Specifications, Application Information Connection Details For The 24V Open Loop' 5A Pump Stroker Driver Unit. and
Specifications, Application Information Connection Details For The 24V Open Loop' 5A Pump Stroker Driver Unit. and
Specifications, Application Information Connection Details For The 24V Open Loop' 5A Pump Stroker Driver Unit. and
And
Connection Details for the
24V ‘Open Loop’ 5A Pump Stroker Driver Unit.
027-22069-0
11-11-1998/22069_AA.ppt 1
Product Application Hints
Denison Hydraulics Have Long Recognised the Need for Driver Electronics Which Are Reasonably
Priced, Easy to Apply, Mechanically Sound and Can Be Utilised in Many Differing Environments and
With a Wide Range of Proportional Products.
The Ideal Is to Keep Product Variation to a Minimum Which Will Reduce Spares Stocking As Well As
Allowing Commissioning Engineers, System Designers and Machine Operators to Become Familiar With
a Limited Range of Connections and Adjustments Which Will Improve Overall Efficiency, Confidence in
the Electronic and Hydraulic Components and Once Comfortable With the Operation and Parameters,
Will Generate Proven Electro-Hydraulic ‘Building-Blocks’ Which Can Be Used Time and Time Again
Without Extra Design or Production Time Being Wasted on Learning a New Product.
This open loop driver for the 5A Electro-Hydraulic Pump Stroker is intended to complement the existing
Jupiter Euro-card range and be used in applications that dictate lower cost and/or where it is difficult to
accommodate the standard Euro-card format.
The unit uses the latest internal component and circuit design technology to give full CE compliance to
present EMC directives to ensure maximum operational potential and efficiency, while offering Multiple
supply voltages and command options ( all selected by internal PCB mounted links ) in ONE unique and
easy to apply package.
The following ‘Application Hints’ for this versatile dual driver unit are only issued as a guide and if
required, further help and /or advice should be sought from your Local distributor or from Denison
Hydraulics internal sales departments.
11-11-1998/22069_AA.ppt 2
Product Advantages & Selling Points.
11-11-1998/22069_AA.ppt 3
General Information
Denison Hydraulics have engineered this 5A Electro-Hydraulic Pump Stroker driver to meet
today's exacting industry needs. The unit can, because of it’s unique design and built in
options, be applied in market areas ranging from marine to mobile with the confidence that our
valve, vane and piston hydraulic product lines already enjoy.
This ‘driver’ module is a culmination of many years field experience and is based on application
ideas that have come from all the various walks of industry that are already using Electro-
hydraulic equipment. This self contained unit consists of all the necessary building blocks which
will allow Electro-hydraulic system designers to fully explore the advantages of proportional
product mounted on a pump, and to see quickly and effectively how we can say that DENISON
hydraulics do have :- ‘ Active Solutions to Dynamic Problems ’.
Denison Hydraulics prides itself on the fact that the product we supply to you is of outstanding
quality that can be applied easily and quickly with success but it is important for us to also
understand changing customer needs, market trends and application requirements. With this in
mind, we will be only too glad to discuss new applications and listen to new requirements that we
can include in our future product designs, and use these idea’s to improve still further the
products usability and application flexibility.
The information contained in this literature brochure is intended as a Guide Only. Installation
and application of either electronic or hydraulic product supplied by DENISON hydraulics, should
only be undertaken by competent personnel with a good understanding of Electro-hydraulic
systems as well as being able to comply with all of the required industry standards and working
practices.
This NEW range of ‘drivers’ has been designed to not only comply with required ‘CE’ legislation
but in many areas, exceed the test specifications demanded by the ‘EMC directives currently
available as of February 1997. The units will however only meet the specifications laid down in
en-50081-1 & en-50082-2 ( heavy industrial specification ) if they are connected in accordance
with the relative ‘application data sheets’ supplied in this booklet.
With the supply of this literature and it’s contents, every effort has been made by DENISON
hydraulics U.K. To show due diligence and to offer as much advice as possible on application of
the product such that it will comply with the relative EC directives , however, it is the purchasers
responsibility to ensure that a copy of this literature is available to the nominated competent
personnel who are assembling the equipment on their behalf so that the ‘application data sheets’
and their contained information can be followed and adhered to.
