Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 21

DOCUMENT TRANSMITTAL

(DTR)
Transmittal.Number : OTC/BKEI/DTR/V/028 Ref.No
Date : 13-May-2024
To : Haerudin<Haerudin@amman.co.id> 028
cc : Bambang Tri Eko Sukarno <bambang.tri.eko.sukarno@amman.co.id>;
La Ode Aluhisadin<la.aluhisadin@amman.co.id>;
Petra Firman<petra.firman@amman.co.id>;
Tutuk Dany Anugroho<tutuk.dany.anugroho@amman.co.id>
Syahrial<syahrial.7333@amman.co.id>;
Muhamad Nur Kholis Majid<nur.kholis.majid@amman.co.id>;
Leonardo Hutabarat<leonardo.hutabarat@amman.co.id>;

Subject : N/A - Engineering, Procurement, and Contruction Utility System At Otakeris

Dear Pak Haerudin,


We enclose herewith the documents as listed below :

NO No. Document Description Rev. Issued Status

CALCULATION SHEET FOR CONTROL BOX


1. AMNT-BKEI-OTC-ST-CAL-05 R.0 ISSUED FOR APPROVAL
CABELING

Remarks :

Submitted by : Authorized Recipient's Signature


PT. BINKEI PT. AMMAN MINERAL
Sign

Name RIDO KURNIA HAERUDIN


Date 13-May-2024
PROJECT TITLE
ENGINEERING, PROCUREMENT, AND CONSTRUCTION UTILITY SYSTEM AT
OTAKERIS

CALCULATION TITLE

CONTROL BOX CABELING

PROJECT NO : BH2408700co
DOCUMENT NO : AMNT-BKEI-OTC-ST-CAL-05

REVISION DATE DESCRIPTION ORIGINATOR CHECKER APPROVED CLIENT APPROVAL

R.0 13-May-2024 ISSUED FOR APPROVAL


R.0 13-May-2024 ISSUED FOR APPROVAL
TITLE

CALCULATION SHEET FOR CONTROL BOX CABELING

DOCUMENT NUMBER FORMAT REV SHEET


AMNT-BKEI-OTC-ST-CAL-05 A4 0

CONTROL BOX FOR CABLE (1.50 m x 1.50 m x 0.95m)


DATA - DATA :
- Control box width (Lx) = 1.26 m
- Length of control box (Ly) = 1.26 m
- Control box height (H) = 0.7 m
- Wall thickness (b) = 12 cm
- Thickness of base plate ( B ) = 10 cm
- Thickness of roof plate ( h ) = 15 cm
- Specific gravity of soil ( g tanah ) = 1.8 T/m3
- Specific gravity of water ( g air ) = 1 T/m3
- Soil shear angle ( j ) = 32 degree
-Active soil pressure coefficient ( Ka ) = 1  sin  0.307
1  sin 

b L b

A CONTROL BOX WALL PLANNING

A.1 Force acting on the wall

tekanan tanah + tekanan air tanah

A.2 At the base of the control box, a pressure of :


- P due to the ground = 1/2 g soil. H2 ka
= 1/2 (1.8) . 0.7^2 . 0.307
= 0.1354 t/m2
- P due to water = 1/2 g water H2
= 1/2 (1) . 0.7^2
= 0.245 T/m2
A.3 Moment occurring at the bottom of the wall
M = (Psoil + Pwater) . 1/3 H
= (0.135387 + 0.245) . 1/3 . 0.7
= 0.089 T.m

A.4 Reinforcement of the control box wall:


- thick wall = 120 mm
- concrete decking = 20 mm
- effective thickness d = 100 mm
- Concrete quality fc' = K-250 = 20.75 Mpa
- Steel grade fy = U-24 = 388 MPa

m = fc / (0,85 .fy)
= 388 / (0.85 . 20.75)
= 22.00

Rn = M / (f b d2)
= ( 0.089.10^7) / (0,85 1000 . 100^2)
= 0.105

r = (1/m) * (1 - √ ( 1 - ((2 Rn m)/fy)) )

