1. Introduction
The AMI Project shall be implemented in the Project Area (contiguous or non-
contiguous) & all consumers shall be smart metered to enable complete energy accounting
with zero manual intervention. The Bidders shall visit the project area before designing the
AMI and quoting the tender to clearly understand the site conditions including feasible
communication options.
2. Project Area
The Project Areas for AMI deployment are in the places of GE (N) Bangalore, GE (S)
Bangalore and GE (C) Bangalore in the AOR of CWE Bangalore.
The basic functionalities of the Smart Metering System defined by CEA are as
below:-
a) Remote Meter data reading at configurable intervals (push/pull).
b) Data logging and reporting
ANNEXURE-I
AMI solution components of different makes (Make neutral) must comply as per IS
15959 part 1 & 2 to have interoperability of different makes. The AMI solution design shall
be based on cross-functional components or subsystems and shall be implemented in such a
way that there is an opportunity for reuse. The integration architecture shall be based on the
concept of a service, so all the applications of the AMI solution are able to integrate without
any complexity. AMI system is envisaged as a service driven architecture at the core of it.
AMI system feature can be accessed via any user interface (internal of 3rd party applications)
which shall work on top of these services. Adoption of DLMS standards is of paramount
importance for the robust and scalable AMI System. Data access must be always
through services, no application will access AMI data directly from the storage layer or data
access layer. For every internal data access also (access between various modules) there will
be services and no direct access will be there to ensure the AMI system is scalable and
secure.
Smarts meters shall be in conformity to IS 16444 Part 1 & IS 15959 part 2 amended
up-to-date. It is mandatory to have BIS identification mark (ISI Mark) on the name plate of
the Smart Energy Meter. The AMISP has to furnish valid BIS certifications & valid in house
NABL lab certification from the manufacturer before the supply of meters.
Smart energy meters shall be capable of measuring electrical parameters i.e. with the
ability to measure electricity consumption with bill through Auto Email to individual
customers in monthly basis and SMS in monthly basis with separate user ID &Smart Mobile
App provisions.
In addition, energy meter shall have capability to configure in prepaid or post-paid
functionality remotely, as and when needed.
4.1.1 Basic Features of AC whole current, single phase, 2 wires Smart Energy Meter&
Three phase, 4 wires Smart Energy Meter:
The Smart Meter would have the following minimum basic features-
4.1.2 Communication: Meter shall have the ability to communicate with Head End System (HES)
as per the communication technologies (RF / GPRS 4G/5G) mentioned in IS16444 Part 1 in a secure
manner. The selection of communication technology should be as per the site conditions and as per
design consideration of implementing agency to achieve the best performance. In case of a GPRS
based meter, the meter shall accommodate a SIM card /e-SIM of any all service providers.
(Should not restrict to single service provider) In case of Plug-in type communication module, the
ANNEXURE-I
meter shall log communication module removal /non-responsive event with snapshot. Data
communication shall be in the bidder’s scope upto end of the contract period.
Further, the Meter should display high resolution energy values with resolution of 3
digits before decimal and 2 digits after decimal in push button mode.
The meter’s display should return to default display mode (continues auto scroll) if
push button is not operated for more than 10 seconds. (The order of display may be revised
as per requirement of the utility). Meter display should not go into sleep mode during
Power-On condition.
4.1.8 Meter base & cover shall be as per IS 16444 Part1 / IS 13779. The meter Base &
cover shall be break to open design. The material for meter base and cover shall be made of
high-grade Polycarbonate. The meter Base & cover shall be ultrasonically welded /
chemically welded or other suitable bonding technology and it will not be possible to
remove the cover from the base without evidence of damage. Terminal block & cover shall
be as per IS 16444 Part 1/IS 13779 and meter suitable for IP 54
The meter shall be mounted type. The Meter should have three fixing holes, one at
top and two at the bottom. The Top hole should be such that the holding screw is not
accessible to the consumer after fixing the meters. The lower screws should be provided
under sealable terminal cover.
4.1.12 Suitable Meter Box shall be provided with each meter and the material of the Meter
Box should be such that it does not hamper communications. It should be preferably
transparent.
It consists of two parts - the Near Area Network (Localized to meters in the field) and
the Wide Area Network (GPRS/Optical Fibre to centralization-this communication
infrastructure enables two-way transmission of data between smart meters and MES utility).
There are several different ways this field-based communications infrastructure can be
implemented, depending on the metering system selected.
A suitable Network Management System (NMS) functioning within the Head End
System (HES) is to be provided which is responsible for the establishment and management
of all networks, the discovery of all nodes once deployed in the field, the overall system
management as well as security management of devices. The proposed NMS shall facilitate
following activities:
The NMS software shall have a simple browser-based user interface to provide all the
pertinent information about the system. The NMS shall not impact the availability and
performance of AMI applications and shall load not more than 1% of network bandwidth and
shall have secure communication. The Network Management Software shall have following
functionality:
a) It shall maintain performance & error statistics, and present this information via
displays, periodic reports and on-demand reports.
b) Apart from real-time monitoring of critical network devices, the above information
shall be collected and stored at user configurable periodicities i.e., 5 minutes to 60
minutes. The NMS shall be capable of storing the above data for a period of one (1)
year at an interval of 5 minutes.
c) It shall maintain a graphical display for connectivity and status of peripheral devices.
The monitored devices shall be configured to send SNMP notifications, and the
graphical element representing the device shall change to a different colour depending
on the severity of the notification received.
d) It shall issue alarms when error conditions occur.
e) The period over which the statistics are gathered shall be adjustable by the user and the
accumulated statistics shall be reset at the start of each period.
f) The statistics shall be available for printout and display after each period and on demand
during the period.
g) In case more than one technology of AMI (example PLCC and RF between Smart
Meter & DCU) deployed in the field. It shall maintain statistics on the performance and
availability of node being delivered per AMI technology.
The AMI Network shall have adequate cyber security measures not limited to the
measures as described below. The network security would be extended to all the interfaces
also.
Secure Access Controls: The system shall include mechanisms for defining and controlling
user access to the applications environment. Best practices from enterprise security including
password strength, password aging, password history, reuse prevention etc. must be followed
for access control.
Authorization Controls: A least-privilege concept such that users are only allowed to use
or access functions for which they have been given authorization shall be available.
Logging: Logs must be maintained for all attempts to log on (both successful and
unsuccessful), any privilege change requests (both successful and unsuccessful), user actions
affecting security (such as password changes), attempts to perform actions not authorized by
the authorization controls, all configuration changes etc. Additionally, the access to such logs
must be controlled in accordance with the least-privilege concept mentioned above, so that
entries may not be deleted, accidentally or maliciously.
ANNEXURE-I
The overall cyber security policy and implementation shall account for:
a) Prevent unauthorized users from reading or writing data or files, executing programs
or performing operations without appropriate privileges.
b) Document all user sign on procedure
c) Record all network traffic for detecting unauthorized activity, unusual activity and
attempts to defeat system security (AMISP to propose and document what
constitutes normal activity/traffic)
d) A user authentication scheme consisting of at least a user identification and password
shall be required for the user to request a connection to any network node.
e) Graphical User Interface (GUI) to provide role-based access based on user identity
and user role. Shall have following types of users:
i. Administrator
ii. Operator
iii. Field staff
iv. Viewer/Guest
The Data Concentrator Unit is a gateway for communication of data between the
Smart Meters and the HES enabling continuous/periodic meter-read and control. DCU shall
exchange data from Smart Meters on RF / PLCC communication and with HES on WAN.
In this type of communication network, different network nodes including end points
(Smart Meters) shall interconnect with each other using RF mesh network and they shall
communicate with nearby gateways/ routers to transfer the data to access points. If any
gateways/ routers/ repeaters/ access points fail, then nodes connected on that device shall
automatically reconfigure the mesh with available nearby nodes. Thus it shall have dynamic &
self-healing capability.
a) Each node shall keep a track of best available nearby nodes or access points.
