Professional Documents
Culture Documents
3 - SG3125HV Troubleshooting Book EN
3 - SG3125HV Troubleshooting Book EN
Contents
1. Product Appearance............................................................................................................ 6
3.5 Control Cabinet Temperature Fault (Temp control cabinet flt) ....................... 36
Page 1 of 65
CONFIDENTIAL I
................................................................................................................................................ 41
3.28 CT Unbalanced........................................................................................................... 59
Page 2 of 65
CONFIDENTIAL I
Page 3 of 65
CONFIDENTIAL I
Upgrade history:
no. by reason by
Page 4 of 65
CONFIDENTIAL I
specifies the parameters of the inverter, the basic structure, the function of PCB and
definition of interfaces, the analysis of faults and upgrading of software. Since this
guideline takes the SG3125HV inverter with standard configuration for example,
there may be differences relating to the cable connection in different versions. This
Page 5 of 65
CONFIDENTIAL I
1. Product Appearance
This section introduces the inverter version, main components and layout as
Indicators
Inverter LCD
Network port
Emergency stop
button
Front view
Page 6 of 65
CONFIDENTIAL I
Inverter unit
module
Measuring board
DC charge/discharge
board
Fans
PMD power
AC contactor of
box
inverter unit
Standby power
board
Intelligent unit/IO
Brach
insulation
AC switch
monitoring
board
AC fuse block
Page 7 of 65
CONFIDENTIAL I
Inverter AC cabinet
Temperature &
humidity collection
board
Smoke sensor
DC switch
DC fuse
Inverter DC cabinet
Inverter state
indicators
Inverter LCD
Network port
Inverter emergency
stop button
Inverter panel
Page 8 of 65
CONFIDENTIAL I
Refer to the following figure for the PCB system diagram of SG3125HV.
Branch current
DC current AC current
sampling A1 A2
sampling sampling
DC1+
DC1- = ~
~ Filter Grid
DCm+ ~
DCm+ Contactor AC
DC switch
DC PE voltage Driver
8 board Internal AC Grid current Grid voltage PE
switch sampling voltage
1. IGBT driver sampling sampling
sampling
2. Driver fault
detection AC SPD
DC SPD Power and signal
4
Branch and insulation 1 DSP board (PA) 2
detection (PL)
conditioning (PD)
1. DC current, leakage
1. Monitor branch 1. Sampling signal
current
current
conditioning Standby power box
2. 3-phase AC current 7
2.Control branch switch (PH)
3.Monitor DC insulation
3. Carrier syn 2. Input and output
Low consumption
resistance RS485 4. Communication IO control
supply at night
5. Driver signal
DC dis-/charge
5 3 Measurement board (PG) 6 LVRT power box (PE)
board (PZ)
RS485 AC & DC redundant
1. DC charge 1. Sampling signal conditioning
2. DC discharge 2. Input and output IO control supply
Inversion unit
RS485
Intelligent
Temperature and
10 unit/IO(PT) 9
humidity board (PW)
1. Communicate to inverter
1. Monitoring of OMD
2. Communicate to touch
CAN screen RS485 state
3. Communicate to server 2. Communication of
end temperature and
4. For external device
communication humidity board
Inverter
As shown in the figure above, the system PCB is mainly inside the inverter unit and
the inverter. Inside the inverter unit are the DSP control board, power and signal
DC charge/discharge board, LVRT power box, standby power box, and driver board.
Inside the inverter are the intelligent unit or IO board and the temperature &
humidity collection board. The following section will describe the functions and
Page 9 of 65
CONFIDENTIAL I
Code in
No. PCB name Position Fucntions
diagram
Current signal sampling; CAN, RS485
In the front of communication and carrier fiber optic
DSP control the AC transmission circuit; IGBT driver signal
1 PA
board cabinet of the modulator circuit; DSP peripheral circuit
inverter unit and related control algorithm and logic
realization.