= (1/22.00) * (1 - √ 1 - ((2 0.11 . 22.00)/388))

= 0.0003

Aneed = r .b .d = 27.14 mm2

The minimum reinforcement for the slab is 0.25% of the


Existing concrete area, or :
Amin = 0,25% . 1000 . 120 = 300.00 mm2
Ause = 300.0 mm2
Reinforcement installed f10 - 200 393 mm2 > Ause
Splitter reinforcement = 20% A = 20% 393 = 78.60 mm2
Reinforcement installed f6 - 200 141 mm2 > Ause

B CONTROL BOX BASE PLATE PLANNING

B.1 Force acting on the slab, when the control box is empty
balok sloof
balok sloof

1.26

1.26

B.2 On the base slab acts a pressure of :


- P due to water g water . H
= 1 . 0.7
= 0.7 T/m2
B.3 Moment occurring at the bottom of the wall

1.26

1.26

Obtained moment :

lx 1.26 m
ly 1.26 m
ly/lx 1.00
Full pinch/elastic {1/2] 2
wlx (table after interpolation) 36.00
wly (table after interpolation) 36.00

Mlx = -Mtx = 0.0360 . Q .lx2 = 0.0360 . 700 . 1.26^2 = 40.01 kg.m


Mly = -Mty = 0.0360 . Q .lx2 = 0.0360 . 700 . 1.26^2 = 40.01 kg.m

B.4 Reinforcement of control box base slab:


- slab thickness = 100 mm
- decking concrete = 20 mm
- effective thickness d = 80 mm
- Concrete quality fc' = K-250 = 20.75 Mpa
- Steel grade fy = U-24 = 280 MPa

m = fc / (0,85 .fy)
= / (0.85 . 280)
= 15.88

Rn = M / (f b d2)
= ( 40.008.10^4) / (0,85 1000 . 80^2)
= 0.07

r = (1/m) * (1 - √ ( 1 - ((2 Rn m)/fy)) )

= (1/15.88) * (1 - √ 1 - ((2 0.07 . 15.88)/280))

= 0.0003

Aneed = r .b .d = 21.06 mm2

The minimum reinforcement for the slab is 0.25% of the


existing concrete area, or :
Amin = 0,25% . 1000 . 100 = 250.00 mm2
Ause = 250.00 mm2
Reinforcement installed f8 - 150 335 mm2 > Ause
( wiremesh M.8)
B.5 REINFORCEMENT DRAWING

Wall reinforcement
f10 - 200

Reinforcement bars
f6 - 200

Base Plate Reinforcement


f8 - 150
C CONTROL BOX ROOF SLAB PLANNING

C.1 Roof slab data


Compressive strength of concrete, f c' = 20.75 MPa
Yield stress of steel for flexural reinforcement, fy = 388 MPa
X direction plate span length, Lx = 1.26 m
Y direction plate span length, Ly = 1.26 m
Thickness of roof slab, h= 150 mm
The slab moment coefficient for : Ly / L x = 1.00 SLAB MOMENT COEFFICIENT

TWO DIRECTIONS because Ly/Lx<2


Field x Clx = 21
Field y Cly = 21
Support x Ctx = 52
Support y Cty = 52
Table 2 with 4 pinched edges

Diameter of reinforcement used, Æ= 10 mm


Net thickness of concrete blanket, ts = 20 mm

C.2 Roof slab loading data

1. DEAD LOAD

No Dead Load Type Unit weight Thickness (m) Q (kN/m2)


