Professional Documents
Culture Documents
E12 Protection Relay Systems Part 3 66 KV
E12 Protection Relay Systems Part 3 66 KV
E12 Protection Relay Systems Part 3 66 KV
CTRICITY UTILITIES
S SPECIFICATION E12-2
PART 3
66 KV
CONTENTS
1 Scope 2
2 Definitions 2
3 Classification 2
4 Requirements 2
5 Marking 15
8 Delivery 19
9 Guarantee 19
10 Submittals 19
11 Reference List 20
12 Last page 20
1. SCOPE
2. DEFINITION
The panels which include the protective relays and testing facilities for each
relay and have also the tripping relays and lockout relays.
3. CLASSIFICATION
The protective relaying system covered by this specification shall be for use with
66 KV switchgear and specified for line feeder, transformer feeder Busbar and bus
coupler.
4. REQUIREMENTS
2- Atmospheric Temperature °C :-
Maximum mean daily 47*
Minimum mean daily -5
Yearly mean 30
3- Relative humidity %
Maximum relative humidity 100
Minimum relative humidity 20
Average relative humidity 75
Daily mean 95
4.4.1.21 All relays shall be subject to routine tests as specified in the relevant
IEC standards before incorporated into the complete panel.
4.4.1.26 All relays shall included all interfaces to enable time synchronization
through satellite (GPS system)and connection with external PC
/laptop.
4.4.1.26 Multi- function protective relays shall be designed so that the
indications will clearly show the stage which has initiated tripping.
4.4.1.26 The design of all protective relays shall satisfy the following as
minimum:-
• Withstand the application of surge withstand capability (SWC)
tests as defined in IEC.
• Insensitive to radiated high frequency wave interference coupled
from nearby radio transmitters as follows .
a) VHF radio transmitter in nominal 150 MHZ band, with an RF the
output power of at least 10W
b) UHF radio transmitter in the nominal 450 MHZ band, with an RF
output power of at least 10W .
• The relaying equipment shall not be affected by operation of a Radio
transmitter operating in the above frequency ranges when its antenna
is brought to within (1)one meter of the relay equipment’s circuits
whether Radio transmitter operate continuously or periodically.
4.4.1.26 The relay panels shall consist of unit type construction forming a rigid
self-supporting, self contained housing having hinged doors. Door
shall be equipped with handles and the panels shall have proper light
and AC sockets with locking facilities. The front door shall be
transparent.
4.4.1.26 Protective relays technical parameters
Rated frequency 50Hz.
Rated voltage (AC) 100/110V
Rated current 1A
Current carrying capacity (1sec.) 50In.
Continuous current withstand >2In.
Accuracy for distance relay function + 0.5%
Accuracy for fault locator function + 0.5%
Operational temp range.. -5°C up to 55°C
Humidity 90% at 40°C.
Supply voltage DC (110-220)+15%
Contacts : a)Max. system voltage across open contact >250
b) Current carrying capacity (1sec.) >10A.
c) Continuous > 3A.
- Relay shall have self monitoring for the whole system including
hardware, voltage circuits , current circuits, DC circuit, and tripping
circuits.. etc and block tripping in case of any failures Failure indication
shall be given .
- I/P and O/P data shall be accessible via front panel, and PC.
- Programmable input and output contacts shall be provided, not less than
12 each.
- Shall have line check function when a dead line is energized.
- Shall have enough programmable LEDs and corresponding signaling for
indication of each phase and steps of operation
- Basic time of operation shall not exceed 35m sec.
- The accuracy of measurement shall not be materially affected by V.T &
C.T transient nor the length of the line.
- Be Suitable for O.H.T.L. and under ground cables.
- The characteristics of the measuring elements for each fault shall be
quadrilateral while for inter phase faults possible to be quadrilateral or
circular with independent adjustable inductive & resistive reaches.
- Have voltage memory for duration not less than 5 cycles.
- The directionality shall be verified under load conditions <20%.
- It shall be possible to change the directionally (preferably) without
distributing VT &CT or relay wiring.
- Shall include back up protection functions as follows:
Tripping relays should be of electrically and manually reset type and designed
to operate from 60% to 120% of the DC supply rated voltage.
5. MARKING
5.1 Name Plate
Each panel shall be provided with a name plate marked in a durable
manner and located such that they are visible and legible. The name
plate shall be written in English and space shall be left to be written
in Arabic.
6.1 Testing
6.1.1 General:
All protective relay shall be tested in accordance with the latest IEC
standards.
The supplier shall provide acceptable type test certificates for the
protective equipments inside the panel.
- Tests Shall be performed as required to insure the proper operation and
complete installation of all components. Upon completion of testing and
checking of each item, any necessary maintenance and protection shall be
carried out. Safety procedure to ensure safety of the personnel and
equipment within the test area shall be considered.
- The contractor shall submit test certificates to demonstrate that all
equipment meets the specification and by reference codes and standards.
- All equipment shall be subjected to routine shop tests. In addition,
performance and functional tests shall be conducted.
- Test procedures and a list of standards and guides that will be used during
construction shall be prepared and submitted to EETC.
- The contractor shall clearly outline all in service tests that will be required
to be performed by the owner for normal operation and maintenance
activities.
- Test reports : all data obtained from receiving, storage, maintenance and
testing of the equipment shall be recorded and submitted to purchaser. The
reports shall include :
Summary of the tests, date of tests, tests procedure with reference numbers,
description of the equipment tested, test equipment used, test results, and
conclusions.
- Offshore inspection tests and checks: all equipment shall be checked for
physical damage, dents, cleanliness, proper fit, and paint scratches.
Correctness of wiring and connections compared to wiring and connection
diagrams. All discrepancies shall be reported to purchaser.
6.1.2 Location of the test
Routine and /or sample test shall be carried out at supplier factories.
Type tests shall be carried out at an independent testing agency or at the
supplier’s laboratory and witnessed by a representative of an independent
testing agency or other representative acceptable to the purchaser.
6.1.3 Type ,Routine and Site Tests
6.1.3.1 Each panel shall be checked to ensure that an output of the of the
specified accuracy results when rated input is applied.
6.1.3.2 Insulation resistance test at 2000 V, AC for one minute shall, if possible
to be carried out on all protection, control, alarm and indication circuits
to ensure that wiring is in satisfactory condition.
6.1.3.3 Visual inspection shall be made on cable gland, cable joints, circuit
breaker rating and small panel items, such as indicating lamps.
10. SUBMITTALS
The supplier should submit the following:-
• Detail design.
• General, layout drawings.
• Outline dimensional drawings.
• Assembly drawings.
• Wiring diagrams.
• Schematic diagrams
• Mounting drawings.
• Type test report.
• Factory routine test report.
• Operation and instruction manuals.
• Catalogues for all equipment in English.
• Equipment reference.
• The necessary documents, drawings, catalogues, wiring
diagrams, calculations of current transformers, and voltage
transformers burdens, guarantee the correct functioning of the
protection equipment without any danger of thermal deterioration
in the relays.
Tenderer shall submit reference list that the proposed equipment have been in
successful operation in an integrated system for a period of three years minimum
on three different substations of same or higher capacity outside country of
manufacture and/or in EETC network during the last ten years.
The experience of manufacturer and the sub-manufacturers shall be evaluated on
the above basis.