ANNEXURE-I
b) All the communication network equipment shall be as per WPC (Wireless Planning &
Coordination Wing) guidelines, Government of India for operation in licensed /
license free frequency band as permitted by WPC/Statutory Bodies as applicable.
c) It shall be secure enough to avoid all cyber threats and it shall support remote
firmware upgrading. It shall also ensure secure communication of data to HES.
d) The equipment shall be weatherproof, dustproof and constructed for outdoor
installation on poles (minimum rating: IP65). A suitable mounting provision shall be
made for the equipment.
e) Gateway/ Router/ Access Point shall have battery with backup for 1(one) hour for
normal meter reading, to push tamper event, carry out on demand reading and the
network health status/ connectivity continuity & check etc. during battery operations
also. It should have the suitable feature to send power outage and restoration message
to the HES even during battery back-up.
f) It shall be able to configure the communication with underlying nodes/end points and
it shall have Wide Area Network (WAN) connectivity to the HES through suitable
means. It shall also support on demand read and ping of individual/group of meters.
g) It shall push events such as tamper, power off etc. to HES immediately on
occurrence/receipt from field devices/meters.
h) It shall communicate with gateways/ routers/ nodes/ end points/ access points on RF
mesh network (Unlicensed or Licensed frequency band as permitted by
WPC/Statutory Bodies in India as applicable).
i) It shall periodically monitor meter reads/downstream commands and shall retry and
reconnect in case of failed events/reads.
j) After power Interruption, on restoration of power supply, it shall establish
communication with underlying devices as well as upstream application (HES)
automatically.
k) Access point shall facilitate recording of minimum of the following events at HES
(for seven (7) days):
i. No of lost packets
ii. Retry attempts
iii. Missed periodic reading
iv. Failure to connect
v. Tamper events
l) It shall be capable to handle interval data of suitable nos. of any type of Smart Meter.
Access point shall be able to acquire and send data to HES for full capacity (No. of
meters/field devices it is designed for) within a suitable time period to achieve the
performance level.
m) Gateway / Router / Access point shall support remote firmware upgrades as well as
remote configuration from the Network Operation cum Monitoring Centre.
n) The Gateway / Router / Access Points shall have provision to maintain the time and
date information and shall always be in Time synchronization to the HES server via
NTP to sub second accuracy. The Gateway / Router / Access Points shall support time
distribution to each Mesh Node.
The main objective of HES is to acquire meter data automatically avoiding any human
intervention and monitor parameters acquired from meters. The contractor shall provide a
HES which is suitable to support the collection and storage of data as per performance level
for a defined no. of Smart Meters with facility of future expansion as per the requirement
specified in the tender.HES includes supply of all the requisite software and hardware to
achieve the defined functionalities of AMI.
HES shall be developed on open platform based on distributed architecture for
scalability without degradation of the performance using additional hardware. The scalability
shall ensure the ability to handle applicable workloads including the following: An indicative
list of parameters is provided below:
(i) Up to 7500 numbers of meters installed
(ii) 5/15mins interval meter reads
(iii) Up to 7500 users requesting data from meters
(iv) Other events and statuses coming from meters
The HES shall be on cloud/ Local server enabled and support deployment with high
availability clustering and automatic load balancing that ensure hardware as well as
application failover. Adequate data base and security features for storage of data at HES end
to be ensured.
a) On power up after installation, Smart Meter shall register itself automatically into the
HES along with its metering profile. The HES shall store meter profile status by meter
type, hardware & software versions, device IDs, logged in / logged out details etc.
b) Upon deployment and establishment of communication, it shall be possible for field
level end device nodes (NAN/WAN) like Router/Gateway, Access Point, DCU to
have self-discovery and registration.
c) Acquisition of meter data on demand & at user selectable periodicity. On demand
meter read may be for single meter (uni-cast) or for a group of meters (multi-cast).
d) Two-way communication with meter/ DCU & Maintain time sync with them.
e) Signals for connect & disconnect of switches present in end points such as meters.
This facility shall be provided for both single meter (uni-cast) as well as for a group of
meters (multi-cast).
f) Audit trail and Event & Alarm Logging.
g) Ability to redirect messages including configuration commands from the Meter Data
Management System (MDM) in order to reach the desired meter.
h) HES shall hold / Store raw data for defined duration (minimum 3 days) before it is
transferred to the MDM.
i) Handling of Control signals / event messages on priority.
j) Manage time distribution to ensure that nodes / meters always have an accurate Real
Time Clock (RTC) using Network Time Protocol (NTP) servers. The time distribution
mechanism shall take into account the network latencies.
k) Setting of Smart Meter configurable parameters.
l) Critical and non-critical event reporting functionality.
m) Device management functionality to get periodic updates from devices on health
check, hardware & firmware version, location mapping etc.
ANNEXURE-I
n) The data collection and computation for the purpose of SLA penalties (as mentioned
in the following
a) Event log for node‘s (meter) events such as tamper/power failures etc.
b) Data not received from nodes/end points
c) Relay does not operate for connect / disconnect
d) Communication link failure with nodes/end points
e) Network Failure
ANNEXURE-I
f) Power Failure
Non-Critical Reporting---
HES shall report and keep record of following communication failure events:
g) Retry attempts
h) Missed periodic reading
i) Failure to connect
The Meter Data Management system (MDM) shall support storage, archiving,
retrieval & analysis of meter data and various other operational systems along with validation
& verification algorithms. The MDM shall be a scalable and commercial-off-the-self (COTS)
product. It shall act as a central data repository with interactive dashboard. MDM shall have
capability to import raw or validated data in defined formats and export the processed and
validated data to various other systems sources and services in the agreed format. It shall
provide validated data for upstream systems such as billing, analytics, reporting, etc. in the
formats as desired by MES authorities.
The illustrations of key use cases to be enabled by the AMI service provider are as
under:
2.1 Command from Billing system triggered Billing MDM / Meter Number, reading date &
and send to MDM / HES for collection of System HES time, kW, kVA, kWh, kVAh, PF,
Monthly billing Data Non-critical Event Code / Date
2.2 At scheduled frequency HES should pull HES Meter Meter Number, reading date &
the monthly meter data from Smart time, kW, kVA, kWh, kVAh, PF,
Meter over the communication channel Non-critical Event Code / Date
2.3 Meter should send the data to HES. Meter HES Meter Number, reading date &
Provision for retrial should be there if time, kW, kVA, kWh, kVAh, PF,
Meter data is not collected within time. Non-critical Event Code / Date
2.4 HES should decrypt and validate the HES MDM Meter Number, reading date &
data collected and send to MDM time, kW, kVA, kWh, kVAh,
PF, Non-critical Event Code /
Date
2.5 MDM should send the required MDM Billing Meter Number, reading date &
parameter to Billing system for Monthly Engine time, kW, kVA, kWh, kVAh,
Bill calculation PF, Non-critical Event Code /
Date
5.2 High priority events reach MDM for HES MDM Meter Number, event date &
further action. time, event Code /description
5.3 Share with WFM to Notify utility MDM WFM Consumer number, Meter
personnel for site inspection Number, Tamper code,
address
5.4 On analysis and detection of valid Meter HES/ Consumer number, meter
tamper event or malfunction, the tamper MDM number, action to be
event must be sent / pushed by the meter triggered (disconnect), action
to the HES /MDM date & time
5.5 HES sends disconnect command to HES Meter Meter Number, action
meter (disconnect)
5.6 Tamper event shared with CIS/CRM. MDM CIS / Meter Number, event date &
Billing determinants are updated for CRM time, event Code /description
tamper invoicing
5.7 Meter re-connection order once tamper MDM HES Meter number, action (re-
issue is resolved connect)
5.8 HES sends re-connect command to HES Meter Meter Number, action (re-
meter connect)
Note :- CIS/CRM --- Consumer Information System/Consumer Relationship Management
13.7 Request instant, interval & events data MDM HES → Meter Number, Reading date
from meter Meter & time, reading params
(kWh, kVAh, kW etc.)
13.8 Acquire instant, interval / events data HES MDM Meter Number, Reading date
from meter by HES which then reaches & time, reading params
MDM system. (kWh, kVAh, kW etc.)