1 Self weight of floor slab (kN/m3) 24.0 0.15 3.600

Total beban mati, QD = 3.600


2. LIVE LOAD

Live load = 120.00 kg/m2


® QL = 1.2 kN/m2

3. FACTORISED PLAN LOAD

Factorised plan load, Qu = 1.2 * QD + 1.6 * QL = 6.240 kN/m2


4. THE SLAB MOMENT DUE TO THE FACTORED LOAD

X-direction field moment, Mulx = Clx * 0.001 * Qu * Lx2 = 0.208 kNm/m


Y-direction field moment, Muly = Cly * 0.001 * Qu * Lx2 = 0.208 kNm/m
X-direction fulcrum moment Mutx = Ctx * 0.001 * Qu * Lx2 = 0.515 kNm/m
Y-direction fulcrum moment Muty = Cty * 0.001 * Qu * Lx2 = 0.515 kNm/m
Plan moment (maximum) of the slab, ® Mu = 0.515 kNm/m

C.3 Slab Reinforcement

For : fc' ≤ 30 MPa, b1 = 0.85


For : fc' > 30 MPa, b1 = 0.85 - 0.05 * ( fc' - 30) / 7 = -
Concrete stress distribution form factor, ® b1 = 0.85
Reinforcement ratio in the balanced condition,
rb = b1* 0.85 * fc'/ fy * 600 / ( 600 + fy ) = 0.0235
Maximum moment resistance factor,
Rmax = 0.75 * rb * fy * [ 1 – ½* 0.75 * rb * fy / ( 0.85 * fc') ] = 5.5065
Flexural strength reduction factor, f = 0.80
Distance of reinforcement to outer side of concrete, ds = t s + Æ / 2 = 25.0 mm
Effective thickness of floor slab, d = h - ds = 125.0 mm
1 m wide floor slab is considered, ® b= 1000 mm
Nominal plan moment, Mn = Mu / f = 0.644 kNm
Moment resistance factor, Rn = Mn * 10 / ( b * d ) =
-6 2
0.04121
Rn < Rmax ® (OK)
Required reinforcement ratio:
r = 0.85 * fc' / fy * [ 1 - Ö [ 1 – 2 * Rn / ( 0.85 * fc' ) ] = 0.0001
Minimum reinforcement ratio, rmin = 0.0025
Ratio of reinforcement used, ® r= 0.0025
Required reinforcement area, As = r * b * d = 313 mm2
Required reinforcement spacing, s = p / 4 * Æ2 * b / A s = 251 mm
Maximum reinforcement spacing, smax = 2 * h = 300 mm
Maximum reinforcement spacing, smax = 200 mm
Spacing of stirrups to be used, s= 200 mm
Taken stirrup spacing: ® s= 200 mm
Used reinforcement, Æ 10 - 200
Area of reinforcement used, As = p / 4 * Æ 2 * b / s = 393 mm2

C.4 Slab Deflection Control


Mpa = N/mm2
Elastic modulus of concrete, Ec = 4700*√ fc' = 21410 MPa
Elastic modulus of reinforcing steel, Es = 2.10E+05 MPa
Evenly distributed (non-factorised) load on the slab, Q = QD + QL = 4.800 N/mm
Span length of the slab, Lx = 1260 mm
Maximum allowable deflection limit, Lx / 240 = 5.250 mm
Gross moment of inertia of slab cross section, Ig = 1/12 * b * h = 3
281250000 mm3
Flexural collapse modulus of concrete, fr = 0.7 * √ fc' = 3.188651752701 MPa
Comparative value of elastic modulus, n = E s / Ec = 9.81
Distance of neutral line to top side of concrete, c = n * As / b = 3.852 mm
The moment of inertia of the cracked section transformed to concrete is calculated as follows. :
Icr = 1/3 * b * c3 + n * As * ( d - c )2 = 56552522 mm4
yt = h / 2 = 75 mm
Cracking moment: Mcr = fr * Ig / yt = 11957444 Nmm
Maximum moment due to load (without load factor):
M a = 1 / 8 * Q * L x2 = 952560 Nmm
Effective inertia for deflection calculation,
Ie = ( Mcr / Ma )3 * Ig + [ 1 - ( Mcr / Ma )3 ] * Icr = 444520204465 mm4
Instantaneous elastic deflection due to dead and live loads:
de = 5 / 384 * Q * Lx4 / ( Ec * Ie ) = 0.000 mm
Floor slab reinforcement ratio: r = As / ( b * d ) = 0.0031
Time dependency factor for dead load (period > 5 years), value :
z= 2.0
l = z / ( 1 + 50 * r ) = 1.7285
Long-term deflection due to creep and shrinkage:
dg = l * 5 / 384 * Q * Lx4 / ( Ec * Ie ) = 0.000 mm
Total deflection, dtot = de + dg = 0.000 mm
Condition: dtot ≤ Lx / 240
0.00 < 5.250 ® SAFE (OK)
Tabel 2. Momen Pelat Persegi akibat beban merata kondisi tumpuan bebas dan terjepit
penuh
Momen Pelat persegi akibat beban merata (PBI'71)