Voltage signal sampling; temperature
In the front of sampling; input node (e.g. feedback
the AC node of contactor, reactor
2 Pinbaord PD
cabinet of the over-temperature node and etc.)
inverter unit detection; output node (e.g. discharge
board, AC contactor control and etc.)
Inverter input & output electric
In the front of parameter measurement; logic
Measrument the AC realization of low power consumption at
3 PG
board cabinet of the night; PID power suppression or repair
inverter unit mode control; RS485, CAN and LAN
communication.
Branch Branch current sampling; DC switch trip
On the left of
insulation control; detection of DC positive &
4 the AC PL
monitoring negative resistance to the ground; RS485
cabinet
board communication.
In the front of
DC charge & DC bus charge at SVG mode and DC bus
the inversion
5 discharge PZ discharge when the AC & DC input is
cabinet of the
board disconnected
inverter unit
In the front of
the inversion
cabinet of the AC & DC double input redundant power
LVRT power
5 inverter unit PE supply; supply power to PCB, AC
box
On the left of contactor and DC switch
the AC
cabinet
Standby In the front of Supply power to the communication unit
6 PH
power box the inversion at the low power consumption mode
Page 10 of 65
CONFIDENTIAL I
cabinet of the at night
inverter unit
On the right
of the AC
cabinet
Power For conditioning and driving of power
8 Driver board /
module tube driver signal
Temperature On the top of For detection of the temperature and
9 PW
&huditiy the inverter humidity inside the inverter
For communication with the inverter
On the right unit, touch screen and the server end,
Intelligent
10 of the AC PT and integrate the communication with
unit/IO
cabinet external devices like the PVS and
transformer.
This section will describe the definition of the abovementioned PCB interfaces.
troubleshooting.
Page 11 of 65
CONFIDENTIAL I
Page 12 of 65
CONFIDENTIAL I
The definition of the interfaces in the DSP control board is shown in Table 3.
Page 13 of 65
CONFIDENTIAL I
5 Grid-side voltage
sampling
5 Sampling of negative
voltage to GND
5 DC voltage sampling
Page 14 of 65
CONFIDENTIAL I
Page 15 of 65
CONFIDENTIAL I
Please refer to the circuit diagram of the corresponding version for details since the
devices connected by the abovementioned interface and the cable connection are
Page 16 of 65
CONFIDENTIAL I
complex.
corresponding circuit diagram. Please see Figure 9 for the description of the
interfaces.
st
1 1 DC voltage sampling
nd
1 2 DC voltage sampling
9 DC insulation
detection control
rd
1 3 DC voltage sampling
th
1 4 DC voltage sampling
10 DC cabinet fan control
1 DC voltage sampling
Page 17 of 65
CONFIDENTIAL I
The definition of the interfaces in the branch current insulation detection board is
shown in Table 6.
Table 6 Definition of the interfaces in the branch current insulation detection board
Page 18 of 65
CONFIDENTIAL I
T1 transformer input
1
The definition of the interfaces in the DC charge & discharge board is shown in
Table 7.
Page 19 of 65
CONFIDENTIAL I
The LVRT power box is identified by PE in the corresponding circuit diagram. Please
The definition of the interfaces of the LVRT power box is shown in Table 8.
Page 20 of 65
CONFIDENTIAL I
PQ
Positive input of
4 Output 24VD power PQ capacitor board
PQ
Control the power supply to the coil of
5 DC output AC main contactor
the main contactor
24V power Supply power to all PCB and touch Cable connection terminal
6
output screens of the inverter block XB1
T1 transformer T1 power supply
7 Output 24VD power
input transformer
The definition of the interfaces of the standby power box is shown in Table 9.
Page 21 of 65
CONFIDENTIAL I
Please see Figure 13 for the description of the interfaces in the driver board.
Page 22 of 65
CONFIDENTIAL I
1 Driver flat cable 4 T3 tube driver 5 T1 tube driver 6 T4 tube driver
3 T2 tube driver
2 NTC
The definition of the interfaces in the driver board is shown in Table 10.