13.9 Once meter remote read verification is MDM Billing / Prepaid consumer profile
ANNEXURE-I
Email/SMS
Gateway
19.4 System resolves request & updates CIS/ Portal/
consumer records CRM App→UI,
CIS/CRM
19.5 System closes SRN CIS/ Email/SMS
CRM Gateway
20. Consumer Complaints
20.1 Consumer logs into Portal/ App Portal/ CIS/CRM
App
20.2 Consumer registers complaint UI CIS/CRM Specific complaint
MDM shall maintain& track information and relationships between Smart meter and
consumer and also maintain the history of in-service asset location throughout the device life
with start and end dates associated with each in-service location reference as under---
- Meter location ( House / shop No, Colony , address etc.)
- Consumer information ( Name/Code No, Account, ID etc.)
- Meter Details (1Ph/3PH, Meter No, with or without Relay)
ANNEXURE-I
- Meter configuration (Demand Integration Period, Load Profile Capture Period etc.)
- GIS Information ( Longitude, Latitude, connection with feeder/Tr/Pole etc.)
- Ability to report and log any damage/deterioration in the meter
a) The MDM shall also support device lifecycle management from device registration,
installation, provisioning, operations and maintenance to decommissioning etc. The
MDM shall generate exceptions for meter or modules not delivering the correct meter
data after installation.
b) The MDM shall provide a reconciliation report that identifies the meters that have
been installed but not communicating for a designated (configurable) period. MDM
shall generate reports on the number of meters installed in comparison to the number
of meters successfully communicating.
a) The MDM shall have the ability to manage at minimum 15 minute interval data.
b) The MDM shall accept input, process, store, and analyze Meter data from HES and
meter data collected through handheld meter reading instruments and manual meter
reads in case of 07 day failure of automatic data transfer such as communication
failure etc.
c) The MDM shall provide meter data as per schedule and on demand meter read and
pinging of meter.
d) The MDM shall provide storage and retrieval of all collected Meter Data, events and
alarm. It shall have capacity of storing minimum five year data via archiving. The
archiving of data should be done at a suitable frequency and all data older than 60
days should be archived. AMISP’s solution should describe the process of archiving
and restoration from the archive.
e) Correctly track & resolve energy usage across meter changes with no loss of
individual meter data.
f) Provide complete history and audit trail for all data collected from meters including
commands sent to meters and other devices for 30 days (configurable period).
g) Handle special metering configurations such as net metering/pre-paid
metering/multiple meters at same premises.
h) The AMISP shall ensure data integrity checks on all metered data received from data
collection systems.
a) Registered Read Data including register reads, daily billing cycle, as well as derived
billing determinants such as TOU
b) Interval Data channels with variable intervals and variable units of measure.
c) Calculated Data that is derived or computed such as billing determinants and
aggregated loads.
d) Event data storage of all collected event and alarm data from meters, network
equipment, and MDM itself.
e) The MDM shall flag, alarm and trigger as and when abnormalities observed in
estimating processes or any anomaly occur in cumulative register read, TOU register
read, Demand register reads etc.
ANNEXURE-I
f) All data shall be transferred to billing system after meter data validation and
estimation
g) The MDM shall maintain both the original received raw data in a non- manipulated
state, in addition to VEE data.
h) Once the MDM receives meter read data, the VEE process occurs in real-time and the
post-VEE data is then immediately available to user or external systems.
i) The MDM shall be able to automatically flag data changes from manual edits, VEE
(Validating, Editing and Estimating) rules and data source corrections and
electronically generate audit trail with timestamps and user-ids.
i. Total Consumption
ii. Consumption in different time blocks for TOU billing
iii. Maximum Demand (in kW and kVA)
iv. Number of tamper counts
v. Average power factor
c) The MDM shall have the ability to properly account for special metering situations
such as check metering, sub metering, prepaid metering etc.
d) The MDM shall have the ability to properly account for special situations such as
curtailment requests, demand response scenarios etc.
e) The MDM shall have the ability to facilitate implementation of automatic
compensation payments.
The MDM with the help of the corresponding HES, should be able to switch the Smart Meter
between prepaid and post-paid modes for any consumer by a simple change in configuration
of the Smart Meter firmware remotely including enrollment/setup of new consumers. The
following prepaid functionality shall apply:
f) The system shall periodically monitor the energy consumption of prepaid consumer
and decrease the available credit based on consumption. For this purpose, the MDM
shall fetch billing data (kWh/kVAh) consumption and MD at configured intervals (at
least one hour) from the prepaid meter. The raw billing data shall be subjected to
standard VEE rules before being used to update recharge balance with the help of
applicable tariff slabs. The credit balance is updated into meter at re-charge time.
g) The prepayment application shall use determinants such as minimum fixed charges,
TOU tariffs, slab rates, duties & surcharge while calculating consumer credit/balance.
Fixed charge shall be deducted on daily basis irrespective of the consumption, even
after disconnection of supply and adjusted in the next transaction.
h) The prepayment application should be able to automatically apply different TOU
tariffs for future date lines, while calculating consumer credits.
i) The system should send connect/disconnect command based on available credit as per
notified rules & regulations.
j) The system should send low-credit notifications to the consumer when their balance
approaches a pre-configured threshold. Alerts shall initiate on every recharge, low
credit and load connection/disconnection. The alerts shall be posted on the consumer
web Portal/ App in real time and sent through SMS and email. Consumer should also
be alerted through other mechanisms such as one-time alarm / beep from the meter,
LED blinking, message, etc.
k) It shall be possible to configure an “emergency” credit limit in INR as well as day
terms. This emergency credit shall be used as reserved amount that is consumed when
consumer credit is exhausted. The credit amount shall be adjusted in next recharge
transaction.
l) It shall be possible to configure certain prepaid consumers where auto-disconnections
shall not happen due to negative credit according to set protocols.
m) The pre-payment function as part of MDM shall also have a facility to configure
arrear recovery mechanism to recover arrears from a consumer.
a) Ability to capture and log data exceptions, problems and failures and to generate
management reports, provide trend analysis, automate generation of service requests
and track corrective actions.
b) Ability to group, prioritize, filter and send system generated alarms and events to
predetermined email addresses, cellular text messages to phone numbers/ SMS/
consumer care etc. Alternatively, these alarms/ alerts may be routed to utility’s Work
Force Management (WFM).
c) Exception Generation - MDM shall generate exceptions based on configurable
business rules including but not limited to the following:
i. Meter tamper alerts
ii. Communication module health alerts for meter/DCU
iii. If the consumption is less/more than pre-defined average consumption
iv. Negative Consumption (not for net-metering)
v. Power outage indications received from the Smart Meter
a) The MDM shall generate service orders based on configurable rules for various
events and alarms such as stop meter, tampers, problem in communication
networks, etc.
b) MDM shall send service orders via SMS, email, etc. with the email addresses /
phone numbers being configurable. MDM shall receive feedback on action taken on
the service order and track the status of service orders until resolution.
c) Service order tickets could be generated by MDM but processed and closed under
jurisdiction of the HES-NMS combine. If the utility already has a separate
Workforce Management System (WFM), then the service order tickets can be
routed.
4.4.9 Revenue Protection Support:
a) Ability to analyze meter tampering flags, power outages, usage trends and usage
profiles to identify potential energy diversion situations, and produce daily reports,
monthly reports and service order requests for investigation.
b) The business rules for revenue protection alerts shall be configurable via a user-
friendly interface.
c) The MDM shall filter out revenue protection alerts that may be caused by field
activities if the field activity information is provided to the MDM.
d) The MDM shall support the analytics/ investigation (i.e., view current and historical
usage patterns) to validate suspected revenue protection issues.
The billing module would collect the date from the meter data management module,
calculate billing determinant and make energy data / billing data available to admin and end
user.
Occupation/vacation module shall be provided & the system shall support based on
the unit categories. The system shall support automatic data capture on occupation and
vacation events.