Nilai Perbandingan Ly/Lx


Kondisi Pelat
Momen Pelat 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5 > 2,5

2
Mtx = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Lx 2
Mlx = 0.001.q.Lx x 44 52 59 66 73 78 84 88 93 97 100 103 106 108 110 112 125
2
Mly = 0.001.q.Lx x 44 45 45 44 44 43 41 40 39 38 37 36 35 34 32 32 25
Ly
2
Mty = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

2
Mtx = - 0.001.q.Lx x 52 59 64 69 73 76 79 81 82 83 83 83 83 83 83 83 83
2
Mlx = 0.001.q.Lx x 21 25 28 31 34 36 37 38 40 40 41 41 41 42 42 42 42
2
Mly = 0.001.q.Lx x 21 21 20 19 18 17 16 14 13 12 12 11 11 11 10 10 8
2
Mty = - 0.001.q.Lx x 52 54 56 57 57 57 57 57 57 57 57 57 57 57 57 57 57

2
Mtx = - 0.001.q.Lx x 68 77 85 92 98 103 107 111 113 116 118 119 120 121 122 122 125
2
Mlx = 0.001.q.Lx x 28 33 38 42 45 48 51 53 55 57 58 59 59 60 61 61 63
2
Mly = 0.001.q.Lx x 28 28 28 27 26 25 23 23 22 21 19 18 17 17 16 16 43
2
Mty = - 0.001.q.Lx x 68 72 74 76 77 77 78 78 78 78 79 79 79 79 79 79 79

2
Mtx = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2
Mlx = 0.001.q.Lx x 22 28 34 42 49 55 62 68 74 80 85 89 93 97 100 103 125
2
Mly = 0.001.q.Lx x 32 35 37 39 40 41 41 41 41 40 39 38 37 36 35 35 25
2
Mty = - 0.001.q.Lx x 70 79 87 94 100 105 109 112 115 117 119 120 121 122 123 123 125

2
Mtx = - 0.001.q.Lx x 70 74 77 79 81 82 83 84 84 84 84 84 83 83 83 83 83
2
Mlx = 0.001.q.Lx x 32 34 36 38 39 40 41 41 42 42 42 42 42 42 42 42 42
2
Mly = 0.001.q.Lx x 22 20 18 17 15 14 13 12 11 10 10 10 9 9 9 9 8
2
Mty = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

2
Mtx = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2
Mlx = 0.001.q.Lx x 31 38 45 53 60 66 72 78 83 88 92 96 99 102 105 108 125
2
Mly = 0.001.q.Lx x 37 39 41 41 42 42 41 41 40 39 38 37 36 35 34 33 25
2
Mty = - 0.001.q.Lx x 84 92 99 104 109 112 115 117 119 121 122 122 123 123 124 124 125

2
Mtx = - 0.001.q.Lx x 84 92 98 103 108 111 114 117 119 120 121 122 122 123 123 124 125
2
Mlx = 0.001.q.Lx x 37 41 45 48 51 53 55 56 56 59 60 60 60 61 61 62 63
2
Mly = 0.001.q.Lx x 31 30 28 27 25 24 22 21 20 19 18 17 17 16 16 15 13
2
Mty = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

