SOLITUDE

12539 EAST WILDERNESS ROAD

UPDATES
02.21.24
obj | gary_matter(s)
SMALL STAIR
EXPANDED STAIR
INTERIOR
SEPTIC DESIGN SHEET NUMBER

S-1
12439 E WILDERNESS ROAD
BRIGHTON
SALT LAKE COUNTY, UTAH

SALT LAKE CITY, UT 84103


515 EAST 11TH AVENUE
10 0 5 10 20

DAVID COLVIN
OWNER

404-919-8971
Scale (24'' x 36'') 1 in. =10 FT.

LOT 27 FOREST GLEN SUBDIVISION


FCOZ & SPETIC SHEET SET

12439 E WILDERNESS ROAD


BRIGHTON, UTAH 84121
SYSTEM SIZE CALCULATIONS & NOTES
1. Determined the daily flow for a 4 bedroom home at 600
gallons per day.

2. Determined the absorption treatment area for a deep wall trench system
using a loading rate from percolation test of 0.9 gal/sq.ft./day and all
reductions at 666 sq. ft. 5 feet deep the total length of leach field is 67 feet.
The Perk Test performed by JASON FORESTER Dated 11-13-2021

2b. Back up system shall have 5 trenches at Various lengths and 3 feet in ISSUE DATE: 10-19-23
width at a maximum depth of 2 feet. with the 30% reduction using chambers
the effective treatment 466 sq.ft/ provided treatment 480 sq.ft. Note REVISIONS:
secondary treatment will need to be pressurised. PORCHED CHANGED
GRADING COMMENTS
HEALTH DEPARTMENT REVIEW
3. Septic Tank shall be of approved cast concrete and/or construction type COMMENTS 10-11-22
with baffles effluent screeds and proper access lid with risers if needed. Tank
NEW HOUSE DESIGN 10-19-23
size = 250 gallons per bedroom plus 1000 gallons for the first 3 bedrooms of
the daily waste water flow totals 1000 gallons. 1000 min. gallon tank shall be
used for the install of this system (see detail) Also see Utah Regulation code:
R317-4-6 concerning design requirements, construction risers and minim STAMP
sizes etc.

4. See percolation test and soils classification log for additional details.

· THE CONTRACTOR IS RESPONSIBLE FOR TRENCH 5. Site design, installation and materials must meet all requirement and
codes as defined in Section R317-4 of the Utah Code.
SAFETY AND SHALL IMPLEMENT TRENCH-SHIELDS
OR SHORING AND PERTINENT OSHA 6. The proposed on site wastewater system is located 100+ feet from any
REQUIREMENTS AS NEEDED TO PROVIDE A SAFE non-public or public water supply sources.
SALT LAKE COUNTY HEALTH DEPARTMENT NOTES WORK ENVIRONMENT TO PROTECT WORKERS IN
DEEPER EXCAVATIONS. 7. The dwelling on this site will be serviced by Emigration improvement
1. No ground water was detected at 10' deep. district water service (see Engineering Utility drawing).
2. Bedrock was not detected. · DRAINFIELD EXCAVATIONS SHALL NOT BE
3. There are PUE' easements along the property 8. The proposed septic tank is located 25+ feet from any water course, as
PERFORMED DURING PERIODS OF PRECIPITATION. well as 50+ feet for the proposed drain field.
lines and the access R.O.W lines.
4. Septic System is greater then 100 ft from ditches, · SALT LAKE COUNTY HEALTH DEPARTMENT WILL 9. Follow all safety requirements as per Utah Regulation code: R317-4
streams, ponds. PERFORM A LEAK TEST ON TANKS PRIOR TO concerning trench safety and installation safety requirements.
5. Surface water must be diverted away from BACKFILLING TO BE ARRANGED BY CONTRACTOR
10. Excavation of the Drain field area may not be commenced during