The system would include features of energy accounting, the system would to able to
account for total energy block wise, facility wise and would also allow calculations of the
unaccounted energy in case total energy meter is also available.
User interface for utility shall have ability for at least the following functionality:
a) Compare total energy costs on one rate schedule vs. one or many alternative rates.
b) Enable the user to see how different options within a rate affect costs.
ANNEXURE-I
c) Enable the user to see how adjusting load or consumption levels or shifting them to
different time periods influences costs.
d) Display meter data at a user defined configurable cycle that allows authorized users
to view energy usage patterns and the data behind them for selected consumers.
e) Allow authorized users to view metered data, initiate and view reports, modify
configurations, and initiate and update service requests.
f) Display the energy usage profile for a single meter or group of meters. The load
profile shall illustrate energy consumption and peak demand in user defined
intervals for a user-specified time period.
g) Display the energy usage profile for a single meter or group of meters according to
Time of Use (TOU) tariff.
h) The User Interface (UI) shall support a configurable utility dashboard for
Operations and Utility Management.
i) Access to a minimum of three (3) years of historical energy usage and meter reads
through the UI.
j) Clearly and visually distinguish between metered, estimated, allocated and
substituted data.
k) User management with roles and access rights.
l) Graphical User Interface (GUI) to provide role-based access based on user identity
and user role. It Shall have following types of users:
i. Administrator
ii. Operator
iii. Field staff
iv. Viewer/Guest
m) Configure the look, feel, and functionality of the MDM in accordance with business
needs, business processes, and business conventions. (E.g., GUI, content, look and
feel of screens, validation rules, exception handling, etc.).
n) Ability to set up alarm and event notifications that can be directed to a combination
of configurable email addresses, cellular text messages.
o) UI shall enable viewing of the credit amount updated in MDM for prepaid
consumers.
p) Option to send messages and notification to select consumers or selected category of
consumers.
q) Facility to enable or disable existing functionalities/sections of App/Portal for
consumers use.
r) Consumer views to be available to Utility consumer Service Executive also except
payment card/bank information.
s) Authorized representative to be enabled for consumer engagement analytics. The
analytics to be configurable/ generated with minimal database skill and nil
programming requirements.
t) Representative to be able to generate various reports at different intervals the various
reports as defined. It shall be also possible to export the report data in multiple
formats such as XLS, CSV format, etc.
u) Provide consumer interactions history to enable efficient consumer complaints and
queries resolution with consumer information in single screen.
Consumer portal and mobile application shall cover all consumer categories and
category specific features as applicable prior to operational Go-Live. These apps shall have
provision to enable features required to facilitate consumer participation in Demand
ANNEXURE-I
Response programs which the utility may choose to roll out in future. The consumer web
portal and the mobile application (for Smartphone and tablet devices using latest and
commonly available browsers and operating systems and platforms) shall provide consumers,
ready access to features extended by MDM. The solution shall integrate via a user-friendly
graphical interface. It shall facilitate self service capabilities such as usage management,
billing, service requests, participation in energy efficiency programs etc. It shall be noted that
the Consumer Portal / App acts as the bridge between the consumers touch point and the
existing utility Customer Care and Billing Systems. It does not replace these legacy systems
in place. Following features shall be supported by Portal / Mobile app:
a) The mobile app and web portal shall support all device form factors such as mobile,
tablet, desktop etc. by recognizing the device details automatically.
b) It shall be OS agnostic to operating system and devices (iOS, Android, etc.)
c) It shall work on all standard browsers such as Internet Explorer (IE), Chrome, Safari,
Firefox etc.
d) The application should be modular and scalable a COTS product.
e) The application should be made in India for better user experience.
f) It shall support Hindi& English languages.
g) The user experience of the citizen on the Portal and App shall be similar in terms of
look and feel, navigation, menu and access to preferences and other data.
h) Menu should have navigation options, not limited to, Home, Settings, Recharge,
notification preferences, usage rates, change password, terms and conditions, privacy
policy, sign out.
i) It shall have search functionality across all the pages.
Software patches, updates, and version upgrades, when they become available for general
release, should be part of ongoing support and maintenance services.
Web portal and Mobile app for consumers should have minimum following
functionalities:
a) The consumer portal/app shall have a landing Home page. This page shall provide a
brief description about the Utility, any promotional features or advertisement for
special programs can be placed in this page. Login Component is provided, and
registered users may login using their username and password. New Users can also
register by clicking on the First Time Users Register link. The Forgot Password link
helps the user to retrieve their password. New users can register by providing their
personal information and setting up of security answers. Forgot passwords can be
retrieved or reset using OTP through registered mobile number or through email
address. The registered users can change their password and account information as
well as registered mobile number through OTP feature.
b) The consumer portal/app shall provide consumers with access to consumer ID, meter
ID, meter type and name plate details, besides other account information such as
account name, address, balance, due, status etc. Any status message pertaining to the
account/s viz. alerts/actions shall be displayed here. It shall also provide current and
historical consumption in graphical formats for at least 12 months. A more detailed
analysis can be provided in a tabular format listing meter reading date, reading,
consumption, charges, selected period etc. Consumers shall be able to view interval
data, outage flags, voltage, power quality indications, existing tariffs and incentives
ANNEXURE-I
for selected period. Information about different consumer engagement programs shall
also be displayed here.
c) The portal/app shall have the ability to provide option for registering in online/paper
billing to the consumer. There shall be a bill summary page that shall display bill
information in summary and also option for detailed view and download in pdf format
if required by consumer. The use shall be able to pay bill for single and multiple
accounts.
d) The portal/app shall be integrated with existing helpdesk of the utility and have the
ability to provide option for recording service requests/complaints lodged by the
consumer as new connection, disconnection, load change, category change, meter
shifting etc. The user can view the service request status. The user can register
complaints viz. power failure, faulty meter, streetlight outage etc. There shall be
option to track status of service requests.
e) Mobile App and Web Portal shall facilitate Chat-bot functionality of the utility’s Help
Desk. The portal/ App shall support configuration of notification types via email/
SMS/ message of configured alarms & events.
f) The information on consumer identification no., meter ID, name plate details, make,
type i.e., 1 Phase or 3 Phase, etc. (as per requirement of Utility) shall be updated in
HES, MDM, and the consumer portal/app.
g) The consumer Portal/ App shall have the ability to provide the consumer near real
time online views of both usage and cost differentiating high energy usage periods,
helping consumers to understand electricity usage and cost information, alerts and
notifications and energy savings tips with different levels of detail. The Portal/ App
shall support the view for past electricity usage, last week’s, yesterday’s, current days
or other period etc. as per selection as well as voltage and power quality indications.
The portal/ app shall provide user friendly access to consumer for their data via
graphs and charts and can download the data into a spreadsheet.
h) The portal/app shall provide option to the consumer to view/download online bill.
There shall be a bill summary page that shall display bill information in summary and
option for detailed view and download in pdf format. The user shall be able to pay bill
for single and multiple accounts.
i) The portal/app shall also provide platform for implementation of peak load
management functionality by providing existing tariff & incentives rates, participation
options etc. The portal/app shall also provide consumers with interval data, flags,
voltage, power quality indications etc. Show outage information in map view.
j) There should be different UI and landing pages for different type of consumers as per
the need of utility.
k) User interface to consumer Portal/ App to access consumer‘s data from MDM for all
authorized consumers shall have ability for at least the following functionality:
i. View metered data, monthly average usage, current monthly consumption,
maximum demand and other reports
ii. View data according to Time of Use (ToU), day, week, month, year and
season etc.
iii. Update profile information such as mobile number/email etc.
iv. Guest user account/multi-user account access facility for consumer
convenience
ANNEXURE-I
The AMI System can be hosted & managed either on local dedicated rack servers
with standby servers (to be installed at NOMC) or Government of India Cloud (MeghRaj) or
any MEITY approved CSP etc.).
4.6.1 If local dedicated rack servers are opted, Capacity of the servers and accessories are to
be provided by the contractor and it shall be commensurate to number of the Smart Meters to
be connected to the servers and it’s response shall be fast enough to achieve specified
response time of various activities as mentioned in this document. It shall also have
expansion capacity of 25% to cater for future requirements, if any.