2
Mtx = - 0.001.q.Lx x 55 65 74 82 89 94 99 103 106 110 114 116 117 118 119 120 125
2
Mlx = 0.001.q.Lx x 21 26 31 36 40 43 46 49 51 53 55 56 57 58 59 60 63
2
Mly = 0.001.q.Lx x 26 27 28 28 27 26 25 23 22 21 21 20 20 19 19 18 13
2
Mty = - 0.001.q.Lx x 60 65 69 72 74 76 77 78 78 78 78 78 78 78 78 79 79

2
Mtx = - 0.001.q.Lx x 60 66 71 74 77 79 80 82 83 83 83 83 83 83 83 83 83
2
Mlx = 0.001.q.Lx x 26 29 32 35 36 38 39 40 40 41 41 42 42 42 42 42 42
2
Mly = 0.001.q.Lx x 21 20 19 18 17 15 14 13 12 12 11 11 10 10 10 10 8
2
Mty = - 0.001.q.Lx x 55 57 57 57 58 57 57 57 57 57 57 57 57 57 57 57 57

Catatan:
= Terletak bebas
= Terjepit penuh
TITLE

CALCULATION SHEET FOR CONTROL BOX CABELING

DOCUMENT NUMBER FORMAT REV SHEET


AMNT-BKEI-OTC-ST-CAL-05 A4 0

CABELING CONTROL BOX (1.74 m x 1.0 m x 1.25 m)


DATA - DATA :
- Control box width (Lx) = 0.76 m
- Length of control box (Ly) = 1.5 m
- Control box height (H) = 1.0 m
- Wall thickness (b) = 12 cm
- Thickness of base plate ( B ) = 10 cm
- Thickness of roof plate ( h ) = 15 cm
- Specific gravity of soil ( g soil ) = 1.8 T/m3
- Specific gravity of water ( g water) = 1 T/m3
- Soil shear angle ( j ) = 32 degree
-Active soil pressure coefficient ( Ka ) = 1  sin  0.307
1  sin 

b L b

A CONTROL BOX WALL PLANNING

A.1 Force acting on the wall

ground pressure + groundwater pressure

A.2 At the base of the control box, a pressure of :


- P due to the ground = 1/2 g soil H² ka
= 1/2 (1.8) . 1^2 . 0.307
= 0.2763 t/m2
- P due to water = 1/2 g water H²
= 1/2 (1) . 1^2
= 0.5 T/m2
A.3 Moment occurring at the bottom of the wall
M = (P soil + P water) . 1/3 . H
= (0.2763 + 0.5) . 1/3 . 1
= 0.259 T.m

A.4 Reinforcement of the control box wall:


- thick wall = 120 mm
- concrete decking = 20 mm
- effective thickness d = 100 mm
- Concrete quality fc' = K-250 = 20.75 Mpa
- Steel grade fy = U-24 = 388 MPa

m = fc / (0,85 .fy)
= 388 / (0.85 . 20.75)
= 22.00

Rn = M / (f b d2)
= ( 0.259.10^7) / (0,85 1000 . 100^2)
= 0.305

r = (1/m) * (1 - √ ( 1 - ((2 Rn m)/fy)) )

= (1/22.00) * (1 - √ 1 - ((2 0.31 . 22.00)/388))

= 0.0008

Aneed = r .b .d = 79.30 mm2

The minimum reinforcement for the slab is 0.25% of the


Existing concrete area, or :
Amin = 0,25% . 1000 . 120 = 300.00 mm2
A use = 300.0 mm2
Reinforcement installed f10 - 200 393 mm2 > Ause
Splitter reinforcement = 20% A = 20% 393 = 78.60 mm2
Reinforcement installed f6 - 200 141 mm2 > Ause

B CONTROL BOX BASE PLATE PLANNING

B.1 Force acting on the slab, when the control box is empty
balok sloof
balok sloof

0.76

1.5

B.2 On the base slab acts a pressure of :


- P due to water = g water . H
= 1.1
= 1 T/m2
B.3 Moment occurring at the bottom of the wall