Page 23 of 65
CONFIDENTIAL I
The definition of the interfaces in the intelligent unit board is shown in Table 12.
Page 24 of 65
CONFIDENTIAL I
the XB9 cable connection between the PMD and the terminal
external network
terminal
24V terminal block of
6 24V power input Supply power to intelligent unit
the PMD
Reserved (defined according to Reserved (according
7 Digital input the circuit diagram of the actual to the circuit
version) diagram)
Reserved (defined according to Reserved (according
8 Digital output the circuit diagram of the actual to the circuit
version) diagram)
Network communication Used for communication
9 connected to the inverter between the PMD and the Inverter panel
Page 25 of 65
CONFIDENTIAL I
The definition of the interfaces in the temperature & humidity board is shown in
Table 13.
Page 26 of 65
CONFIDENTIAL I
The fault or alarms of the SG3125HV inverter displayed in the touch screen is
If the power supply of the device is normal and the LCD works normally, do not
Page 27 of 65
CONFIDENTIAL I
disconnect the power supply nor restart the device. Collect the following
information:
(1) Enter the software version interface to record the device software version
number.
(2) Record the history fault before and after this fault from the LCD.
Page 28 of 65
CONFIDENTIAL I
(3) Record the history event before and after this fault from the LCD.
(4) Copy the history data stored in the USB on the back of the LCD.
(5) Record the DSP running information protected by Class II password from
the LCD, especially the PDP fault code information for PDP protection.
Page 29 of 65
CONFIDENTIAL I
(6) Record the related power yields, voltage, current, temperature and other
data from the main interface and the running information interface.
(7) Perform fault recording to the failed device. Save the recording data in
format of .xml.
If the device LCD has no power supply, check if the fuse F32 is damaged (the LED in
the enclosure flashes) and if the micro-switch Q15 is disconnected. If the IGBT is
broken, connect the AC circuit breaker after replacing the IGBT and supply control
power to the device. When the LCD works normally, record the device fault data.
For the specific data, please refer to the requirements mentioned above.
terminal connection, PCB and other related components of the failed device
before troubleshooting, and then record related data. Do not disconnect the
The following section will introduce the corrective measures of fault or alarm in
detail.
Page 30 of 65
CONFIDENTIAL I
The detection condition and corrective measures of PDP protection are described
in Table 14.
Flt code
Corrective
measures
The corrective measures for the several types of PDP protection faults are shown
below (all the three units are the same; hereinafter will take unit 1 for example):
1) Phase A1 overcurrent: if this fault occurs occasionally, send the fault data to
R & D department for judgment; if this fault occurs frequently, replace the
PA board and PD board;
2) Phase B1 overcurrent: if this fault occurs occasionally, send the fault data to R
& D department for judgment; if this fault occurs frequently, replace the PA
board and PD board;
3) Phase C1 overcurrent: if this fault occurs occasionally, send the fault data to
Page 31 of 65
CONFIDENTIAL I
R & D department for judgment; if this fault occurs frequently, replace the
PA board and PD board;
4) Reserved
5) Reserved
6) Reserved
7) DC overcurrent: if this fault occurs occasionally, send the fault data to R & D
department for judgment; if this fault occurs frequently, replace the PA
board and PD board;
8) Phase A1 PDP corresponds to phase A1 module: there may be problems to
the phase A1 driver and the IGBT of phase A1. Test the resistance of module
GE; if the resistance is normal, replace the driver.
9) Phase B1 PDP corresponds to phase B1 module: there may be problems to
the phase B1 driver and the IGBT of phase B1. Test the resistance of module
GE; if the resistance is normal, replace the driver.
10) Phase C1 PDP corresponds to phase C1 module: there may be problems to
the phase C1 driver and the IGBT of phase C1. Test the resistance of module
GE; if the resistance is normal, replace the driver.