Minimum Server specifications --- 03 servers of 64 Core, 128GB RAM, 1TB SSD
Hard Disk for each server.
The cloud data centre shall have to comply with requirements of tier III category which applies to
a concurrently maintainable site infrastructure with redundant capacity components and multiple
independent distribution paths serving the critical environment. All IT equipment shall be dual
powered. The following general conditions will apply:
a) Only GI (MeghRaj) cloud services or Meity empanelled Cloud services should be used.
b) One of the most critical issues in the Cloud Service implementation is the security of the data. It
is the responsibility of the Bidder to define the security services that need to be implemented for
their workloads depending on the nature of the applications / data hosted on the cloud.
c) Bidder need to ensure that the CSPs facilities/services are compliant to various security
standards and should be verified by CERT Auditors of Armed forces
d) CSP should suitably address all the potential risks and issues in cloud implementation including
data security and privacy, increased complexity in integration with existing environments, vendor
lock-in, application portability between different platforms, exit management / Transition-Out
Services etc.
e) The Bidder shall be responsible for providing the cloud data center services. It shall be up to the
Bidder, to identify the critical service agreements with the concerned cloud data center provider
the better services without any interruption.
ANNEXURE-I
Necessary Room(s) for setting up Network Operations and Monitoring Centre to cater
to the needs of the AMI network operations team shall be provided by the CWE at the station.
Necessary desktop for workstation monitoring & control centre shall be deployed as detailed
in this specification.
The Room(s) to be arranged by the utility shall be properly illuminated, and adequate
for at least two operator workstations. Required power supply required for AMI Hardware
shall be provided by MES at one place in the room and further distribution in the room will
be in the scope of the contractor. Provision of Split ACs as per Room and equipment load
shall be provided and maintained by the contractor. Cost of such work to be carried out by
contractor in the NOMC is deemed to be included in the scope of work.
AMISP/contractor shall establish connectivity between the workstations located at the
NOMC with that of the cloud-based MDM-HES system. In addition, the AMISP shall
establish connectivity between the cloud-based MDM system with utility‘s existing Billing
system. All the necessary Hardware and Software along with security patches/ software’s
required for setting up NOMC are to be provided by the contractor.
The network operation and monitoring centre shall be equipped with the following
minimum hardware components:
a) Two numbers 17” Operator/Supervisor workstations
b) A dual redundant 1 Gbps local area network
c) Internet router with at least 48 no’s 1 Gbps LAN ports and redundant at least 2 Gbps
internet ports supporting IPsec, and SSLVPN capability
d) Firewall and intrusion protection system
e) One video display system of at least 70-inch diagonal with laser light source HD cube
(DLP technology) supported by
i. Dual power supply
ii. IP based control options and
iii. Display Port, DVI, HDMI and Analog D-Sub signal interfaces
f) One A3/A4 size laser jet B/W printer with LAN interface
g) One A4 size ink jet color printer with LAN interface
h) One dual redundant online UPS to support the load of the above-mentioned
equipment with minimum 2 hours backup
i) 2 Gbps internet connectivity
In addition to above, One Number of work Station along with B/W A4 Laser printer
shall be provided to Each GE formation or it’s BSO at a specified place along with Internet
connection
The minimum technical specification and requirement to be followed for hardware equipment
is as per below:-
Firewall(s)
Firewalls should be properly configured to segregate networks into different
1. segments. The following strategies shall be followed for the secure configuration of
firewalls:-
a) Clean up rule
b) Place a "Deny Any-Any" rule at the end of the rule base.
c) Never create an "Allow any-any" rule.
d) Allow rules should be created only for required services
e) This will result in all traffic being disallowed unless specifically allowed.
f) Lockdown /stealth rule
g) All Traffic destined for the firewall itself should be disallowed
h) Place anti-spoofing rule as per RFC 2827
i) Enable DoS / DDoS features on the Firewall
j) Enable application-level filtering of firewall
Firewall with UTM solution
GENERAL REQUIREMENTS
1. The proposed system must be appliance-based and rack-mountable
2. All UTM features like Firewall, Anti-Virus, Anti-Spam, Web & Application filtering up to
Layer 7. IPS.DNS
ANNEXURE-I
HARDWARE REQUIREMENTS
1. The proposed solution must be based on ASIC or Multicore Parallel Processing
Architecture
2 The proposed solution should support an inbuilt HDD 250GB for storage or an
external device for Logs and Reports to meet the UTM Features.
3. The proposed solution should have a minimum 8 x Copper GbE ports &
Expandable to 24 x Copper GbE ports for Future Expansion & Segregation of
Zones.
4. There should be a provision to Load Fiber modules (1G & 10G) for future
Enhancements.
5. The proposed solution should have a minimum of 2 USB ports.
PERFORMANCE REQUIREMENTS
1 The proposed solution should meet the following performance criteria & should
mandatorily produce valid references for the same at the time of bidding.
a. Firewall Throughput of 20,000 Mbps or Above
b. Concurrent sessions: 3,200,000 or Above
c. New sessions/second: 1,00,000 or Above
d. IPSec VPN throughput: 1,300 Mbps or Above.
e. SSL VPN throughput: 500 Mbps or Above
f. Antivirus throughput: 2,900 Mbps or Above
g. IPS throughput: 4,000 Mbps or Above
h. UTM throughput (Firewall, IPS, Web & App, Filtering and Anti-virus): 1,700
Mbps or Above.
UTM FEATURES REQUIREMENTS
1. The proposed solution should facilitate the application of UTM policies like AV/AS,
IPS, Content filtering, Bandwidth policy and policy -based routing decision on the
firewall rule itself, Also, UTM controls should be able to be applied to inter-zone
traffic.
2. The proposed system must provide Mac Address (Physical Address) based firewall
rule configuration to provide OSI Layer 2 to Layer 7 security.
3. The proposed solution must support Application/Web Category-based Bandwidth
Management which allows the administrator to create application/web category-
ANNEXURE-I
12. The proposed solution should provide an option to define different bandwidths for
the different schedules in a single policy and bandwidth should change as per
schedule on the fly.
13. The proposed solution must be capable of identifying hidden applications running
over standard ports
14 The proposed solution must be capable of blocking the following type of
applications P2P, VOIP. Games
Remote: Control, Chats etc.
VPN REQUIREMENTS
1 The proposed solution should support IPSec, L2TP, PPTP and SSL VPN
connection.
2 The proposed solution should support DES, 3DES, AES, Two fish, Blowfish, and
Serpent encryption algorithms.
3. The proposed solution must support automatic failover of Point-to-point links
(MPLS) with VPN for redundancy purposes.
4. The proposed solution must support Apple iOS and Android VPN clients.
LOGGING & REPORTING REQUIREMENTS
1. The proposed solution should have On-Appliance, integrated reporting solution or
External Device.
2. The proposed solution should allow exporting of reports in PDF and Excel format.
3. The proposed solution should support logging of Antivirus, Antispam. Content
Filtering, Traffic discovery, IPS, and Firewall activity on the Syslog server.
4. The proposed solution should provide connection-wise reports for the user,
source IP, destination IP, source port, destination port or protocol.
5. The proposed solution should provide compliance reports for SOX, HIPPA, PCI,
FISMA and GLBA compliance.
6. The proposed solution should support multiple Syslog servers for remote logging.
7. The proposed solution should have customizable email alerts/automated Report
scheduling.
WARRANTY, SUPPORT & CERTIFICATION REQUIREMENTS
1. Warranty & UTM Features Subscription: (full contract period)
2. OEM Web/Phone/Chat Support: 24x7 (full contract period).
ANNEXURE-I
Minimum Server specifications --- 03 servers of 64 Core, 128GB RAM, 1TB SSD
Hard Disk for each server.
ANNEXURE-I
Drives
18. Ethernet Integrated Gigabit (10/100/1000 NIC) LAN
19. Connectivity Integrated Gigabit LAN Network Connection 10/100/1000
Mbps NIC with RJ45/UTP Interface.
