66 KV CONVENTIONAL DISCONNSCTOR
SWITCHES AND
66 KV EARTHING SWITCHES
EUS (C03 & C04)
First Edition
August 2006
ELECTRICITY UTILITIES SPECIFICATION C03,C04
CONTENTS
1 Scope 2
2 Definitions 2
3 Classification 2
4 Requirements 2
5 Marking 10
7 Sampling 13
9 Delivery 14
10 Spare parts 14
11 Guarantee 14
12 Submittals 14
13 Reference List 16
Test Schedules 17
Enquiry Schedules 21
Last page 27
66 KV CONVENTIONAL DISCONNECTORS
AND EARTHING SWICTHES
1. SCOPE
2. DEFINITIONS
2.1 Disconnector:
A device used to open and close a circuit when either- negligible current is
broken or made or when no significant change in voltage across the
terminal of the poles of the disconnector occurs.
A device used to earth or ground high voltage equipment which has been
disconnected from the high voltage system.
3. CLASSIFICATION
4. REQUIREMENTS
2- Atmospheric Temperature °C :-
Maximum mean daily 47*
Minimum mean daily -5
Yearly mean 30
3- Relative humidity %
Maximum relative humidity 100
Minimum relative humidity 20
Average relative humidity 75
Daily mean 95
All material shall be manufactured and tested in accordance with the latest
editions of relevant publications of the international electrotechnical
commission. Where no IEC publication has been issued to cover a
particular subject then a recognized national standard shall be applied.
The rated normal current, based on 45°C ambient, required for each type of
disconnector shall be as follows:-
- 2000 ampere for busbar sections.
- 1250 Ampere for incoming, outgoing and transformer feeders.
The rated voltage for design disconnector is the highest voltage of the
system.
2. Insulation level”
2.1 Lightning impulse withstand voltage (LIWL):
KVpeak
- phase to earth KVpeak
325
- across isolating distance 375
2.2 Power frequency withstand voltage (AC):-
- phase to earth KV 140
- across isolating distance KV 160
3. Short-circuit currents.
3.1 Rated short circuit making current. KA 80
3.2 Short time current for one second KA 31.5
4.3 Design
The disconnectors may be vertical break type or horizontal break type and
rotary type are accepted.
4.3.1 Mounting
Provision shall be made for padlocking both the disconnector and the
earthing switch mechanisms in the open and closed positions.
4.3.3 General
The blades of each phase of the disconnectors shall be one unit and not two
parts.
4.3.3.1Main Contacts
4.3.3.2Terminal Pads
4.3.3.3 The disconnector switches shall be suitable for operation whilst the
busbars of feeder are alive and they shall be suitable changing over
the load from a bus bar to another, whilst the two bus bars are
connected through the bus coupler.
4.3.3.5 The rated current of the disconnector switches shall be the same as
that of the circuit breakers {the rating of D.S are
mentioned in table (3)}.
4.3.3.10 Earthing switches shall comply generally with the provisions given
for disconnector switches. They shall be provided for all lines at
line side. It is essential that the contact of earthing switches make
a definite contact and the under reference to self cleaning contacts
is therefore important.
4.3.3.11 The disconnector switch shall be capable for carrying the rated
current under normal circuits conditions and carrying for a
specified time currents under abnormal conditions.
4.3.3.12 Enclosure for control, auxiliary circuit and operating mechanism
shall be of sufficient mechanical strength and with degree of
protection not less than IP3X for outdoor and IP2X for indoor
installation.
5. MARKING
The nameplate, which shall be of stainless steel, shall be attached to each base.
The name plate shall have (in addition to those items specified in IEC 62271-102)
the particular order number, the year of manufacture and the reference number of
the maintenance manual in both Arabic and English. The nameplate shall be easily
read from ground level.
6.1 Testing
6.1.1 General:
Test certificates are considered valid if the tests have been carried
out within the last ten years on equipment identical to that on offer
using the test methods outlined in this specification.
6.2 Inspection
6.3.1 Type tests shall be carried out in accordance with the latest edition
of IEC 62271-102.
6.3.2 Type tests which have been carried out to prove the design of the
disconnector/ earthing switch or its components shall be supported
by a test certificate, giving the type, description, location and date of
the tests carried out at an approved independent testing laboratory or
witnessed by the representative of an approved independent testing
laboratory.
6.3.3.4 Short – time withstand and peak current tests and making current
test for earthing switch.
6.4.1 Routine tests shall be carried out in accordance with latest edition of
IEC 62271-102.
The test shall be carried out in accordance with IEC 60694 and
62271-102 for routine tests. The result shall be compared with that
obtained during the type test.
7. SAMPLING
9. DELIVERY
9.1 Packing
The sides and top of each case shall be marked clearly with the supplier’s
name, purchaser order no., item no., case serial no. and gross weight and
shall be accompanied by a detailed packing note in Arabic and English.
The supplier shall provide a guaranteed delivery time from the date of
receipt of the official order.
11. GUARANTEE
The supplier guarantee the delivered equipment against manufacturing, design and
material defects for a period as given in the tender documents.
12. SUBMITTALS
Detailed catalogues.
Electrical drawings.
Maintenance manuals.
13.1 Tenderer shall submit a reference list that the proposed equipment have
been in successful operation in an integrated system on three different
substations of same or higher capacity outside country of manufacture
and/or in EETC network for a period not less than three years during the
last ten years. The experience of manufactures and the sub-manufacturers
shall be evaluated on the above basis.
TEST SCHEDULES
Disconnector closed
No disruptive discharge
Disconnector open across isolating distance
No disruptive discharge
ENQUIRY SCHEDULES
ENQUIRY SCHEDULES
(To be completed by Purchaser)
66 kV Conventional Disconnectors and Earthing Switches
66 kV 3-pole Disconnectors
3- Type of drive :-
------------------------------------------------------------------------------------
------------------------------------------------------------------------------------
------------------------------------------------------------------------------------
------------------------------------------------------------------------------------
------------------------------------------------------------------------------------
Store/Site ---------
Rated values to be filled in and submitted with tender for each type of
disconnector / earthing switch offered.
1- Manufacturer -----------
2- Disconnector type -----------
3- Type number -----------
4- Disconnector / earthing switch type -----------
Type number -----------
5- Disconnector / earthing switch drive -----------
6- Rated voltage kV -----------
8- Frequency Hz -----------
Signed : ------------------
Company : ------------------