11) Reserved
12) Reserved
13) Reserved
14) Module 1 shoot-through: send the fault data to R & D department for
judgment;
15) Reserved
Note
The above mentioned PDP protection classification and analysis of the fault code
1) The signal output of the driver FA is low level and the device reports PDP
protection;
4) The PDP fault code in the DSP running information is hexadecimal code and it
Page 32 of 65
CONFIDENTIAL I
The detection condition and corrective measures of contactor fault and contactor
Page 33 of 65
CONFIDENTIAL I
open, replace the LVRT power box and retest. If the problem does
not occur, there is problem to the power box; if not, the contactor
is failed.
c) If there is voltage to the main contactor coil but the contactor
cannot close, the contactor is failed.
Note
Auxiliary contact of main contactor
Fault Mism-Iac
Type Device stops
Detection
The current sampling values for either two phases deviate for 10%In.
condition
1、 Check if the AC grid is normal.
Check if there is phase loss situation.
2、 Check the PA board and the current sampling cable.
Corrective Test if the PA board and the current sampling cable are normal by replacing them
measures in turn.
3、 Check the 3-phase current sensor under the power module.
Test if the 3-phase current sensor is normal by replacing it. Locate the specific
group with the help of the fault data when necessary.
Page 34 of 65
CONFIDENTIAL I
AC current sampling
Note
AC 3-phase sensor
Note
Page 35 of 65
CONFIDENTIAL I
Axial fan
PA, PD board
cabinet flt)
Page 36 of 65
CONFIDENTIAL I
Uab Ubc
Voltage/V
Inverter RUN Inverter Stop
Ib Ia
Current/A
Record point
120℃ thermorelay
Note
Filter capacitor
Page 37 of 65
CONFIDENTIAL I
in Table 20.
Fault DC undervoltage
Type Device stops
Detection DC voltage is below 500V during inverter operation and the device stops due to
condition this fault
1、 Check if there is short-circuit in the DC side.
(1) Measure the actual DC voltage and check the DC side cable.
(2) Analysis according to the fault data.
Corrective
2、 Check the DC voltage sampling channel.
measures
Check if the DC voltage displayed in the touch screen is the same with the
measured value when the device stops. Confirm by replacing the PA and PD
board when necessary.
3、 Driver board
If all the above mentioned items are normal, check the related power module.
Confirm by replacing the driver board when necessary.
Note
The detection condition and corrective measures of neutral point potential offset
Page 38 of 65
CONFIDENTIAL I
overcurrent, DC undervoltage fault. If yes, refer to the related
troubleshooting method; if no, test if the PA board, PD board, driver flat
cable, driver board and the power module are normal by replacing them in
turn.
DC+, DC-
Neutral point
Note
DC-
DC neutral point
DC+
The detection condition and corrective measures of temperature anomaly fault are
Page 39 of 65
CONFIDENTIAL I
temperature of air inlet exceeds 55℃.
1、 Measure the ambient temperature.
Measure by thermodetector if the ambient temperature is within the allowable
range for inverter operation.
2、 Check the container and the air inlet of the inverter unit.
Check if the dustproof cotton needs to be replaced and if the air inlet is blocked.
Corrective
3、 Check the functionality of the cooling fan.
measures
Refer to the 1st troubleshooting method of the module over-temperature.
4、 Check the PD board, temperature sampling cable and NTC temperature
sensor.
Test if the PD board, temperature sampling cable and NTC temperature sensor
are normal by replacing them in turn.
Page 40 of 65
CONFIDENTIAL I
The detection condition and corrective measures of islanding are described in Table
Page 41 of 65
CONFIDENTIAL I
24.
Fault Islanding
Type Device stops
Detection
Grid power off or the AC transient voltage exceeds 140%.
condition
1、 Check if the grid is normal.
Check if there is islanding to the grid according to the fault recording data and
Corrective
the history fault from the touch screen.
measures
2、 Check the grid voltage sampling channel.