20 Keyboard USB 104 Keys or higher OEM make.
21. Mouse 2 Button USB optical scroll mouse OEM make.
22. Chassis Volume Max. 1.2 Litre (without Mounting Kit). CPU must be
mounted behind the monitor.
23 Power Supply Minimum 65W or above External Indian Power Adapter
for CPU with an average efficiency of 87% or more
24. Security Features TPM 2.0, Setup/BIOS Password, Slot for locking CPU
using lock and key (Lock with 2/3 keys should be
provided)
25. Software Office 365 Enterprise
Loaded in Desktop)
26. Diagnostics Tool Inbuilt Pre-Boot BIOS Diagnostics
27. Security TPM 1.2 Security Chip, SATA port disablement (via
BIOS), Serial, USB enable/disable (via BIOS),
Removable media write/boot control, Power-on.
Password (via BIOS) , the Administrator
Password (via BIOS), Setup password
(via BIOS), Support for chassis padlocks and cable lock
devices
28 Warranty 5 years Comprehensive onsite warranty
29. Compliance & Energy Star ver 6.1, EPEAT Certified for India for quoted
Certification desktop & Monitor, TCO
Certified for both Desktop & Monitor FCC CE, RoHS
certified UL Certified ISO 9001, 14001, 27001, Certified
OEM
29 Information Accessibility Product details, specifications, and brochure to be
available in the public domain
30. Support Drivers should be available for download from the OEM
site for at least 5 years from the date of purchase order.
B. Workstations with Monitor:
The workstation for the development system shall consist of dual monitors & single keyboard
and a cursor positioning device/mouse. The user shall be able to switch the keyboard and
cursor-positioning device as a unit between both monitors of the console. Workstation
consoles shall also be used as development consoles to take up developmental.
Maintenance activities such as generation updation of database, displays etc, and to impart
training. The minimum hardware configuration of the operator workstation and Display
monitors are as follows:
Operator Workstation -
1. Spec As per the base runtime requirements of SPEC CPU
2017 V1.0 Benchmarking Standards.
2. RAM 16 GB expandable upto 64 GB
3. Processor Speed 3.0 GHz
4. Internal Auxiliary Memory 2x500 GB RAID, expandable upto 1 TB
5. Speakers 2 Internal speakers
ANNEXURE-I
4.7.1 All software provided by the AMISP/contractor, including the operating system,
database, AMI Applications, and support software (compilers, DBMS, display development,
network utilities, report generation, diagnostics and backup utilities) , shall comply with the
industry-accepted software standards. In areas where these organizations have not yet set
standards, the software shall comply with those widely accepted de-facto open standards put
forth by industry consortiums, such as Open Software Foundation (OSF) and X/Open. The
AMISP/contractor shall commit to meet the "open systems" objective promoted by industry
standards groups. All the software shall be compatible with smooth function with computer /
Work Stations with keyboard, Smart Mobile Phones etc.
4.7.2 All components of AMI application system shall be maintainable by owner using the
supplied software utilities and documentation. The software design and coding standards of
the system shall address the followings:
e) Programming Languages: The software shall be written using high level ISO or
ANSI standard programming languages.
All applications shall be designed with sufficient background logs which capture various
level of errors encountered (warning, fatal, informational) while executing, so that the same
can be reviewed and attended to.
4.7.3 The operating system of all the equipment of AMI application system including
network equipment shall be latest version released up to six months prior to FAT. The
operating system shall be hardened to provide robust security. The operating system and data
file shall be placed in different disk partitions.
In order to facilitate cyber security requirements including patch management,
common operating system is preferable to be used by all server nodes within the AMI
application including MDM/HES servers. This is also to minimize the maintenance. All
licenses for Operating System and other application software shall be supplied by the AMISP
and shall be valid throughout the contract period.
4.7.4 The AMI application & other servers shall maintain time and calendar for use by
various software applications and all of them shall be in synchronization with NTP.
4.7.5 Remote Diagnostic facility with necessary hardware as required shall be provided for
communication between the AMI application system at the cloud data centre and the NOMC
for the diagnosis of hardware & software problems. The login shall be protected by a
username & password entry. An automatic logging and intimation shall be provided to inform
authorized person from AMISP/utility on such events of remote access and diagnosis.
4.7.6 The network communications software shall use a standard network protocol such as
TCP/IP, UDP etc. and shall support IPv6. The software shall link dissimilar hardware nodes
such as local and remote workstations and peripheral devices into a common data
communication network allowing communications among these devices. The network
communication software shall include network security, security management, patch
management and network services of the AMI system. Network communication software
shall have scalability feature as envisaged.
4.7.7 The AMISP shall provide all necessary software tools for the development and
maintenance of the databases required for AMI application. This tool shall be capable of
managing the entire system database. The System should support exchange of data from
utility‘s computerized billing & collection, consumer indexing and asset mapping systems
residing at different servers.
4.7.8 The AMISP shall provide necessary software tools preferably browser based for the
generation, management and Integration of AMI application displays. Displays shall be
generated in an interactive mode. The user shall be able to interactively:
All workstation features and all user interface features defined in this specification shall be
supported by the display generator software. The display generator shall support the addition,
deletion and modification of segments, including the merging of one segment with another to
create a new segment. Displays shall not be limited by the size of the viewable area of the
screen.
4.7.9 AMISP shall supply all software utilities used to develop and maintain these software,
whether or not specifically described by this Specification. The software utilities shall operate
on-line (in background mode) without jeopardizing other application functions running
concurrently. Utility software shall be accessible from workstations, processor terminals and
servers.
Software utility, to take back-up of auxiliary memory files of server and workstation
onto a user- selected archival device such as SAN, shall be installed. Backup shall be
maintained for the entire duration of contract period.
On-Line monitoring diagnostic programs shall be provided for verifying the
availability of the backup equipment and for limited testing of devices without interfering
with on-line operations of AMI application system or the failover capability of the devices.
Facility of data export and import between this system and external systems shall be
provided through web services.
AMI Application management shall also include the following utility services:
a) Loading and storage of information from labelled portable media storage units as
dictated by the requirements of this specification.
b) Preparation of .pdf output for the displays/reports available in the AMI Application
system. It should also be possible to export all the reports to any MS-Office format.
c) Displays and Reports for Web server -The AMISP shall provide utilities for preparing
displays and reports suitable for Web publishing. These utilities shall be used to
generate, all required displays and reports from the system displays and reports,
automatically (without requiring rebuilding).
d) Online access to user and system manuals for all software products (e.g., Operating
System and Relational Database Software) and AMI applications shall be provided
with computer system.
e) Antivirus Software - All computers and firewalls shall be provided with the latest
antivirus software as on date of supply. The antivirus software shall have the
capability of having its virus definitions updated from time to time. The AMISP shall
be responsible for the maintenance & update of the antivirus software during the
contract period.
f) Software Upgrade-The AMISP shall be responsible for the maintenance & update of
the patches and signatures of operating system, applications (AMI Applications)
system and Web based System up to the contract period.
g) Automated patch management and anti-virus tools shall be provided to expedite the
distributions of patches and virus definitions to the system using an orchestration
facility.
These tools should consider the possibility to use standardized configurations for IT
resources.
ANNEXURE-I
Cyber security governance problems are unique as well as evolving therefore, they
cannot be dealt with a traditional approach. For establishing secure and resilient Smart Meter
systems, a standardized cyber security framework should be adopted by the AMISP. Global
Security Standards and Indian Standards that are relevant in context of underlying
technologies shall be used in securing AMI such as framework for Cyber Physical Systems
(CPS) developed by National Institute of Standards and Technology (NIST), National Cyber
Security Policy developed by Department of Electronics and Information Technology
(DeitY), Government of India etc.
Cyber security incident management will be managed as per ISO/IEC Standard 27035.
enough details of such algorithm including the mechanism of security key generation
to the Utility. In case of proprietary or secret mechanism, the same shall be kept in a
secured escrow account.
