Current Transformer Open Detector

Model No.

KYS-01

Overview

Under CT secondary open condition, current transformer can be damaged and making noise due to insulation breakdown. This device
used to protect current transformer while CT secondary open condition.

Feature
Connected to the secondary side of the CT to monitor the voltage of each phase, and if the voltage exceeds the set value, close
secondary of CT.
Two contacts relay for alarm in case CT secondary opens.
Recovery and short circuit button for testing recovery and short.

Specification Connection diagram

Input 0.1~6A
Aux. power AC/DC 90~260V(50/60Hz), DC 110V
Operating humidity 20~85%
Withstand voltage AC 2kV Can withstand 1 minute
Insulation
More than 10MΩ
resistance
Voltage(2㎲/ 50㎲, 5kV),
Surge impulse
Current(8㎲/20㎲)
Burst immunity Level 4(IEC 61000-4-4)
10A, 250V AC(1 Form A),
Short circuit relay Current Transformer Open Detector
cov
ery
Power on time : 0.3sec / Fixed time Recovery: Normal Recovery / up Re cuit
rt cir
Sho ion
Short circuit: manual short/down
Selection: Set (press for 3 seconds) / ct
5A, 250V AC(1 Form C), Voltage sensitivity, Delay time, Relay setting, Save Sele
Alarm relay
Power on time : 0.3 sec / Fixed time
Operating
-10~50℃
temperature
Elevation Less than 1,000m from sea level

① CT secondary connection : R(P1), S(P2), T(P3), N(P0)

Function ② Alarm relay : ALARM1(A, C, B), ALARM2(A, C, B)


③ Display LED: Open (On), short (Off)
Open / closed state LED.
④ Aux. power
Voltage sensitivity digital setting (4 levels).
⑤ Switch for Recovery, Short circuit and Selection
Delay time setting (1 to 10 sec).
OTHERS

- Recovery: Normal Recovery / up


Manual short and recovery for each phase.
- Short circuit: manual short/down
Relay setting(Activate/ de-activate) for alarm condition. -Selection: Set (press for 3 seconds) /
Voltage sensitivity, Delay time, Relay setting, Save