Check if the sampling cable, PD board or the PA board are normal.
Note
The detection condition and corrective measures of DC voltage sampling fault are
Page 42 of 65
CONFIDENTIAL I
Ground sampling
Note
DC- sampling
DC+ sampling
The detection condition and corrective measures of soft start fault are described in
Table 27.
Page 43 of 65
CONFIDENTIAL I
INV-C
PM1 INV-B
INV-A
Net-C
Net-B
Note
Net-A
The detection condition and corrective measures of SPD fault are described in Table
28.
Page 44 of 65
CONFIDENTIAL I
Test if the node sampling cable, PD board (AC SPD) and the branch board PL (DC
SPD) are normal by replacing them in turn.
Note
Notice: since the node of DC SPD is connected to the branch board (PL) and
transmit to the DSP board (PA) by communication, check if the PL is normal when
locating the cause of DC SPD fault.
in Table 29.
Fault DC overvoltage
Type Device stops
Detection
Device stops when the DC voltage exceeds 1500V.
condition
1. Check the actual configuration of the PV array.
Disconnect the inverter DC switch and check the open-circuit voltage of the PV
array.
2. Check if the neutral point of the AC side transformer is grounded.
Check if the AC transformer is connected according to requirements. When the
low voltage side is connected in star, the neutral point cannot be grounded.
Corrective 3. Check the DC voltage sampling channel of PD board.
measures Check if the DC voltage displayed in the touch screen is the same with the
measured value when the device stops.
4. If the fault occurs in the moment of grid-connection and the transformer
isolation and neutral point are correct, check if the sequence of the AC
voltage, current sampling or the driver cable.
Check if the PA current sampling channel, PD AC voltage sampling channel and
the 3-phase driver flat cable are connected correctly.
Note
Page 45 of 65
CONFIDENTIAL I
The detection condition and corrective measures of carrier synchronization fault are
DIP switch
Note
Carrier optic
INV#1
INV#2
INV#3
ON ON ON
1 2 3 4 1 2 3 4 1 2 3 4
Page 46 of 65
CONFIDENTIAL I
#1 Inverter #2 Inverter #3 Inverter
Note
The detection condition and corrective measures of device code repeating fault are
Page 47 of 65
CONFIDENTIAL I
Fault Device code repeating fault
Type Device stops
The ID codes for two or more units in parallel connection are set to be the same and
Cause
device reports encoding repeat fault.
Correcti Check the DIP switch in the PA board.
ve Check if the DIP switch positions for two or more units in the PA board are set to be
measure the same. If yes, reset after disconnecting the power supply; if no, replace the PA
s board to test if it is normal.
Set the DIP switch in the PA board as follows:
ON ON ON
Note
1 2 3 4 1 2 3 4 1 2 3 4
Page 48 of 65
CONFIDENTIAL I
Note
The detection condition and corrective measures of hardware fault are described in
Table 34.
Overload-pro)
Page 49 of 65
CONFIDENTIAL I
The detection condition and corrective measures of leakage current protection are
Page 50 of 65
CONFIDENTIAL I
Leakage current
Page 51 of 65
CONFIDENTIAL I
2. Check the functionality of the cooling fan.
If the fan does not work, refer to the fan troubleshooting for the next step.
3. Check the PA board, the driver flat cable, the driver board and the power
module.
Test if the PA board, the driver flat cable, the driver board and the power module
are normal by replacing them in turn.
PA
Driver board NTC temperature sampling
Note
The detection condition and corrective measures of fan fault are described in Table
38.
Note
Page 52 of 65
CONFIDENTIAL I
The present fan type is EBM. View the related information in the set parameter
interface after entering the class II password. The following section will describe the
fan state and alarm bit definition (as shown in the figure below) in the password
protected interface. Note that the fan state and the alarm bit are displayed in
hexadecimal.