4.7.11.2 CERT Audit of Smart Metering System at the time of commissioning shall be
carried out. Subsequent audit of the system shall be carried out after every three years. Cost
of such audits and rectifications thereof shall be borne by the contractor. This clause shall be
applicable to both new as well as existing Smart Metering System. The following cyber
Security as aspect shall be adhered to: -
4.7.11.3 The IT Infrastructure will have multiple security layers to secure the
infrastructure from threats. The proposed deployment has different security zones as briefed
below and all zones shall have separated firewall in addition to the external (Perimeters
security appliances). The firewall policies shall be configured based on zone-based
requirements. All user traffic will enter in this security zone after firewall only. The
proposed solution will have provision of dedicated internal firewall to secure the critical
production (Data base and application) environment.
Web server/Application: This security zone will host all servers that can be
accessed from external users after authentication and traffic filtering. This zone shall host the
web servers, access control and sign on servers, antivirus server etc.
Testing and Development Zone: This zone will host all servers required for test
and development for applications. This zone will have limited access and it will not have any
direct access to Production Server Zone and the activity shall be monitored. It is to
implement Smart Meter / AMI system on GPRS/RF/Hybrid (RF+GPRS)/ any other advanced
communication technology i.e. communication technology need to be decided based on field
condition, and most suitable communication technology in that area shall be selected for
meter data acquisition.
a) The following basic security features should be ensured by any Cloud Service
provider (CSP):-
c) The Contractor needs to review and validate the security configurations, review the
notifications and patches released by the CSP and validate that the same is being
taken into consideration during operations, confirm that the audit trails (e.g. , who is
accessing the services, changes to the configurations etc.) are captures for supporting
any downstream audits of the projects by the finance or audit organization such as
Standard Testing & Quality Certificate (STQC), Meity Govt of India.
AMISP should describe ensure that the system is compliant with the applicable
provisions of the Reasonable security practices and procedures and sensitive personal data or
information Rules, 2011 (IT Act) as well as shall be committed to work with Utility for
compliance to Personal Data Protection requirements.
The Utility shall be the sole custodian of the Smart Meter data. The AMISP and its
contracted vendors will have limited need basis access to the data.
AMISP is required to adhere all the policies, practices, processes and technologies
employed to manage, and process the Smart Meter data in a secure manner. This should also
include the details on methods of anonymization applied to the personal Smart Meter data
based on data types defined below:
ANNEXURE-I
Certain Do's & Don'ts have to be strictly implemented to ensure privacy & security of
consumers: -
Do's----
(i) User IDs must not reveal identity and locations.
(ii) User ID to be kept in confidentially by Competent Engineer Authority
maintaining the overall system.
(iii) Any breach of information from server/cloud should immediately be
reported to Local Military Authority
(iv) Syslogs by installing SIEM log collectors should be in place to
maintain records.
(v) Regular change of passwords is imperative. System driven periodic
change of passwords to be ab-initio built into the applications.
Don’ts----
(i) No Personal Identifiable Information (PIIs) be used in the system.
(ii) Tempering of meter.
(iii) Disclosure of Information of consumer to anybody other than the
consumer.
(iv) Access to servers by only authorized person.
Audit of software for AMI will be done by CERT-India empanelled firm/ CERT
Auditor of Armed Forces. The cost of the audit will be borne by the Contractor.
4.7.15 Work of various subsystems of AMI shall be prioritized & executed in such a way
that AMI system is in place as soon as 20% Smart metres at a station are installed, Smart
Metering System is operational in ‘Go-Live’ phase.
The AMISP‘s core deliverables are the MDM, the HES, the NMS and the smart field
devices (DCUs/Routers, Smart Meters etc.). Integration of different devices of different
makes/ equipment/ software is covered in scope of this project with each other as per
functional requirements, including water charges, furniture and license fee etc.
Integration/interface of the AMI system with application systems like
metering/billing/collection is to be ensured. Interface has to be provided in the proposed
solution to upload and process meter data from these systems.
a) HES with field devices (DCUs/Routers and smart Meters) & NMS Module
ANNEXURE-I
The integration middleware should be based on Service Oriented Architecture (SOA) and
other forms of Application Program Interface (API) and use publish subscribe mechanism.
The integration middleware has to be an open architecture based. Implementation and
configuration of functional APIs from different meter manufacturers and configuration of
Head End System/Meter Data Acquisition System has to be done. All meter data of 30/15
minutes block (Load profile) shall be polled at least once in a day. The duration to polling
frequency shall be remotely configurable and can be altered as per the requirement of MES.
The bidder must store and manage the security information related to Smart Meters. These
include Device Security keys and asset information for processing further by MES. The
bidder must support the mass receipt of data of each meter every day and subsequent update
of Meter Data Management System with the necessary asset information to complete meter
reading and billing. The integration middleware / interface must validate the data to be
integrated. It must maintain integration logs that confirm the success or otherwise of the
interface, complete with control totals. The integration mechanism adopted must have
minimal impact on the existing systems.
Consumer Indexing (CI) and Meter installation & its inventory management will be the
responsibility of the Contractor/AMISP at each location covered in the project. CI database of
electrical indexing shall have the following broad parameters:
6.1 The contractor shall prepare a SOP (standard Operating Procedure) document for
meter installation in consultation with MES and Meter installation activity shall adhere to this
document. Installation services shall be performed in a professional and courteous manner,
from initial appointment set up to final installation of the meter. Customer service, effective
project team and customer communication are of the utmost importance to this project. All
site installation personnel employed on this project will be subject to background checks and
shall, at all times, carry a suitable Govt. issues photo ID ( such as Driving License, Voter
Card, Aadhaar etc.) for identification. Scope of AMI Implementing Agency shall include but
not limited to:
Most of the installations are meter replacement cases the contractor shall adhere as
per the Regulations on “ Installation and Operation of Meters”, 2006 to be read in
conjunction with amendments.
MES Project in- charge shall check on the quality of installation by checking methods
and its integration with AMI backend system by performing basic data communication with
the HES application. On successful test and field quality check the MES In charge engineer
will certify for acceptance to contractor.
AMI Implementation Agency shall ensure the availability, insertion and management to
be used in communication module of Automatic meters. However, GPRS M2M industrial
grade SIM has to be managed by the contractor. The installation and replacement of SIMs at
site shall be in scope of AMI Implementation Agency (IA). In order to pursue this, following
points need to be ensured by the system Integrator. The SIM will be in the name of GE and
the charges shall be paid by contractor as defined in BOQ.
The MDM shall have analysis capability based on configurable business rules including but
not limited to the following:
The MDM shall generate following reports (an indicative list only). Utility may request
for additional reports as well during the contract period.
The AMISP shall start up and check the performance of the equipment of field locations. All
hardware shall be aligned and adjusted, interfaces to all inputs and outputs installed, operation
verified, and all test readings recorded in accordance with the AMISP’s recommended procedures.
The SAT shall exhibit generally all functions of the equipment as per factory test reports. All
variances must be corrected prior to the start of the SAT. The list of final tests to be carried out in the
ANNEXURE-I
field shall be listed in the site-testing document by the AMISP. The site testing document shall
include the following minimum performance tests:-
For installed AMI meters (for a batch of at least 20% of installed Action performed at 99.9% of
base) meters within [24] hours
12.Remotely read events logs
Action performed at 90% of
meters within [30] minutes;
Action performed at 99% of
For reading the full event log for installed AMI meter meters within 1 hour; and
Action performed at 99.9% of
meters within [6] hours.
13.VEE processing
Action performed in [15]
For all installed meters
mins
14.Computation of Billing Determinants
Action performed in [2]
For all installed meters
hours
15.Prepaid Recharge
Payment success to consumer acknowledgement Within 5 mins
● From 90% of meters
within 30 minutes
Payment success to meter update (From MDM to HES to Meter)
● From 99% of meters
within1(one) hour
16.Utility User Interface
Manual data entry of new value appears on screen Less than 6secs
Acknowledgement of any action request Within 3 secs
Display update rate 2 secs
17.On-Demand Remote reads of meters
Collection of 7days interval energy data and the current total 95% complete within 2 hrs
Accumulated energy from a group of 10% of installed base of 100% complete within 4 hrs
meters (configurable)
The Pre-commissioning tests and inspection will be carried out after installation of
AMI completely by an Officer detailed by Accepting officer in presence of the GE, Engineer-
in-charge and the Contractor & OEMs. All the arrangement at site for testing/Re-testing and
its Cost will be borne by the contractor.