0.76

1.50

Obtained moment :

lx 0.76 m
ly 1.50 m
ly/lx 1.97
Full pinch/elastic {1/2] 2
wlx (table after interpolation) 25.00
wly (table after interpolation) 25.00

Mlx = -Mtx = 0.0250 . Q .lx2 = 0.0250 . 1000 . 0.76^2 = 14.44 kg.m


Mly = -Mty = 0.0250 . Q .lx2 = 0.0250 . 1000 . 0.76^2 = 14.4 kg.m

B.4 Reinforcement of control box base slab:


- slab thickness = 100 mm
- decking concrete = 20 mm
- effective thickness d = 80 mm
- Concrete quality fc' = K-250 = 20.75 Mpa
- Steel grade fy = U-24 = 280 MPa

m = fc / (0,85 .fy)
= / (0.85 . 280)
= 15.88

Rn = M / (f b d2)
= ( 14.44.10^4) / (0,85 1000 . 80^2)
= 0.03

r = (1/m) * (1 - √ ( 1 - ((2 Rn m)/fy)) )

= (1/15.88) * (1 - √ 1 - ((2 0.03 . 15.88)/280))

= 0.0001

Ause = r .b .d = 7.59 mm2

The minimum reinforcement for the slab is 0.25% of the


existing concrete area, or :
Amin = 0,25% . 1000 . 100 = 250.00 mm2
Ause = 250.00 mm2
Reinforcement installed f8 - 150 335 mm2 > Ause
( wiremesh M.8)
B.5 REINFORCEMENT DRAWING

Wall reinforcement
f10 - 200

Reinforcement bars
f6 - 200

Base Plate Reinforcement


f8 - 150
C CONTROL BOX ROOF SLAB PLANNING

C.1 Roof slab data


Compressive strength of concrete, f c' = 20.75 MPa
Yield stress of steel for flexural reinforcement, fy = 280 MPa
X direction plate span length, Lx = 0.76 m
Y direction plate span length, Ly = 1.50 m
Thickness of roof slab, h= 150 mm
The slab moment coefficient for : Ly / L x = 1.97 SLAB MOMENT COEFFICIENT

TWO DIRECTIONS because Ly/Lx<2


Field x Clx = 41
Field y Cly = 12
Support x Ctx = 83
Support y Cty = 57
Table 2 with 4 pinched edges

Diameter of reinforcement used, Æ= 10 mm


Net thickness of concrete blanket, ts = 20 mm

C.2 Roof slab loading data

1. DEAD LOAD

No Dead Load Type Unit weight Thickness (m) Q (kN/m2)


1 Self weight of floor slab (kN/m3) 24.0 0.15 3.600

Total dead load, QD = 3.600


2. LIVE LOAD

Live load = 120.00 kg/m2


® QL = 1.2 kN/m2

3. FACTORISED PLAN LOAD

Factorised plan load, Qu = 1.2 * QD + 1.6 * QL = 6.240 kN/m2


4. THE SLAB MOMENT DUE TO THE FACTORED LOAD

X-direction field moment, Mulx = Clx * 0.001 * Qu * Lx2 = 0.148 kNm/m


Y-direction field moment, Muly = Cly * 0.001 * Qu * Lx2 = 0.043 kNm/m
X-direction fulcrum moment Mutx = Ctx * 0.001 * Qu * Lx2 = 0.299 kNm/m
Y-direction fulcrum moment Muty = Cty * 0.001 * Qu * Lx2 = 0.205 kNm/m
Plan moment (maximum) of the slab, ® Mu = 0.299 kNm/m

