Transformer-2-1000 KVA Data Sheet

SL NO Genral Characteristics Reliance to project Manufacturers Comments (WESCOSA)


1 Type Power Transformer Confirm
2 Applicable Standard IEC Confirm
3 Service/Installation Outdoor Confirm
4 Duty Continous Confirm
As per specification Confirm (details attached)
insulating liquid shall be MIDIL
7131. And shall follow IEC codes
5 Insulating Liquid IEC 61099, IEC 61125, IEC 60156
and IEC
60836.

Preservation Sytem
1 Rating power 1000kVA Confirm
2 Number of windings 2 Confirm
3 Nominal Primary voltage 6.6kV Confirm
4 Nominal Secondary voltage 0.38kV Confirm
5 Rated Frequency 60Hz Confirm
6 Cooling ONAN Confirm
7 Preservation Sytem Hermetically sealed with
Confirm
deteachable radiator
8 Transformer shall be one Please refer to WESCOSA
coat rust inhibiting primer, one painting procedure Document " PPSP18023 Rev.00" For review and acceptance.
coat M10 after pressure testing,
Tank Material and one coat gloss dark
admiralty grey color 623

9 Tank charger type Off Circuit tap charger Cofirm


10 Primary Voltage Tapping (at no 5(0+/-2.5%+/-5%)
Confirm
load)
12 Insulation Voltage HV 60kV Confirm
13 HV/LV winding Delta/Star/Dyn 11
Confirm
connection/Vector group
14 Primary/Secondary winding Copper
Confirm
conductor material
15 Ambient Temprature 50C Confirm
16 Oil/Winding Temprature 50C/55C Confirm
rise[C/C]
17 Insulation Class Shall be as Class H Class A

Termination
1 Primary Side tank mounted bushing with Confirm
air insulated cable box
2 Secondary Side tank mounted bushing with Confirm
air insulated cable box
3 Neutral Within LV cable box Confirm
Guaranteed Value
1 Standard for Tolerance IEC Confirm
2 Impedance 5% Confirm
Standard Accessories
1 Buchholz relay Oil level guage with contact Transformer accessories shall be as per specification but not limited to that
itself. Please refer project specification Section 3.1
2 Oil temprature indicator with Pressure relief device with 1. 25 mm drain valve with 10 mm sample port.
contact contact 2. 25 mm fill plug.
3 Sudden pressure relay Winding temprature relay with 3. Liquid-level gauge.
contact 4. Pressure vacuum gauge with bleeder.
4 Control cabinet LV Bushing 5. Pressure relief device.
6. Dial type temperature gauge.
5 HV Bushing Conservator 7. Mounting provisions for low- voltage current transformerss
8. Alarm contacts on gauges.
6 Terminal box Drain valve with sampler 9. All alarm and relay contacts to be connected to an IP66 four terminal
junction box by means of flexible, watertight conduits.
7 Lifting lugs Earthing studs • Surge Arresters: Provide distribution class metal oxide- type surge
arresters.
8 Rating plate Logo plate WESCOSA: Surge Arrester, Conservator, Buchholz Relay, Sudden Pressure
relay, winding temperature relay and silica Gel Breather not applicable.
9 Wiring diagram Connection Plate

10 Silica gel breather Jacking Pads

11 Tap Changer

Noted:1.Kindly provide FAT report. Along with tests mentioned in the project specification section 3.1
. Please review the images attached in the documents & project specification
2. Kindly Refer the attached drawing for your review