While these units are ‘CE’ marked to show compliance with E.M.C. Directives, further advice on
matters pertaining to ‘CE’ marking of systems and equipment can be obtained from the D.T.I.
Who have a specific ‘Hotline’ set up to deal with these matters.
Denison Hydraulics U.K. Ltd reserve the right to alter, modify, up-issue and improve this products design,
specification and performance to meet new legislation, EC directive requirements and changing application areas
without giving prior notice.
11-11-1998/22069_AA.ppt 4
Product Application Hints.
IMPORTANT NOTE :-
Before starting to install or Apply any DENISON Hydraulics electronic control products,
please read the “ Helpful Hints for Trouble Free Application and Use of Electronic Driver
cards and Modules ” booklet which is available from your local distributor or from any U.K.
Denison Hydraulics office.
ALWAYS
• Take a few minutes to FULLY read THESE information / data sheets BEFORE starting.
• Ensure that you are aware of the available adjustments on the electronics and hydraulics.
• Make sure you have the correct tools to do the intended job ( i.e. D.V.M. ) e.t.c.
• Ensure that the correct option links applicable have been selected BEFORE applying power.
• ‘Isolate’ this unit from all other equipment BEFORE any form of welding takes place.
• Check ALL connections to and from the driver to ensure correct connections with NO short circuits.
• Make sure that all cables are ‘Screened’ and connected as indicated in the application data sheets.
• ‘Start’ operating a new system at LOW pressure and with SMALL command signals.
• Ensure that each valve coil has 2 dedicated wires to the connector for correct operation.
• Check that the units supply voltage is CORRECT, ‘ ELECTRICALLY CLEAN ’ and STABLE.
• Fit correctly rated ‘ In-Line ’ fuses on all SUPPLY and OUTPUT lines to protect unit.
• Operate the units within the specified operating temperature range for best performance.
• Ensure that units unused wires/terminals are terminated correctly and not shorted together.
• Contact DENISON Hydraulics for additional information if you are still unsure of connecting this unit.
NEVER
• Connect this unit’s 4-20mA PCB in series OR parallel with another as damage may occur.
• Attempt to use this unit if you are unsure of connections or expected operation.
• Attempt to use this unit in Areas where AC or DC coils HAVE NOT been fully suppressed.
• Attempt to use a power supply that is not rated for the correct required O/P current under full load.
• Allow wires TO or FROM the unit to be short circuited ( to each other or chassis/cabinet e.t.c. ).
• Attempt to use this unit in areas of intense RF without adequate screening measures.
• Disconnect or connect wires to or from this unit unless it it isolated from the power supply.
Wherever Possible.
• Keep High Voltage AC cables separate from Low Voltage DC signal and supply cables.
11-11-1998/22069_AA.ppt 5
Operational Information.
The ‘NEW’ 5A Electro-Hydraulic pump Stroker Driver is designed to operate continuously in any environment from a single
polarity +24VDC ( +/-20%) supply voltage.
The driver use the latest ‘MosFet’ type output stage with ‘Current Feedback’ to ensure accurate efficient operation of the
pump stroker valve, while giving an unrivaled linear output characteristic relative to a linear command voltage. Due to the
current feedback sensing circuit, the 5A’s valve coil MUST be individually connected using separate cables and NONE of
these wires should be connected to Earth, 0V or shared with any other valve driver or coil.
The output driver is ‘Normally Off’ but on application of a command signal, uses Pulse Width Modulation ( PWM ) which, is
pre-set to approx. 2000Hz to suit the type and size of valve being driven,
This PWM frequency is deliberately kept to a very high value to avoid damage to the 5A Pump Strokers ‘Jet-Pipe’ assembly
and to ensure maximum durability, accuracy and operational life from the product.
The Proportional output drive from this unit is capable of driving a single coil in ‘Push-Pull’ configuration where only ONE
direction of pump stroke is available at any one time.
