Professional Documents
Culture Documents
Power System Operation and Control
Power System Operation and Control
Control
1
Power Balancing Control
No. Control Name Time Frame Objectives
Power balancing, transient
1 Inertial Response < 5 seconds
frequency. (automatic)
Primary Control, governor 3 seconds to 10 Power balancing, transient
2
(Frequency Response) minutes frequency. (automatic)
Power balancing, steady-state
20 seconds to
3 Secondary Control (AGC) frequency. (automatic, signal-
20 minutes
based)
5 minutes to 1 Power balancing via economic
4 Tertiary Control (SCED/OPF)
hour dispatch.
• When the grid frequency falls below a predefined level, grid operators will
disconnect some customers from the grid to boost the frequency.
• If frequency drops too fast, RoCoF may be large, which will cause relays to trip
generators that lead to even less generation and then lower frequency.
Inertia
Heavy truck v.s. Compact sedan: when running at the same speed,
which one is harder to stop?
Inertia in power systems refers to the energy stored in large rotating generators and some
industrial motors.
• Solar/wind provides little inertia.
• Virtual inertia.
nadir
In addition to nadir, we also care about the initial Rate of Change of Frequency (RoCoF).
Lower inertia, higher RoCoF.
6
Inertia
• When a disturbance occurs, e.g. loss of a generator, the system would be short of
generation.
• The stored energy will then be extracted from the inertia of the spinning generators
and temporarily make up for the lost generator.
• This action will slow down the generators – Frequency drops.
• This will provide time for the mechanical systems in the grid to detect the imbalance
and react.
Inertia of a Single Machine
The inertia of a single machine is equal to the kinetic energy Ei stored in the rotating
shaft of synchronous generator, which is defined as:
1
Ei = Ji ω2n
2
1
𝐸𝑖 Ji ω2n
Hi = = 2
𝑆𝑖 𝑆𝑖
System Inertia (Multi-machine)
The power system inertia, Esys is equivalent to the rotating kinetic energy in the system.
The system inertia determines initial RoCoF.
1
Esys = Ei = Ji ω2n = Hi Si
2
Swing equation:
(sum over all generators) It describes the rotor
dynamics of a synchronous
generator 𝑖.
d𝜔𝑖 𝑃𝑖𝑀 − 𝑃𝑖𝐸
𝑅𝑜𝐶𝑜𝐹𝑖 = = ω P𝑖𝑀 : the mechanical power of generator 𝑖.
dt 2𝐻𝑖 S𝐵𝑖 𝑛 P𝑖𝐸 : the electrical output power of generator 𝑖.
The swing equation of the equivalent model can be applied to the whole system:
12
One-line Diagram
percentage 200 MW
100 MVR
1.00 pu
loading of
100 MW
lines 2 MVR
-33 MW -17 MW
150 MW AGC ON
10 MVR 5 MVR 100 MW
114 MVR AVR ON
33 MW 17 MW
-10 MVR -5 MVR
Bus 3 1.00 pu
100 MW
50 MVR Load
150 MW AGC ON
Bus 35 MVR AVR ON
Circuit Breaker
Power Balance Constraints