C.3 Slab Reinforcement

For : fc' ≤ 30 MPa, b1 = 0.85


For : fc' > 30 MPa, b1 = 0.85 - 0.05 * ( fc' - 30) / 7 = -
Concrete stress distribution form factor, ® b1 = 0.85
Reinforcement ratio in the balanced condition,
rb = b1* 0.85 * fc'/ fy * 600 / ( 600 + fy ) = 0.0365
Maximum moment resistance factor,
Rmax = 0.75 * rb * fy * [ 1 – ½* 0.75 * rb * fy / ( 0.85 * fc') ] = 6.0002
Flexural strength reduction factor, f = 0.80
Distance of reinforcement to outer side of concrete, ds = t s + Æ / 2 = 25.0 mm
Effective thickness of floor slab, d = h - ds = 125.0 mm
1 m wide floor slab is considered, ® b= 1000 mm
Nominal plan moment, Mn = Mu / f = 0.374 kNm
Moment resistance factor, Rn = Mn * 10 / ( b * d ) =
-6 2
0.02393
Rn < Rmax ® (OK)
Required reinforcement ratio:
r = 0.85 * fc' / fy * [ 1 - Ö [ 1 – 2 * Rn / ( 0.85 * fc' ) ] = 0.0001
Minimum reinforcement ratio, rmin = 0.0025
Ratio of reinforcement used, ® r= 0.0025
Required reinforcement area, As = r * b * d = 313 mm2
Required reinforcement spacing, s = p / 4 * Æ2 * b / A s = 251 mm
Maximum reinforcement spacing, smax = 2 * h = 300 mm
Maximum reinforcement spacing, smax = 200 mm
Spacing of stirrups to be used, s= 200 mm
Taken stirrup spacing: ® s= 200 mm
Used reinforcement, Æ 10 - 200
Area of reinforcement used, As = p / 4 * Æ 2 * b / s = 393 mm2

C.4 Slab Deflection Control


Mpa = N/mm2
Elastic modulus of concrete, Ec = 4700*√ fc' = 21410 MPa
Elastic modulus of reinforcing steel, Es = 2.10E+05 MPa
Evenly distributed (non-factorised) load on the slab, Q = QD + QL = 4.800 N/mm
Span length of the slab, Lx = 760 mm
Maximum allowable deflection limit, Lx / 240 = 3.167 mm
Gross moment of inertia of slab cross section, Ig = 1/12 * b * h = 3
281250000 mm3
Flexural collapse modulus of concrete, fr = 0.7 * √ fc' = 3.188651752701 MPa
Comparative value of elastic modulus, n = E s / Ec = 9.81
Distance of neutral line to top side of concrete, c = n * As / b = 3.852 mm
The moment of inertia of the cracked section transformed to concrete is calculated as follows. :
Icr = 1/3 * b * c3 + n * As * ( d - c )2 = 56552522 mm4
yt = h / 2 = 75 mm
Cracking moment: Mcr = fr * Ig / yt = 11957444 Nmm
Maximum moment due to load (without load factor):
M a = 1 / 8 * Q * L x2 = 346560 Nmm
Effective inertia for deflection calculation,
Ie = ( Mcr / Ma )3 * Ig + [ 1 - ( Mcr / Ma )3 ] * Icr = 9229552157844 mm4
Instantaneous elastic deflection due to dead and live loads:
de = 5 / 384 * Q * Lx4 / ( Ec * Ie ) = 0.000 mm
Floor slab reinforcement ratio: r = As / ( b * d ) = 0.0031
Time dependency factor for dead load (period > 5 years), value :
z= 2.0
l = z / ( 1 + 50 * r ) = 1.7285
Long-term deflection due to creep and shrinkage:
dg = l * 5 / 384 * Q * Lx4 / ( Ec * Ie ) = 0.000 mm
Total deflection, dtot = de + dg = 0.000 mm
Condition: dtot ≤ Lx / 240
0.00 < 3.167 ® SAFE (OK)
Tabel 2. Momen Pelat Persegi akibat beban merata kondisi tumpuan bebas dan terjepit
penuh
Momen Pelat persegi akibat beban merata (PBI'71)

Nilai Perbandingan Ly/Lx


Kondisi Pelat
Momen Pelat 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5 > 2,5

2
Mtx = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Lx 2
Mlx = 0.001.q.Lx x 44 52 59 66 73 78 84 88 93 97 100 103 106 108 110 112 125
2
Mly = 0.001.q.Lx x 44 45 45 44 44 43 41 40 39 38 37 36 35 34 32 32 25
Ly
2
Mty = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