The 5A pump strokers start point ( Minimum flow ) is set by ‘I Min’ while the end point ( Maximum flow ) is set by ‘I Max’ for
each individual coil by the potentiometers on the front panel. The minimum output value ( I Min ) will only be seen on the
respective output drive AFTER the +/-250mV ‘Zero-Band’ has been exceeded by the command signal.
The ‘I Min’ A & B and’ I Max’ A & B adjustments are CLOCKWISE to INCREASE the relative channels output current and
ANTI-CLOCKWISE to DECREASE the output current with all four potentiometers being approx. 20 turn variety ( ±5 turns )
with mechanical end stop slipping clutches to protect them from over adjustment.
The Standard unit is supplied with the ‘S’ link in a NULL STORAGE POSITION and is therefore defaulted to 0 to +/-5V
command. This can by easily changed by altering links S1, or S3, which configures the unit to accept 0 to +/-20mA OR 0 to
+/- 10V command signals respectively. The unit has an internal comparitor detection circuit which will ignore any command
signal input upto +/- 250mV ( Approx. ). This is done to ensure that when zero drive is required, it can be achieved without
the fear of ‘Electrical Noise’ on the command signal wires causing an erroneous valve operation. This ‘Zero-Band’ also allows
for mechanical tolerances and increasing ‘sloppiness’ in Joysticks or potentiometers at the zero position with age and usage.
With the addition and fitting of the 027-22072-0 sub-board, the dual driver unit can accept the industry standard 4 to 20mA
command signal and offer Bi or Uni-Directional control of the proportional valve selected by links ‘C1’ or ‘C2’. When the Sub-
board is fitted, the current command is connected directly to it via connectors ‘X’ & ‘Y’ ( See ‘Command Input Details Sheet’ in
this manual ).
The 027-22072-0 sub-board also has a built in ‘Loop Fault’ detector circuit which activates if the current loop input falls below
approx.. 3.7mA. If this occurs, the command signal is immediately sent to zero ( the output led’s will immediately go ‘Off’ ) and
held there until the current loop goes above the 3.7mA threshold when the driver will again start to follow the command. At
the same time, an open collector circuit is triggered and made available on terminals ‘T1’ & ‘T2’ which goes from a ‘HI’ level (
approx.. 8V with 3K3 pull-up ) to a ‘LO’ level ( approx. 0V ) on error. A front panel led also lights as a visual indicator of the
problem.
The units Ramp Generator is of the linear variety, is imposed onto the command signal and is fully adjustable from the front
panel potentiometers in the range of 20mS to 10 Secs ( Approx.) The ‘UP’ slope adjustment effects any signal going from a
numerically smaller value to a Larger one ( i.e. +1V to +4V OR -1V to -4V ) In any quadrant, while the ‘DOWN’ adjustment
effects any signal going from Larger numeric value to a smaller one ( i.e. -4V to -1V OR +4V to +1V ) again In any quadrant.
The ramp generator adjustments are CLOCKWISE to INCREASE rate of change of signal ( longer ramp time ) and ANTI-
CLOCKWISE to DECREASE the rate of change of signal ( shorter ramp time ) with both potentiometers being approx. 20 turn
variety with mechanical end stop slipping clutches to protect them from over adjustment.
For added safety, the units have a separate ‘High Current’ input supply for the output stage. This connection MUST be made
for the unit to work and should normally be connected to the supply voltage via a NORMALLY CLOSED ‘Emergency Stop’
switch. If this switch is opened, the output Immediately goes to zero, the ‘A’ or ‘B’ output On led’s on the front panel go ‘OFF’
and the front panel led marked as ‘Emergency Stop’ illuminates( this will only happen IF the other ‘Low Current’ supply input
is connected and powered ).
11-11-1998/22069_AA.ppt 6
Set-Up Procedure.
I Min ‘A’
+ 24V Power Supply Input 1 MosFet
Input Output
0V Supply Input 3 Supply Stage ‘A’
System ‘Earth’ Input 4 protection I Max ‘A’
Generator
Current
Feedback
0V Signal Input Y
027-22072-0
‘Add-On’ 4 to 20mA 9
Loop Fail ‘Digital’ Output T1 Sub-Board. Valve Coil
Connections
Loop Fail 0V Output T2
10
NOTES:-
1) +V Command ALWAYS makes terminal 9 +v.
