300 300

Backfill Slope 1(V) : 1(H) Backfill Slope 1(V) : 1(H) 300 Backfill Slope 1(V) : 1(H)
Vertical Bars
Weep Hole 100 mm Ø 16 Ø - 250 c/c Extra Hooks

2455
Stoneware / Heavy Duty UPVC Pipe 12 Ø - 400 c/c
Spacing = 3000 c/c Horizontal along Height
1000 c/c Vertical
Horizontal Bars
12 Ø - 150 c/c
4870

Bars @ Bothway
12 Ø - 150 c/c
RC Wall
1St Weep Hole
Alternet Hooks
100 mm Ø
Vertical Bars
12 Ø - 200 c/c 1000

3065
along length
16 Ø - 125 c/c
Compacted filling
500

Filling Side Exposed Side


Main Bars
1350
300 Distri. Bars 16 Ø - 220 c/c
12 Ø - 150 c/c
1250

100
1250

300
600 550
Typ. Typ.

600
500
500 500 500 300
2500 450 300
150

PCC 1 : 3 : 6
PCC 1 : 3 : 6 Distri. Bars
150

1000 1000
SOLING 150 MM 12 Ø - 150 c/c Main Bars Extra Hooks
2500
SOLING 150 MM 16 Ø - 220 c/c 12 Ø - 500 c/c

1500

1500

1500
Notes:
1) All Codes of Practice Published by Bureau of Indian Standards and referred to
in this Drawing shall be of Latest Publication with all of it's amendments.
2) Concrete shall be design mix and shall have minimum 28 days
Characteristic Strength 20 MPa on 150 mm Cubes for all elements of the Structure
Ordinary Portland Cement conforming to IS 269 & 53 Grade Cement conforming
to IS 12269 capable of achieving the required design Concrete strength shall be used
Total Chloride content and Sulphuric Anhydride (SO3) of concrete as a percentage of mass of 25 Ø Anchor Rod 3 No.s
cement in Mix shall be limited to 0.3 % and 4 % respectively 1000 c/c along Length of
3) Concrete shall be produced in a mechanical Mixer of capacity not less than 200 Ltrs having Integral Wall
weigh Batching facility and preferably having automatic water measuring & Dispensing facility
4) H. Y. S. D. Bars shall be of Grade Fe 500 Conforming to IS:1786
Anchorage 1500
5) Clear Cover of 100 mm shall be provided to Bars @ bottom in Raft
Clear Cover of 50 mm shall be provided to Bars in all other locations
6) For General Instructions on R.C.C. Work refer To SP 16, SP 24, SP 34, IS: 2502 Approved for Execution
7) For Detailing of Reinforcement refer to SP 34 Handbook and IS 13920
8) Development Length (Ld) of the Column Reinforcement shall be (50 x Bar Diameter)
arranged as per clause - 304.6.6.2 of I.R.C. 21 - 2000
9) Sharp edges of concrete shall be chamfered
10) In aggressive soil conditions the concrete faces in contact shall be protected with approved bituminus Paint or Coating as Directed Registration ID CBRCM/R/2022/APL/00239
11) Design, Erection, Stability & satisfactory performance of shuttering is scope & responsibility of execution contracting
A/P Khend opposite to Shree Krishna Temple,
12)Pipes for weep Holes shall be laid at Slope of 1 (Vertical to 15 (Horizontal) Chiplun, Ratnagiri, 415605
Mob- 9011984068 / 7219582298
Structural Consultant Approval by
15
Date 25-03-2024 Designed Er.Shubham D CLIENT: Maharashtra Industrial Development Corporation (MIDC)
13) Safe Bearing Capacities of strata below the Base of the wall is considered as 200 kN / Sq.m. this shall typically correspond to Hard Strata PROJECT: Construction of Retaining Wall in Gane Village ,Khadpoli MIDC
14) Backfill shall consist of Compacted Soil of Unit Weight up to 18 kN / Cu.m. Scale Drawn Er.Shubham D
15) Max. straight Length shall be 10 m. Provide Gap of 10 mm between two adjacent Wall Segments.
TITLE: Structural Details of RCC Retaining Wall
Rev. DRG. No. 1 for Gane Khadpoli Industrial Area