Professional Documents
Culture Documents
Fire & Safety
Fire & Safety
Fire pumps:
Requirements:
1. Fire pumps shall be capable of giving a quantity of water, for fire fighting purpose, at
following minimum pressures of;
0.31 N/mm² for passenger ships of 4000 tons gross tonnage and upwards,
0.27 N/mm² for passenger ships of 1000 ~ 4000 tons gross tonnage, and
0.27 N/mm² for cargo ships of 6000 tons gross tonnage and upwards.
2. For passenger ships, fire pumps shall be capable of giving a quantity of water, for fire
fighting purpose, not less than 2/3rd of the quantity given by bilge pumps.
3. For cargo ships, fire pumps shall be capable of giving a quantity of water, for fire
fighting purpose, not less than 4/3rd of the quantity given by bilge pumps in a
passenger ship of same dimension, provided that total required capacity of fire pumps
need not to exceed 180 m³/hr in cargo ship.
4. At least 3 fire pumps, provided for passenger ships of 4000 tons and upward.
5. At least 2 fire pumps, provided for cargo ships of 1000 tons and upward.
6. Sanitary, ballast, bilge or GS pumps may be accepted as fire pumps, provided that
they are not normally used for pumping oil fuel, and suitable change-over
arrangements are fitted if they are subjected to occasional duties for pumping oil fuel.
7. In cargo ships of 2000 tons gross tonnage and upwards, if fire in any compartment
could put all the pumps out of action, there shall be a fixed independently driven
Emergency Fire Pump.
7. If motor driven:
a) Two sources of power supply provided.
b) Power operated emergency fire pump, with source of power and sea
connection, must be located outside machinery space.
50
1. Diameter of fire main and water service pipes, for cargo ships, need only be
sufficient for the discharge of 140 m³/hr.
2. Hydrants shall be positioned near the accesses to the protected spaces and fire
hoses may be easily coupled to them.
3. Standard nozzle size: 12mm, 16mm and 19mm.
4. For accommodation and service spaces, nozzle size greater than 12mm need not
be used.
5. All nozzles shall be approved, duel purpose type [jet/spray] incorporating a shut-
off.
4. In boiler room:
Fireman’s outfit:
Consists of:
À Personal equipment, comprising protective clothing, boots and gloves of rubber, a rigid
helmet, an electric safety lamp [min burning period 3 hrs.], and an axe.
Á A breathing apparatus. Smoke Helmet [Smoke mask] or Self-contained compressed air
BA set.
For ER
1. At least 1 Portable Foam Applicator with 200 lb. spare container.
2. At least 45 litres Foam Extinguisher
3. At least 2 Portable Foam Extinguishers shall be placed within, not more than 10
meter walking distance.
Sprinkler System:
Operation:
1. Each sprinkler head provided with a quartzoid valve, which seals the outlet of water
pipe.
2. Valve is partially filled with special fluid, so that a rise in room temperature will
expand the liquid and the valve will burst.
3. Water under pressure; will flow out from Sprinkler System. [ 5 – 8 bars pressure is
maintained in FW pressure tank by air pressure.]
4. Sprinkler head can cover a floor area of about 12m² with water pressure of 5 – 8
bars.
5. Pressure drop in tank activates the pumps to take over and supply water from FW
holding tank. When holding tank become empty, SW pumps come into action
automatically.
Rules:
1. No: of heads not more than 200 per section.
2. Heads are spaced not more than 4 meters apart.
3. At least 2 sources of power supply to Automatic alarm system and SW pump.
Advantages:
1. Self fire detection, and immediate and automatic operation at all time
2. Not harmful to human.
3. No need to seal the space.
4. No need to clean the media, after use.
Advantages:
Disadvantages:
1. Only suitable for confined space, and needs total sealing of the space.
2. Fatal to life.
3. Re-ignition can occurs after fire is completely died out.
4. No cooling effects, only extinguished by smothering and inhibition.
1. Exhaust fan, and suction duct is provided at the bottom of the room. Any accumulated
CO₂ from leakage at the bottom can be exhausted to atmosphere.