2
Mtx = - 0.001.q.Lx x 52 59 64 69 73 76 79 81 82 83 83 83 83 83 83 83 83
2
Mlx = 0.001.q.Lx x 21 25 28 31 34 36 37 38 40 40 41 41 41 42 42 42 42
2
Mly = 0.001.q.Lx x 21 21 20 19 18 17 16 14 13 12 12 11 11 11 10 10 8
2
Mty = - 0.001.q.Lx x 52 54 56 57 57 57 57 57 57 57 57 57 57 57 57 57 57

2
Mtx = - 0.001.q.Lx x 68 77 85 92 98 103 107 111 113 116 118 119 120 121 122 122 125
2
Mlx = 0.001.q.Lx x 28 33 38 42 45 48 51 53 55 57 58 59 59 60 61 61 63
2
Mly = 0.001.q.Lx x 28 28 28 27 26 25 23 23 22 21 19 18 17 17 16 16 43
2
Mty = - 0.001.q.Lx x 68 72 74 76 77 77 78 78 78 78 79 79 79 79 79 79 79

2
Mtx = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2
Mlx = 0.001.q.Lx x 22 28 34 42 49 55 62 68 74 80 85 89 93 97 100 103 125
2
Mly = 0.001.q.Lx x 32 35 37 39 40 41 41 41 41 40 39 38 37 36 35 35 25
2
Mty = - 0.001.q.Lx x 70 79 87 94 100 105 109 112 115 117 119 120 121 122 123 123 125

2
Mtx = - 0.001.q.Lx x 70 74 77 79 81 82 83 84 84 84 84 84 83 83 83 83 83
2
Mlx = 0.001.q.Lx x 32 34 36 38 39 40 41 41 42 42 42 42 42 42 42 42 42
2
Mly = 0.001.q.Lx x 22 20 18 17 15 14 13 12 11 10 10 10 9 9 9 9 8
2
Mty = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

2
Mtx = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2
Mlx = 0.001.q.Lx x 31 38 45 53 60 66 72 78 83 88 92 96 99 102 105 108 125
2
Mly = 0.001.q.Lx x 37 39 41 41 42 42 41 41 40 39 38 37 36 35 34 33 25
2
Mty = - 0.001.q.Lx x 84 92 99 104 109 112 115 117 119 121 122 122 123 123 124 124 125

2
Mtx = - 0.001.q.Lx x 84 92 98 103 108 111 114 117 119 120 121 122 122 123 123 124 125
2
Mlx = 0.001.q.Lx x 37 41 45 48 51 53 55 56 56 59 60 60 60 61 61 62 63
2
Mly = 0.001.q.Lx x 31 30 28 27 25 24 22 21 20 19 18 17 17 16 16 15 13
2
Mty = - 0.001.q.Lx x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

2
Mtx = - 0.001.q.Lx x 55 65 74 82 89 94 99 103 106 110 114 116 117 118 119 120 125
2
Mlx = 0.001.q.Lx x 21 26 31 36 40 43 46 49 51 53 55 56 57 58 59 60 63
2
Mly = 0.001.q.Lx x 26 27 28 28 27 26 25 23 22 21 21 20 20 19 19 18 13
2
Mty = - 0.001.q.Lx x 60 65 69 72 74 76 77 78 78 78 78 78 78 78 78 79 79

2
Mtx = - 0.001.q.Lx x 60 66 71 74 77 79 80 82 83 83 83 83 83 83 83 83 83
2
Mlx = 0.001.q.Lx x 26 29 32 35 36 38 39 40 40 41 41 42 42 42 42 42 42
2
Mly = 0.001.q.Lx x 21 20 19 18 17 15 14 13 12 12 11 11 10 10 10 10 8
2
Mty = - 0.001.q.Lx x 55 57 57 57 58 57 57 57 57 57 57 57 57 57 57 57 57

Catatan:
= Terletak bebas
= Terjepit penuh

You might also like