 0.0 0 6.3 6.3 1.0 6.3 10 No OA-AHU-SC-MZ-01 OA-AHU-SC-MZ-01
AND ICT ROOM
GF - ELECTRICAL
33 Electrical Room 21.0 3.0 Corridors 0.0 0.3 0.0 0 6.3 6.3 1.0 6.3 10 No OA-AHU-SC-MZ-01 OA-AHU-SC-MZ-01
ROOM
34 GF - MTR ROOM MTR 8.0 3.0 Corridors 0.0 0.3 0.0 0 2.4 2.4 1.0 2.4 10 No OA-AHU-SC-MZ-01 OA-AHU-SC-MZ-01
GF - SECURITY
35 Security Control Room 10.0 3.0 1 Office Space 2.5 0.3 5.0 1 5.5 8.5 1.0 5.5 10 No OA-AHU-SC-MZ-01 OA-AHU-SC-MZ-01
CONTROL ROOM
Soiled laundry storage Fresh air will be compensated from
36 GF - UPS ROOM UPS Room 12.0 3.0 Corridors 0.0 0.3 0.0 0 3.6 3.6 1.0 3.6 No OA-AHU-SC-MZ-01 5.0 60.0 No 60.0 EF-SC-MZ-03
rooms main hall
Total 1242 m² 122 209 1315.0 l/s 0.0 l/s 1.1 l/s/m² 1005.0 l/s 0.8 l/s/m² 130.85%

AHU TAG OA AIR FLOW EA AIR FLOW PERCENT OF EA Remarks

OA-AHU-SC-MZ-01 1315.0 L/s OA 835.0 L/s EA 63.5% EA of OA FAHU on Mezzanine level

EF-SC-MZ-03 60.0 L/s EA UPS Room

EF-SC-MZ-02 70.0 L/s EA Waste room

EF-SC-MZ-01 40.0 L/s EA Feature Café

Summery 1315.0 L/s OA 1005.0 L/s EA

Sheet 1 of 1