2. Cable operated Safety Valve is fitted on Pilot Cylinder discharge line.
It prevents accidental discharge of CO₂ from Quick Release Cylinders due to action of
53
For cargo space, CO₂ quantity shall be sufficient to give a minimum volume of free gas,
equal to 30% of gross volume of largest cargo space so protected.
For machinery space, CO₂ quantity shall be sufficient to give a minimum volume of free gas,
equal to 40% of gross volume of machinery space so protected excluding the casing.
Inert gas:
1. The gas which does not support combustion is inert gas, such as CO₂, N₂, and
boiler flue gas containing < 11% O₂.
54
2. Tankers of 20,000 DWT and above, provided with Fixed Inert Gas System.
a) To prevent accumulation of explosive mixtures in cargo tanks, during
ballast voyage and during tank operations.
b) To minimise risks of ignition by static electricity generated by the system
itself.
3. Inert gas is used only in fixed installations and large bore piping are used due to
low pressure of the gas.
4. Main function is essentially fire-preventive by providing an inert atmosphere.
5. Inert gas installation is not acceptable in machinery spaces.
Applications:
1. To use in Electric Fire
2. To use in Electronic system fire
3. To use in Class A fire
[ Halon used for fire fighting are: Halon 1301, 1211, 2402.]
Limitation:
1. Not to use in general cargo space.
2. Not to use in Metal Fire.
3. Not to use on Oxidising Agents.
55
Extinguishing Media:
Water: Cooling and smothering by steam.
Foam: Combined effect of cooling and smothering.
CO₂: Smothering and inhibition.
Dry Power: Extinguished by inhibition ( breaking chain reaction.)
Halon: Extinguished by inhibition.
Inert Gas: Fire-preventive, by providing an inert atmosphere.
a) This system with manual call points must be able to operate immediately at all
times.
b) Must have two sources of power supply, and visual and audible alarms for power
failure.
c) Control panel should be located on Bridge.
d) Heat, smoke or other products of combustion, flame or any combination of these
may operate detector.
56
Types of Detector:
Smoke detector:
1. Installed at stairways, corridor, escape route within Accommodation Space.
2. Also used in Cargo space and Machinery space
3. Maximum floor area per detector = 74 m².
4. Max. distance apart = 11 meters.
5. Max. distance away from bulkhead = 5.5 m.
6. Photocell or light scattering types.
Heat Detector:
1. Maximum floor area per detector = 37 m².
2. Max. Distance apart = 9 meters.
3. Max. Distance away from bulkhead = 4.5 m.
4. Used Bi-metal strip.
5. Fitted in boiler room, laundry, Control Room, Galley.
Flame Detector:
1. Ultra Violet or infrared.
2. Fitted near fuel handling equipment.
Combustible Detector:
1. Fitted in galley, ER fwd bulkhead adjacent to p/p room under floor plate.
7. After opening the cabinet door, master valve must be opened first.
8. Pull the operating handle of pilot cylinders.
9. CO₂ , released from pilot cylinder, operate the gang release bar so that all CO₂
from quick release or total flooding cylinders will be released to machinery space.
10. By regulation, 85% of the capacity must be able to be released within 2 minutes.
1. Remote detector fitted at the bridge can detect concerned cargo space.
2. This operation must be done by master’s order.
3. After ensuring no person left in cargo space, seal off the cargo space [closing of
ventilation fan, fire damper, hatch cover].
4. Before discharging, change 3-way valve to CO₂ discharge line so that connection to
smoke detector is isolated.
5. Open the quick opening valve so that alarm will automatically initiated.
6. Manual operation procedure and amount of CO₂ bottle to be released is stated in
CO₂ room.
7. By master’s order, release the correct amount to concerned cargo space.
8. Topping up procedure must be followed at port arrival.
Paint Locker
» Paint and other inflammable liquid lockers must be protected by an appropriate fire
fighting equipment.
» Paint locker is usually protected by pressure water spray system for boundary
cooling, and detector should be flame detector.
Detection:
1. Automatic fire alarm and detection system indicates presence of fire and its location.
2. Indicators are centralised in Engine CR and Bridge, and alarm signals are audible and
visual.
