Professional Documents
Culture Documents
IRV302 Danfoss Troubleshooting
IRV302 Danfoss Troubleshooting
4. Pressure does not display in Setup 1. Make sure Set-Up 1 3-03 is set
to “200” instead of “65” per the older guides. The pressure is
programmed to display in both setups. In order to display the pressure
in setup 1 it was required to program it as process control, even
though the process loop is not used. The display of pressure in both
setups was done to display pressure while in the unload condition.
Related parameters, 0-24, 1-00, 3-01, 3-03
7.
Drive trips on A7, DC Over volt. If it occurs when pressure
disturbance occurs. Reduce the drive’s gain. Related parameters, 7.33
which is P, its range is (.01-10), higher number is more gain, 7.34
which is I, (.01 – 10000) higher is less gain and parameter 7.35 which
is D (.00-10000), smaller is more gain except if it is set to 0.
Setup1 could be locked in at 60 Hz. If drive starts up and goes over 35
Hz then check setup1 parameters 3-02 and 3-03. Also, set 2-17 to
choice “2”
If this does not fix the problem then there could be a programming
issue. Download the blank parameter list and email it to tech support.
8. Drive trips on A9, A13, or A59 over current; Increase motor current
setting; reduce ramp time/gain; related parameters; 1-24, 3-41, 3-42,
7-33, 7-34, 7-35. If the VFD runs the fan motor, also, make sure 1-24
includes the amperage draw from both motors. Most newer machines
run the motor to the top of the Service Factor, so settings 1-24 to the
SFA instaead of rated Amps may help. If the Current warning occurs
only between 45 and 57 Hertz, then set 14-51 to “off” and 1-64 to 0%
9. 0-10 Sets the active setups, make sure it is choice “9” multi. Also at
the upper right hand corner the active setup and the setup that is being
edited. I.e. 1(2), 1 is the active setup and (2) is the setup that is
selected for editing.