RiTherm Summary

Project: fff Calculation: New calculation


Company:

Ambient parameters

Minimum temperature outside the enclosure Ta 0 °C


Maximum temperature outside the enclosure Ta 55 °C
Maximum temperature inside the enclosure Ti 35 °C
Mains voltage 230 V
Frequency 50 Hz

Enclosure set: Set 1

Enclosure no. 1 VX 8884000


Dimensions (W x H x D) 800 mm x 1,800 mm x 400 mm
K-Factor of the enclosure 5.5
Power dissipation 473.99 W

Climate control calculation

Average temperature without climate control 82.07 °C


Heat loss 474 W
Heat exchange across surface -350 W
Heat to be dissipated 824 W
Cooling solution for set is needed, but no device had been selected

1/1
Rittal can not assume any liability for the calculation, dimensioning and selection. 4/5/2024