3. Detectors operate when rate of temperature rise of surrounding air reaches set limit of
145°F (62.8°C).
4. Human common senses such as sight, smell, hearing and feeling are also good
detection.
Prevention:
1. Fire Control Plan is set out in accessible position in CR.
2. ER personnel must have training such as to locate the fire, to inform, restrict, and
extinguish with suitable appliances.
58
3. Fire Drill carried out once a week. Exercise for abrupt evacuation of ER before
releasing CO₂ must also be practised.
4. Weekend testing and checking of emergency stops, quick closing valves, watertight
doors (remote and local) ventilation dampers and skylight doors.
5. Cleanliness in ER is most important.
6. Maintenance of all fire fighting appliances.
Extinguishing:
1. Two independently driven power pumps and one emergency pump driven by own
engine with delivering capacity of at least 25 m³ / hr. each.
2. Two hydrants (port and starboard) with spray nozzle fitted hose. [Minimum water
pressure 37 psi.]
3. International shore connection [outside 7" or 178 mm: inside 2 ½ " or 64 mm].
» General arrangement plan must be permanently exhibited onboard, for the guidance of
officers.
» Positioned outside the deck house [opposite to gangway of both sides] in a permanently
watertight enclosure for assistance of shore fire brigade.
» Fire Control Plan includes:
1. All portable and semi-portable extinguishers: Good working order ensured, properly
placed in ER and always made handy.
2. Fixed fire fighting installation: Alarm testing and function testing once a week,
compressed air blowing of lines and discharge nozzles, contents to be weighed and
checked periodically.
3. Emergency fire pump: Good working order ensured, weekly test run without failure.
59
4. Fire detection, monitoring and alarm system: Tested weekly without any failure.
5. All fire hydrants and their connection, sand boxes and scoops: Kept in good working
order.
6. Fire man’s outfits: 2 numbers in good working order and handy at all times.
7. International shore connection: Placed at proper location.
8. All ER members: Properly educated about fire fighting appliances and their operation.
9. Fire drill: Carried out at least once a month.
Safety Equipment:
To dispose sludge and bilge, from ship to shore reception facility, a standard discharge
connection is provided at discharge side of sludge pump.
If ER is abandoned, the Emergency Fire Pump can supply the deck line, even if there is a
burst water main in ER.
Fire Main can also be pressurised, if necessary, from shore or from another ship by use of
International Shore Connection, in the event of emergency situation.
International Shore Connection is usually used when vessel is in dry docking, for
pressurising the fire main.
Dimension: 178 OD, 132 PCD, 64 ID, 14.5 thickness, Four 16Φ bolts with 50 mm
length for four 19mm slotted holes, with 8 washers and a gasket. (all in mm)
Location: At Fire Control Station and location is known by every crew.
Emergency Signals:
At weekly:
» All lifeboats, life rafts to be visually checked for immediate use.
» One of the lifeboats to be swung out at least 50% onto water.
» Lifeboat engine to be test-run for two minutes, ahead and astern.
» General alarm system tested, CO₂ alarm, fire alarm, refer room alarm.
» All watertight doors and skylight doors to be tested.
» Emergency fire pump, emergency generator, emergency 24V lighting tested.
At monthly:
» All life saving appliances.
» Lifeboat drill. [Logbook entry to be made for all drills].
» Fire drill.
Fire Drill:
Boat Drill:
Every ship shall be provided with documentary evidence of its fitness, to operate with
periodically unattended machinery space.
1. Fire precaution.
2. Protection against flooding.
3. Control of propulsion from Navigation Bridge.
4. Communication.
5. Alarm system.
6. Safety system.
7. Special requirement for machinery, boiler and electrical installation.
1) Fire Precaution:
Detection and alarm system must be provided for:
1. Boiler air supply casing and uptake.
63
4) Communication:
Reliable vocal communication provided between C/R, ME control position,
Bridge and duty engineer’s cabin.
5) Alarm system:
Alarms should be provided to indicate any fault:
1. Audible and visual alarms in ER and Control Room.
2. Connections provided to Engineers’ public room and each Engineer’s cabin
through selector switch.
