AHU TFA Check List & Air Balancing Sheet

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 8

AHU/TFA INSTALLATION CHECK LIST

Project name:
AHU/TFA Tag Name:
Sl No. Check Points

1 AHU Floor plans, schematic & Technical Data sheet approved from Daikin
2 AHU Control Kit installed as per installation manual
3 AHU Control Kit Wiring's continuity checked
4 Capacity setting adapter of AHU Control kit connected properly
5 Control Kit F1 & F2 terminal are looped with ODU's.
6 AHU Starter's panel Auxillary contactor integrate with Control box C1 & C2 Terminal
7 AHU Starter's panel Auxillary contactor integrate with limit switch & marine light
8 AHU's control box covered for weather protection
9 VFD's frequency set corrosponding to desired Airflow
10 If VAVs in system, Are they calibrated
11 Liquid, Gas & Return Air thermistor installed as per installation manual.
12 Ductwork intact and properly sealed.
13 Ductwork leak tested.
14 Access doors installed and properly secured.
15 Ductwork installed according to the drawings and specification.
16 Ductwork free from debris.
17 Dampers, including fire and smoke dampers, installed and accessible.
18 Terminal boxes, reheat coils, electrical reheat, etc. installed, functional and accessible.
19 All other air distribution devices such as diffusers, etc., installed and functional.
20 Return air has an unobstructed path from each conditioned space back to the unit.
21 Filters clean and correctly installed.
22 Filter frame properly installed and sealed.
23 Coils cleaned and properly installed.
24 Drive components properly installed.
25 Pulleys properly aligned and tight on their shafts.
26 Belts adjusted for the correct tension.
27 Fan dampers functional.
28 Flexible connections installed properly.
29 Fan bearings lubricated
30 Fan Rotation checked
ATION CHECK LIST

Date:

Yes No Remarks
AHU/TFA AIR BALANCING AT SUPPLY AIR COLLAR / RETURN A
S.No. Location Item CFM Collar Design Airflow Reading

Collar No No CFM V1(fpm) V2(fpm) V3(fpm) V4(fpm) V5(fpm) V6(fpm) V7(fpm)


SAC 1 Supply
SAC 2 Supply
SAC 3 Supply
SAC 4 Supply
SAC 5 Supply
SAC 6 Supply
SAC 7 Supply
SAC 8 Supply
SAC 9 Supply
SAC 10 Supply
1 AHU 10000
RAC 1 Return
RAC 2 Return
RAC 3 Return
RAC 4 Return
RAC 5 Return
RAC 6 Return
RAC 7 Return
RAC 8 Return
RAC 9 Return
RAC 10 Return
LY AIR COLLAR / RETURN AIR COLLAR SIDE
Average Average Velocity(fpm) Collar Collar CFM Value(Flow Velocity

V(ft/minute) X Duct cross


Grille
cofficient section Area(ft) x Grille

V8(fpm) V9(fpm) V10(fpm) Velocity(fpm) Size(mm²) Size(Feet²) cofficient


0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
0.55 1000X200 2.15 0
1 mm= 0.00328 feet
AHU/TFA AIR BALANCING AT FILTER SIDE

Report No. Date / Time :

Unit Capacity:
Air Quantity at Return Air Filter:

Filter Size-610 X 610 mm Filter Area Quantity

Filter Size-610 X 305 mm Filter Area Quantity

Filter Size-305 X 305 mm Filter Area Quantity

Average Reading
X Filter Area
Actual Air Quantity at Filter
Date / Time :

Quantity

Quantity

Quantity

X Filter Area
AIR HANDLING EQUIPMENT AIR BALANCING REPORT

PROJECT: - CAPACITY: -
Date
Location :
AHU/TFA Tag Number

UNIT DATA MOTOR DATA


Make/Model No. Make
Type/Size KW
Serial Number POLE/RPM
Discharge Volts/Phase/cycles
Fan Dia FULL LOAD Amps.
Fan Pulley Dia /Bore Motor Pulley Dia /Bore
No. Belts/make/size
Fan Model /make
No .Filters /type. size

TEST DATA DESIGN ACTUAL REMARKS

Fan RPM
Voltage
R R
Y Y
Motor Current in Amps
B B

Outside air CFM at fresh air


damper side
Return air CFM at filter
side
Total CFM

REMARKS. Checked By : Approved By :