Link ‘C1’ = Bi_Directional Output
Link ‘C2’ = Uni-Directional Output 1a) +V Command ALWAYS makes terminal 10 -v
2) -V Command ALWAYS makes terminal 9 -v
2a) -V Command ALWAYS makes terminal 10 +v
11-11-1998/22069_AA.ppt 8
Specification Data Sheet
027-22069-0
Open Loop Driver For The
5A Electro-Hydraulic Pump Stroker
I Max ‘A’
Power ‘ON’
I Min ‘A’
Emergency ‘STOP’
I Max ‘B’
Output ‘A’ ON
I Min ‘B’
Output ‘B’ ON
Ramp UP
4-20mA Loop Fail
Ramp DOWN
12mA
20mA +FSD 0V connection for Digital signal
Coil ‘A’ X Y
Time Time
Voltage
Coil ‘B’ Digital Signal Output
4mA -FSD T1 T2 Characteristic
Current
Digital Output
0V = Loop Fail
+V = Loop OK.
4mA = 0V Time
Selecting link C2 =
20mA = +FSD
Current 20mA
Current
20mA +FSD
Y = - 4 to 20mA Return ( 0V )
Coil ‘A’ X = + 4 to 20mA Input Time
0mA
ONLY
4mA = 0V Time 3.7mA Approx...
To allow 4 to 20mA operation, the Add-On sub board part No:- 027-22072-0 must be ordered as a
separate item and fitted by the user to the base 5A driver unit ( 027-22069-0 ).
11-11-1998/22069_AA.ppt 10
Specification Data Sheet
For Issue 1 Converter Boards With For Issue 2 Converter Boards With
Steel Screws. Nylon Screws.
M3 Nylon Screw
M3 Fiber Washer M3 Steel Screw
Converter Converter
PCB M3 Fiber Washer PCB
11-11-1998/22069_AA.ppt 11
Command Input Details
Command Inputs
10KOhm
+/- 5VDC 7 To Driver Circuit
+/- 10VDC 8 Link ‘S 1’ Link ‘S 3’
+/- 0 to 20mA
250 Ohm 10KOhm
0V Sig
0V Sig 0V Sig
‘Sx’ ‘S 1’ ‘S 2’ ‘S 3’ ‘C 1’ ‘C 2’
Input Command Type
+/- 5VDC
0 0 0 0 / /
+/- 10VDC
0 0 0 1 / /
+/- 0 to 20mA
0 1 0 0 / /
4 to 20mA
Bi-Direction X 0 0 0 1 0
4 to 20mA
Uni-Direction X 0 0 0 0 1
Legend :-
NOTES:-
1 = Link Jumper Fitted
1) Terminal ‘8’ & ‘Y’ are BOTH connected to 0V Signal (Sig). 0 = Link Jumper NOT Fitted
2) NO ‘S’ LINK = Default 0 to +/-5V command setting. / = Link Position Not Important
x = NO links fitted. Fit sub-
11-11-1998/22069_AA.ppt board 027-22072-0. 12
Link Options Data Sheet
S
1 3
1 23 4 56 7 8 9 10
Terminal
Function
Number Link Function
1 ---- +V DC Power Supply Input Number
2 ---- +V DC Valve Supply Input ‘S 1’ ---- +/- 0 to 20mA Command Input Option Select
NO LINK ---- +/- 5V DC Command Input Option select
3 ---- 0V DC Power Input ‘S 3’ - +/- 10V Command Input Option select
11-11-1998/22069_AA.ppt 13
Link Options Data Sheet
NOTE:- 027-22072-0
4 to 20mA Option Board
Remove ALL links from ‘S’
before fitting 4 to 20mA option 1
sub-board.
When option sub-board is
C 2
fitted , automatic selection of
4 to 20mA command takes X Y T1 T2
place.