3. Audible and visual alarms fitted on bridge for necessary items, which are required
Officer’s attention.
4. Alarm system shall have automatic changeover to stand-by power supply, in case
of main power failure.
5. Alarm shall be able to indicate more than one fault at the same time.
6. After an alarm is acknowledged, visual indicator must be remained until the fault is
corrected. After correction, alarm should be reset to normal automatic operation.
6) Safety system:
1. Auto-shut down of boiler and machinery if serious malfunction occurs, and alarm
must be given.
2. Shut down of propulsion machinery shall not be activated, except in very
dangerous cases.
3. If overriding system is provided for ME, protection for inadvertent operation must
be fitted. Visual indicator fitted to indicate, when overriding has been activated.
Alarm Checking:
1. Using the Simulator can check UMS alarm system, when engine is in stopped
condition.
2. Alarm system for manned ship can be checked, by checking temperature and
pressure gauge readings, at the time of alarm initiating, while engine is shutdown.
64
What is Simulator?
1. A computerised special device, which can duplicate artificial conditions, likely to
be encountered in actual operation.
2. Modern UMS ship is provided with Adapter, to connect the Simulator, so that
alarm system can be checked, when engine is stopped.
Causes:
1. Accumulation of unburned fuel in exhaust trunk, due to incomplete combustion
together with heat source, like leaking exhaust valve.
2. Carried-over cylinder oil due to excess cylinder lubrication.
Effects:
1. T/C over-run, bearings and casing damaged.
2. Abnormally high, scavenge air pressure.
3. Possible ER fire.
Remedies:
1. Stop ME and cool down.
2. Defective fuel v/v and exhaust v/v changed.
3. Complete combustion, maintained at all times.
Crankcase Explosion:
Primary Explosion:
When the ratio of air/ oil mixture in crankcase falls within Explosive Limits, and this mixture
is exposed to Hot Spot, primary explosion will occur.
Secondary Explosion:
Primary explosion causes a Flame Front and Negative Pressure Wave to accelerate through
crankcase. A Partial Vacuum will draw uncontrolled amount of fresh air, back into the
crankcase, where it will mix with already evaporated and burning oil, to cause Secondary
Explosion.
Operation:
1. Oil mist is drawn from crankcase by electric fan through sampling tubes, connected
to top of respective crank chambers.
2. Rotating sampling valve connect each tube in turn for 4 seconds to measuring tube,
whilst reference tube has average valued sample from remaining crank chambers.
3. So can evaluate the difference in oil mist levels, between each crankcase and
remaining crank chamber.
4. At ‘0’ position of rotary sampling valve, clean air is admitted to both reference and
measuring tubes for ‘0’ calibration.
5. Two identical beams of light along the axis of parallel measuring and reference
tubes fall on light sensitive photocells, connected electrically back to back with a
circuit.
6. Photocells generate electric current directly proportional to intensity of light falling
on their surfaces.
7. Under normal condition, oil mist level is the same in both tubes, and photo cells’
output current is electrically balanced, (i.e. output is ‘0’).
8. Increase in oil mist density in any one crank chamber will unbalance the photocell’s
output and alarm is energised.
9. Out of balance current, due to rise of oil mist density indicates on Galvanometer,
connected to continuous chart recording and auto visual and audio alarms.
10. False alarms can be given, if electrical resistance increases, affecting the supply
current, when water is in LO, and detector lens are dirty.
Explosimeter:
An instrument for detecting and measuring of Flammable Gases in atmosphere.
Main Causes:
1. Leaky or sticky cylinder air start valve in opened position.
2. Collected oil inside start air pipe, carried over from air compressor’s faulty oil
scraper rings, through Air bottle.
Preventive measures:
1. Periodical overhauls of cylinder air start valve.
2. Before manoeuvring, cylinder air start valve is tested by isolating Air Distributor,
and escape of air through indicator cock, indicates its leakage.
66
3. Before manoeuvring, all valves well lubricated and rotated by hand spanner, to
ensure proper working condition.
4. While manoeuvring, all air manifolds touched and sensed their temperature. Local
overheating of adjacent pipe indicates valve leakage.