Page 53 of 65
CONFIDENTIAL I
Fan state
Alarm state
Page 54 of 65
CONFIDENTIAL I
Power limitation in mesh 1:Fault
TE_high 0:Normal
b3
Output stage temperature high 1:Fault
TM_high 0:Normal
b4
Motor temperature high 1:Fault
TEI_high 0:Normal
b5
Electronics interior temperature high 1:Fault
UzLow 0:Normal
b6
DC-link voltage low 1:Fault
0:Normal
b7 Brake
1:Fault
0:Normal
b8 Reserved
1:Fault
0:Normal
b9 n_Low
1:Fault
0:Normal
b10 Cable break
1:Fault
0:Normal
b11 Reserved
1:Fault
0:Normal
b12 Reserved
1:Fault
0:Normal
b13 Reserved
1:Fault
0:Normal
b14 Reserved
1:Fault
0:Normal
b15 Communication between fan and controller is fail
1:Fault
Example:
The EBM fan state 1010 (hexadecimal) can be converted into binary:
0001 0000 0001 0000. According to the table above, the fan state is DC-link
For the analysis of other fan state code and alarm code, please refer to this section.
Please notice that when the fan operates normally, the EBM state code is 0.
Page 55 of 65
CONFIDENTIAL I
The detection condition and corrective measures of GFDI protection are described
in Table 39.
Note
Page 56 of 65
CONFIDENTIAL I
Notice: DO not pull or insert the fuse under voltage. Operate when the DC is
discharged completely.
Page 57 of 65
CONFIDENTIAL I
Note
Note
Notice: connect the RS485 communication cable of the PL board to the RS485 of
Page 58 of 65
CONFIDENTIAL I
the PA board of the 3 inverter units
3.28 CT Unbalanced
Table 47.
Fault CT unbalanced
Type Device alarms but does not stop
Difference between the sampling currents of either two phases of the
Cause
measurement board is 120A; device does not stop
1. Check the current sampling channel of the measurement board.
(1) Observe if the current transformer (CT) between the AC switch and the AC
Corrective
contactor is damaged.
measures
(2) Test if the PG board, the current sensor of the measurement board and the
current sampling cable are normal by replacing them in turn.
Note
AC CT
The detection condition and corrective measures of GFRT run are described in Table
48.
Page 59 of 65
CONFIDENTIAL I
Page 60 of 65
CONFIDENTIAL I
2. Check the air inlet of the container and the inverter unit.
Check if the dustproof cotton needs to be replaced and if the air inlet is blocked.
3. Check the functionality of the cooling fan.
Refer to the 1st troubleshooting method of the module over-temperature.
4. Check the PD board, temperature sampling cable and NTC temperature
sensor.
Test if the PD board, temperature sampling cable and NTC temperature sensor
are normal by replacing them in turn.
Note
PD board temperature
sampling node
com-flt)
Page 61 of 65
CONFIDENTIAL I
Fault DSP-MDC communication anomaly
Type Device alarms but does not stop
Communication between the PA board and the measurement board PG is
Cause
abnormal; device does not stop
1. Check the PA, PG board and the communication cable.
(1) Check if the DIP switch in the PA board is set correctly; refer to the device
Corrective encoding repeat and parallel operation communication fault method for
measures troubleshooting.
(2) Test if the PA, PG board and the communication cable are normal by
replacing them in turn.
Note
Page 62 of 65
CONFIDENTIAL I
Note
fwd/rev-ldc-high)
Page 63 of 65
CONFIDENTIAL I
2. Check the DC branch current.
Decrease the grid-connected output power and check if the LCD branch current is
abnormal. If the branch current difference is too big, measure the actual current of
each branch by ammeter. if the branch current difference is small, replace the DC
detection board. If the actual current difference is too big, maintain the branch with
the bigger current.
Note
(T&H-com-flt)
The detection condition and corrective measures of temperature & humidity board
Page 64 of 65
CONFIDENTIAL I
Note
Page 65 of 65