The operation, maintenance, and support services start after the successful completion of
the operational go-live of the system. Operation, maintenance and support services shall
extend up to end of Total Meter-months from Operational Go-Live. The scope of work under
operation and maintenance services shall include:-
e) Day to day operations of the AMI system under supervision and authority of the
Utility. These shall include among others:-
i. New meter installation
ii. Changeover of consumer meters from post-paid to prepaid mode and vice
versa
iii. Firmware update of remote devices (Meters and DCUs) as required
iv. Update of tariff slabs
v. Ensuring completion of recharge cycle of prepaid consumer meters
vi. Connecting, disconnecting or reducing consumer‘s licensed load under
approval from the Utility
vii. Initiating resolution of consumer trouble tickets raised by utility
viii. Ensuring availability of interval data and event notifications from meters in
time schedules as agreed with the utility
ix. Ensuring scheduled completion of billing determinant calculations
x. Ensuring daily reports from the AMI system as per agreed list, are made
available to utility
xi. Ensuring Consumer Portal is kept updated
xii. Ensuring smooth data traffic between the MDM and utility systems
xiii. Patch management of AMI applications at cloud data centre
xiv. Provide backup data to support SLA and AMISP invoicing
xv. Carry out performance checks of various functions as per agreed schedule or
on demand
As part of their Operation and Maintenance responsibilities, the AMISP shall develop
a compendium of Operation and Maintenance Manuals. These manuals shall be kept updated
as often as necessary to reflect best practices being employed in the project.
The AMISP is to hand hold the Utility team to take over operation, maintenance and
support services after completion of contract period. The project/ system devices should
allow their functionalities to be upgraded without disruption to the existing functionalities by
downloading new software and configuration information.
9.1 Contractor should provide all the updates free of cost till completion of
contract. Contractor should also provide the required training to the users for operating,
developing system and administrative training to selective persons for running system after
support period free of cost. Any software updates, upgrades, patches released shall be
supplied & installed and commissioned till completion of contract under scope of agreement /
PO / RC. Contractor shall maintain the system on 24X7 basis as per contract conditions.
9.2 The contractor shall depute the requisite manpower at appropriate levels
across the project area for upkeep of the Advanced Metering Infrastructure
(Meters/DCU/Communication Modules) installed at sites. The contractor has to deploy the
requisite manpower (on site deployment) at appropriate levels for maintenance of the
software system, undertaking change requests, report generation etc. The contractor has to
maintain and continually monitor the assets installed and see to that all the infrastructure is
working for providing seamless data acquisition.
The Contractor warrants that all the Goods are new, unused, and of the most recent or
current models, and that they incorporate all recent improvements in design and
materials, unless provided otherwise in the Contract.
The Contractor further warrants that the Goods shall be free from defects arising from
any act or omission of the Contractor or arising from design, materials, and
workmanship, under normal use in the conditions prevailing in the country of final
destination.
Guarantee of Hardware /software/ Communication infra which include bug fixing,
patches, replace, upgrade etc. and same shall be provided.
Trouble shooting of AMI Hardware/Software.
System and database administration
Post implementation support and management shall be governed by performance
parameters as mentioned in this tender.
Post implementation shall also cover the new requirement of tools, application,
reports etc. of MES.
The contractor shall provide the off-site support of experts also to resolve the issues in
shortest time.
a) The contractor will be responsible for management of all the smart meters
mentioned in the BOQ with the same specification available in the tender as a
buffer stock 5% without any additional cost offered by MES.
b) The contractor shall ensure that in case of any observation arise from the field the
buffer stock shall be utilized as replacement with Prior approval from MES.
c) The contractor shall ensure at any point of time till the warranty period the
mentioned buffer stock must be available in their custody and the same shall be
acknowledge by MES where ever it’s applicable.
d) The contractor always responsible to carry out and complete the
replacement/Erecting activity mentioned in the Penalty class.
The contractor will be responsible for replacement and making operational of any
meter within 72 hrs of meter going faulty. The vendor must maintain suitable buffer stock to
ensure the same.
9.5 Penalty:
10.0 Training:
The AMISP/contractor shall appoint at least the following personnel dedicated for the
AMI Project from the commencement of the project till Commissioning of the project.
a) Project Manager: She / he shall have the authority to make commitments and
decisions that are binding on the AMISP. Utility will designate a Nodal officer to
coordinate all project activities. All communications between the Utility and the
AMISP shall be coordinated through the project manager and nodal officer. The
project manager should be an expert in AMI Implementation including metering and
related aspects, installation and management of Smart Meters, communication
network, last mile connectivity, HES and MDM. The project managers shall be
responsible for all communications between other members of the project staffs
including sub-contractors, if any.
b) System Integration Expert: An expert in System Integration covering application
software, hardware and network installation, integration design and ability to manage
multiple partners with different skill sets in different technology domains.
c) Cyber Security Expert: An expert in cyber security related aspects covering
planning and implementing high level system security requirements, managing data
privacy and confidentiality, information flow through adequate authorizations, threat
modelling and security testing.
d) Communication Protocol Expert: An expert in communication protocols and in
implementing applications using different communication technologies and ensuring
communication inter-operability across applications/ functionalities
The project manager shall be responsible for bringing in the Cyber Security expert and
Communication Protocols expert at the appropriate stage in the project as and when required.
1 Submission of detailed Project Implementation Plan Within 60 days from the date
giving the compliance sheet along with the make and of Commencement of the
model of various infrastructure, hardware & software Contract
that are proposed for delivery and operations incl.:
● Specification of System
● Architecture and Software Solution
2 Approval of detailed Project Within15days from the date of
Implementation Plan by the GE Submission of Project
Implementation Plan.
3 ● Delivery, site installation and commissioning of Within 7 months from the date
Network Operations cum Monitoring Centre with of Commencement of the
related hardware, software and equipment; and Contract
● Delivery, site installation, integration and
operationalization of [20%] of Smart Meters each
with related meter box, service cable, hardware,
software and equipment and successful
operational go-live
4 Delivery, site installation, integration and Within 10 months from the
operationalization of 50% of Smart Meters each with date of Commencement of
related meter box, serviceable, hardware, software and the Contract
equipment
5 Delivery, site installation, integration and Within 18 months from the
operationalization of 100% of Smart Meters each with date of Commencement of
related hardware, software and equipment the Contract
6 Testing and Commissioning of the AMI Within 20 months from the
date of Commencement of
the Contract
Note: - The firm for HES and MDM system must have integrated with at least 5000
meters with RF/ Cellular technology and meters should be of different make installed in any
DISCOM/State Govt/ Central Govt/ PSU.
Note: - For a Station with Smart Meters more than 10,000 there must be 02 Nos of
HES & MDM system of different makes so as to remain available as a standby in case of
failure of one system.
(e) Printers
Ser Stage/Yard Stick Likely Time frame Payment Penalty for delay
ANNEXURE-I
MOU Requirement:-
The Sole / lead bidder has to mandatorily mention the details of all the solution / component providers
(vendors) for each of them as given below:-
Accordingly, the various solution / component providers should also separately meet the following
requirements as on date of bid submission or as on date of replacement of solution/ component
provider post award of contract, subject to necessary approval in writing from the utility. Each of the
solution / component providers shall sign an agreement with the sole/ lead bidder, provided the
solution/ component provider is not the sole/ lead bidder, clearly mentioning:
a) Their intent to comply with the terms and conditions of the AMISP Contract in the event the
solution/ component provider is selected to undertake the Project
b) Their willingness to work with the said sole/ lead bidder; and
c) Their proposed roles and responsibilities.