5. Compressor air suction filter regular cleaning.
6. Regular draining of Air bottle drain valve, Air compressor intercooler drain valve,
and air start pipe system.
7. Regular overhauling of compressor piston rings.
8. Discharge of ER blower directed to Air compressor suction filter.
Safety devices:
1. Bursting discs: Fitted at start air manifold, at cylinder valve inlet.[ 0.75 mm thick
copper, steel or bronze and will rupture at 3 x max. start air pressure.]
2. Safety caps: Fitted at cylinder valve inlet [ steel- cadmium coated safety tube or
copper hood]. If the cap rupture, movable hood can be moved around
to blank-off the holes in fixed hood, for emergency use.
3. Lightning full bore safety valve: At start air line after Master starting valve, to
relieve excess pressure and close back automatically.
4. Spring loaded safety valve: Fitted at start air line, but not reliable.
1. Any space that has been closed or unventilated for some time.
2. O₂ content < 18% and ≯ 21%.
3. The space contains harmful and toxic gases, CO, H₂S.
4. Not well ventilated and has very narrow access for easy working.
5. Confined spaces are: Fore Peak, Aft Peak, FW Tanks, Ballast Tanks, Fuel Tanks,
Cofferdams, Pump rooms, Paint store, Cargo tanks, Duct Keel, any DB tanks and
any closed compartments.
L.E.L. Smallest percentage of gas, that will make an ignitable air/vapour mixture.
[That is 2% of Gas and 98% of Air].
H.E.L. Largest percentage of gas, that will make an ignitable air/vapour mixture.
[That is 10% of Gas and 90% of Air].
Uptake Fire:
1. Happened when soot, carbon, and oily deposits collected at the Uptake, being
spread along a surface, where temperature is high enough to start fire.
2. Deposits may become thicker and thicker, having lowering the ignition
temperature.
3. In some cases, fire can start even at normal atmospheric temperature, as presence
of oil can reduce ignition temperature considerably.
4. Uptake fire is important, because hydrogen fire is possible, when soot blowing is
done during big uptake fire situation.
Protective devices:
1. Soot blowers
2. Uptake gas thermometer
3. Uptake gas back pressure gauge or manometer.
Indication:
Prevention:
1. Follow all of the above steps, except Soot Blowing, which may intensify the fire
and cause explosion.
2. After the self-perpetuating fire has been died down, open up and clean the smoke
side, with fresh water pressure jetting.
1. When metal itself burning due to fire, at about 700°C, and if steam smothering
soot blowing or water jetting system have been attempted, the big hydrogen fire
may results.
2. The applied steam dissociates into Hydrogen and Oxygen, accelerating the fire,
until steam supply is exhausted, or temperature drops below 700°C.
3. Dissociation of steam into H₂ and O₂, by heat alone requires temperature about
2500°C.
4. But iron will burn in steam with free H₂, at much lower temperature of 700°C.
5. Once such a fire has started, two kinds of fire may take place simultaneously: one
kind, iron burning in steam, and the other, H₂ burning in air.
6. This combined fire, being self supporting and lasting until steam supply is
exhausted.
7. Primary object of dealing this nature of fire is, to cool the surface and burning
materials as quickly as possible.
Scavenge fire:
Symptom:
1. Increase in Exhaust temperature.
2. Increase in Scavenge air temperature.
3. Increase in Jacket temperature.
70
Precaution:
1. Stay away from vicinity of fire, flame may burst out behind safety doors if violent.
2. Do not open scavenge trunk, while still hot, and also the crankcase.
Prevention:
Grounding:
Actions to be taken:
1. Sea chest to be changed over to unaffected side.
2. Frequent sounding at all DB tanks and cofferdam.
3. Thorough inspection at affected area.
4. Check steering gear, rudder to be tested, after getting permission from bridge.
5. Turn engine by turning gear, to ensure that propeller is clear or not.
6. Check crank shaft deflection and compare with former record.
7. Check all sea water pumps are free from sand, mud etc.
8. Check tunnel bearing.
9. Check engine vibration, and if not satisfactory, it is due to damage of propeller.