GENERAL NOTES:
1. CONCRETE COMPRESSIVE STRENGTH IN 28 DAYS:
SLAB ON GRADE, FOOTINGS. . . 3000 PSI
SLUMP SHALL BE 3-5 INCHES.
2. REINFORCING:
ASTM A615 - GRADE 60.
WELDED WIRE FABRIC - ASTM A185 (FLAT SHEETS ARE ACCEPTABLE)
3 3. PROVIDE REINFORCING IN SLABS ON GRADE 1/3 DEPTH DOWN FROM
7 TOP OF SLAB. SEE PLAN FOR SIZE.
S1.1
S1.1 4. REFER TO THE DRAWINGS FOR REINFORCING LAP REQUIREMENTS,
WHERE LAP SPLICES ARE NOT SHOWN, LAP PER ACI 318 OR CRSI
STANDARDS (24" MIN. LAP).
7 5. LAP WELDED WIRE FABRIC SHEETS 8" MINIMUM.
S1.1 6. CLEAR COVER FROM FACE OF CONCRETE:
FORMED SURFACE . . . . . . . . . . . . . . . . . . 1-1/2"
EXPOSED TO EARTH . . . . . . . . . . . . . . . . 3"
7. ANCHOR RODS SHALL CONFORM TO THE REQUIREMENTS OF ASTM
F1554 GRADE 36, OR A36.
8. GROUT UNDER BASE PLATES (IF SPECIFIED) TO BE HIGH STRENGTH,
NON-SHRINK.
9. IF NO SOILS REPORT IS PROVIDED, SOIL BEARING STRENGTH WILL BE
ASSUMED TO BE 2000 PSF. CONTRACTOR SHALL FIELD VERIFY DURING
CONSTRUCTION. ANY VARIANCE SHALL BE REPORTED TO THE ENGINEER
FOR REDESIGN IF REQUIRED.

PREMIER BUILDING SYSTEMS, INC.


10. ALL FOOTINGS SHALL BE PLACED ON ORIGINAL SOIL, OR STRUCTURAL

KNESTRICK PROPERTY HOLDINGS


FILL COMPACTED TO 95% STANDARD PROCTOR. EITHER CONDITION
MUST MEET THE MINIMUM BEARING STRENGTH SHOWN.
11. CONTRACTOR SHALL PROVIDE NECESSARY CRACK CONTROL - SAW
JOINTS OR CONSTRUCTION JOINTS. IN CONCRETE POURS, SUBDIVIDED
3 SLAB AREA SHALL NOT EXCEED 750 SQ FT.

BRASELTON, GA 30517
S1.1 12. IF MECHANICAL OR ELECTRICAL CONDUIT EXCEEDS 3/4" DIAMETER,

847 HWY 124 SUITE A

LA VERGNE, TN 37086
CONTRACTOR SHALL TAKE SPECIAL PROVISIONS TO PROVIDE 1-1/2"
CONCRETE POURING CLEARANCES.
4", 4000 PSI CONCRETE SLAB W/6X6-10/10 WELDED 3 13. SEE PREMIER BUILDING SYSTEMS, INC DRAWINGS JOB # 147484

165 JONES BLVD


BLDG. A, C, & E
WIRE REINFORCEMENT AND 6 MIL VAPOR BARRIER S1.1 DATED 3/8/19 FOR THE BUILDING REACTIONS AND ANCHOR ROD (BOLT)
SIZES AND SETTINGS.

ALTERNATE SLAB REINFORCEMENT NOTE: FIBER REINFORCED


CONCRETE SHALL BE
AN ACCEPTABLE ALTERNATIVE TO WELDED WIRE MESH IN SLABS. IF
FIBER MESH IS USED ADD FIBER, PER CUBIC YARD OF CONCRETE,
ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
4
S1.1 ANCHOR RODS TYPE:
SIZE LENGTH HOOK
5/8 12" 3" CONTRACTORS OPTION
3/4 16" 5"
1.0 24" 6"

6
SEE BUILDING MANUFACTURERS
S1.1 DRAWINGS FOR DIAMETER, QTY,
AND LOCATION LENGTH

3/16"

1
4 S1.1 THREAD EACH END
S1.1 3 OR ALL THREAD ROD
S1.1 HEAVY HEX NUT

03/27/19
The Professional Engineers seal affixed to this sheet applies only to the
material and items shown on this sheet. All drawings, or other documents
not exhibiting this seal shall not be considered prepared by this engineer,
and this engineer expressly disclaims any and all responsibility for such
plan, drawing, or documents not exhibiting this seal.

FOUNDATION PLAN

S1.0
J. WALTER LEWIS
2 P.E., S.E.
S1.1 113 STONECREST AVE.
WAYNESBORO, VA 22980-9646
PH 239-565-7849
FAX239-481-6124

PREMIER BUILDING SYSTEMS, INC.

KNESTRICK PROPERTY HOLDINGS


BRASELTON, GA 30517
847 HWY 124 SUITE A

LA VERGNE, TN 37086
165 JONES BLVD
BLDG. A, C, & E
GRADE GRADE

03/27/19

The Professional Engineers seal affixed to this sheet applies only to the
material and items shown on this sheet. All drawings, or other documents
not exhibiting this seal shall not be considered prepared by this engineer,
and this engineer expressly disclaims any and all responsibility for such
plan, drawing, or documents not exhibiting this seal.

FOUNDATION DETAILS

S1.1