Professional Documents
Culture Documents
Memco Offer
Memco Offer
Dear Sir,
We have the pleasure to submit offer for the a.m.project according to
your specification & our attached technical offer
We hope that our offer meets your requirements, Please don’t hesitate to
contact us if have further enquiries
Best Regards,,,,,
Technical Studies Director of Technical Studies
Misr Electrical & Mechanical Ind. Co. ﺷ ــﺮآﺔ ﻣﺼــــﺮ ﻟﻠﺼﻨـﺎﻋﺎت اﻟﻜﻬـﺮﺑــﺎﺋﻴﺔ واﻟﻤﻴﻜــﺎﻧﻴﻜـﻴﺔ
S.A.E. ﺷﺮآــــﺔ ﻣﺴــﺎهﻤﺔ ﻣﺼـــﺮﻳﺔ
Head Office: 25 Al-Tayaran St.(M ahmoud Shaltoot)-Nasr City اﻟﻘـــــــــﺎهﺮة- ﻣﺪﻳﻨــﺔ ﻧﺼــﺮ- ( ﺷـﺎرع اﻟﻄﻴـــﺮان ) ﻣﺤﻤﻮد ﺷــﻠـﺘﻮت25 :اﻹدارة
Tel. : ( 02 ) 22620642 - ( 02 ) 22616760 - ( 02 ) 24016523 ( 02 ) 24016523 - ( 02 ) 22620642 - ( 02 ) 22616760 :ﺗﻠﻴﻔﻮن
Factories : 10th of Ramadan City - Industrial Zone ( B1 ) 1 اﻟـﻤـﻨـﻄـﻘـــــﺔ اﻟـﺼـﻨـــﺎﻋـﻴـﺔ ب- ﻣـﺪﻳـﻨـــــﺔ اﻟﻌــﺎﺷـــــﺮ ﻣـﻦ رﻣﻀـــﺎن: اﻟﻤﺼﻨﻊ
Tel. : (015)360234-(015)369066-(015)351833-(015)364685 (015) 364685 - (015)351833 - (015)369066 - (015)360234 :ﺗﻠﻴﻔﻮن
Head Office Fax : ( 02 ) 24035260 Factories Fax: (015)351834 (015) 351834 : ف اﻟﻤﺼـﻨــﻊ ( 02 ) 24035260 : ف اﻻدارة
ITEM NO. : 1
TITLE : MDB-CS
QTY. : 1
INSTALLATION:
● Indoor.
● FreeStanding.
CONSTRUCTION:
● Type test - Prisma iPM "System M".
● IP 54.
INLET AND OUTLET:
● # Incoming :- Top/Bottom
● # Outgoing :- Bottom
MAIN BUSBAR:
● Short-circuit withstand 36KA.
# INCOMING:
» 1 ACB NT-16-H1-3P MICR-2.A - Fixed Type, (Ir=1600A/42KA S.C)
Adj. Over-Load Trip (0.4-1) In , Adj. Short-Circuit Trip (1.5-10) Ir.
INSTRUMENT&MEASURMENT:
3 Indicating lamps (R-S-T).
3 Current Transformer (1600/5A).
1 Power Monitoring PM200 Basic Version.
6 Fuse 1A + Holder.
# OUTGOINGS:
TO ATS:
» 1 MCCB NSX630F 3P3T Micrologic 2.3 630A,(Ir=400A/36KA S.C)
Adj. Over-Load Trip (0.4-1) In , Adj. Short-Circuit Trip (2-10) Ir.
TO BCP-X:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
TO BCP-FH:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
TO BCP-FR:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
TO BCP-TH:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
TO BCP-S:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
TO BCP-F:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
TO BCP-GS:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
TO BCP-B1:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-B2:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-WT1:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
TO BCP-GC1:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-GC2:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
SPARE:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
SPARE:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
SPARE:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
SPARE:
» 1 MCCB NSX250F 3P3T TM200D,(Ir=160A/36KA S.C)
Adj. Thermal (0.7-1) In , Adj. Magnetic (5 -10) In.