1 3
1 23 4 56 7 8 9 10
S
11-11-1998/22069_AA.ppt 14
Application Data Sheet
( 24V @ 2 Amps )
= User fitted
‘In-Line’ fuse. S
1 3
1 23 4 56 7 8 9 10
Signal ‘SCREEN’
NOTE 1) To maintain compliance with E.M.C. directives, Terminal 4, MUST be made to ‘ System Earth’
11-11-1998/22069_AA.ppt 15
Application Data Sheet
C
1
= User fitted X Y
2
T1 T2
‘In-Line’ fuse.
1 23 4 56 7 8 9 10
IMPORTANT 0V Supply
See Note #1
Below
4-20mA Command
Input (+) +4-20mA I/P ( 250R ) 5A Pump
Stroker Unit
4-20mA Command - 4-20mA I/P Return ( 0V Sig )
Input (-) Signal ‘SCREEN’
NOTE 1) To maintain compliance with E.M.C. directives, Terminal 4 MUST be made to ‘ System Earth’
NOTE 2) Remove ALL links from ‘S’ before fitting 4 to 20mA option board as this automatically selects current command.
11-11-1998/22069_AA.ppt 16
Troubleshooting Guide
• Cannot achieve full flow at full command and full ‘I Max’ adjustment.
1) Check supply voltage is fully +24V and is stable under load conditions.
2) Ensure that the strokers mechanical ‘Max’ end stop adjustments are set correctly.
• The ‘Emergency stop’ red led is always lit and no output is available.
1) Ensure that there is voltage supply to terminal No. 2 ( Valve supply input ).
• The output from the driver goes between zero and full on only with no proportionality.
1) Ensure that there is a coil connected to the output on terminals 9 & 10.
2) Check that the coil wires (2) are not shorted and correctly connected to the driver unit.
• The pump strokes the wrong way for a positive command input.
1) Reverse the wire connections on terminals 9 & 10.
• The pump has flow even at zero command and with both output lights off.
The pump has a mechanical offset within the stroker unit.
1) Remove the electrical connector plug on the stroker.
2) Adjust the strokers zero screw to achieve zero flow.
3) re-connect the electrical connector.
11-11-1998/22069_AA.ppt 17
Mechanical Data
Drawing NOT TO SCALE.
40mm
60 mm 60 mm 6mm 2mm
5mm
Dia.
5mm 5mm
Dia. Dia.
22 mm
6mm 6mm
108 mm
Wire entry ‘slots’ in
Rear panel ‘Support bar’
NOTE:- Rear panel is ‘self-locking’ and comes loose in unit packaging and must be
fitted by user once adjustments have been completed. If the rear panel must be removed
for further adjustments, the ‘locking’ clips may be damaged. This is not detrimental to the
units operation as the rear panel is adequately held in place by the main housing once re-
mounted to the bulkhead / panel.
11-11-1998/22069_AA.ppt 18
Important Information Sheet.
The electronic unit contained in this package MUST be mounted in the manner described in this
Information Sheet to fall in line with current regulations on EMC. By issuing this document, Denison
Hydraulics are showing their commitment and due diligence to the rules concerning EMC within Europe.
• ALWAYS follow connection, application and usage instructions provided with the electronic unit.
• ALWAYS mount this unit inside a steel or conductive metal enclosure with NO unused open holes.
• ALWAYS ensure that the enclosure is EMC approved OR sealed with conductive gaskets.
•ALWAYS use fully screened cables of the correct rating for ALL input and output connections.
• ALWAYS connect the ‘Screen’ from the cables to Earth points INSIDE the enclosure as shown.
• ALWAYS ensure that ANY Earth connection is to clean, bare metal and NOT a paint finish.
•ALWAYS connect the ‘Earth’ terminal on the solenoid coil to the cable screen.
• ALWAYS ensure that the enclosure is securely connected to a known good bonded ‘Earth’ point.
• ALWAYS ensure that ALL cables enter and exit the enclosure through ‘METAL’ cable glands.
• ALWAYS ensure that NO High Power RF is used near or inside an open enclosure.
• Electronic Unit.
• Cable Screens
connected to enclosure
• Conductive gasket if enclosure is • Metal cable glands with or as close to entry point
not EMC approved. without screening option. as possible.