Power factor correction 200KVAR:
» 1 MCCB NSX400F 3P3T Micrologic 2.3 400A ,(Ir=400A/36KA S.C)
Adj. Over-Load Trip (0.4-1) In , Adj. Short-Circuit Trip (2-10) Ir.
Fixed step 100 KVAR:
» 1 Low Voltage Capacitors 100KVAR.
» 3 1-P - H.R.F.C 250A.
1 Indicating lamps for step.
Variable steps (4*25 KVAR):
» 4 Low Voltage Capacitors 25KVAR.
» 4 Contactors for capacitor switching type LC1DMK11M7.
» 12 1P - HRFC - 125A.
» 1 Power factor controller NR6 - 6 STEPS.
4 Indicating lamps for controller steps.
ITEM NO. : 2
TITLE : EMDB-CS
QTY. : 1
INSTALLATION:
● Indoor.
● FreeStanding.
CONSTRUCTION:
● Type test - Prisma iPM "System M".
● IP 54.
INLET AND OUTLET:
● # Incoming :- Top/Bottom
● # Outgoing :- Top/Bottom
MAIN BUSBAR:
● Short-circuit withstand 36KA.
# INCOMING:
» 1 MCCB NSX630F 3P3T Micrologic 2.3 630A,(Ir=400A/36KA S.C)
Adj. Over-Load Trip (0.4-1) In , Adj. Short-Circuit Trip (2-10) Ir.
INSTRUMENT&MEASURMENT:
3 Indicating lamps (R-S-T).
3 Current Transformer (600/5A).
1 Power Monitoring PM200 Basic Version.
6 Fuse 1A + Holder.
# OUTGOINGS:
TO BCP-EX:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-EFH:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-EFR:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-ETH:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-ES:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-EF:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-EGS:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
ELEVATOR:
» 4 MCCB NSX100F 3P3T TM63D,(Ir=63A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
P.FAN:
» 2 MCCB NSX100F 3P3T TM32D,(Ir=32A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-EB1:
» 1 MCCB NSX100F 3P3T TM50D,(Ir=50A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-EGC1:
» 1 MCCB NSX100F 3P3T TM25D,(Ir=25A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO BCP-WT2:
» 1 MCCB NSX100F 3P3T TM32D,(Ir=32A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO SUMP.PIT1:
» 1 MCCB NSX100F 3P3T TM32D,(Ir=16A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
TO SUMP.PIT2:
» 1 MCCB NSX100F 3P3T TM32D,(Ir=16A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
SPARE:
» 1 MCCB NSX100F 3P3T TM32D,(Ir=32A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
SPARE:
» 1 MCCB NSX100F 3P3T TM32D,(Ir=32A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
SPARE:
» 1 MCCB NSX100F 3P3T TM63D,(Ir=63A/36KA S.C)
Adj. Thermal (0.7-1) In , Fixed Magnetic.
ITEM NO. : 3
TITLE : ATS-FIRE
QTY. : 1
INSTALLATION:
● Indoor.
● Free standing.
CONSTRUCTION:
● Type test - Prisma iPM "System M".
● IP 54.
MAIN BUSBAR:
● Short-circuit withstand 50KA.
# INCOMING:
» 1 Source changeover ( ATS ) Compact NSX630N-4P-Micrologic 2.3 (Ir=400A/50KA)
Adj. Over-Load Trip (0.4-1) In , Adj. Short-Circuit Trip (1.5-10) Ir.
ATS contains only two motorized circuit breakers and the necessary auxiliaries for electrical and
►
mechanical interlock.
Complete with :
4 Auxiliary contacts (changeover).
2 MN 220/250VAC (under voltage).
4 Push Buttons (ON-OFF).
1 Selector (M-0-A).
» 1 Control circuit by PLC to achieve 1 out of 2.
INSTRUMENT&MEASURMENT:
6 Signal lamps (ON-OFF-TRIP).
9 Indicating lamps (R-S-T).
6 Current Transformer (600/5).
2 Digital Meter DM6000 V,I,F,CosØ.