Shell Petroleum Development

Company of Nigeria

Specification for Structured Cabling System (Fiber and Copper)

Project Gbaran Phase 3B – Uzu with CPF Upgrade Project


Originating Company Ariosh Limited.
Specification for Structured Cabling System (Fiber and
Document Title
Copper)
Document Number UZU-SEDO-ZRMS2-TA7739-00002
Document Revision R01
Document Status Issued for Review
Originator / Author Adediran Adelu
Security Classification Restricted
ECCN EAR 99MM
Issue Date 6 June 2019
Revision History is shown next
page

Rev # Date of Issue Status Description Originator Checker Approver

R01 19 March 2019 Issued for Review Adediran Adelu ParlinSilalahi Kareem Sanni
ADDITIONAL AGREEMENT/APPROVAL RECORD

Restricted
ECCN: EAR 99 Deminimus
This document is made available subject to the condition that the recipient will neither use nor disclose the contents except as
agreed in writing with the copyright owner. Copyright is vested in Shell Petroleum Development Company Ltd. © All rights
reserved.
Neither the whole nor any part of this document may be reproduced or distributed in any form or by any means (electronic,
mechanical, reprographic, recording or otherwise) without the prior written consent of the copyright owner.
Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Party Ref Indicator Name Sign Date

Revision Philosophy:
a. All FEED documents for review shall be issued at R01, with subsequent R02, R03, etc as
required.
b. All documents approved for issue, or approved for design shall be issued at A01 with
subsequent A02, A03, etc. as required. (Management of Change is required for A02, A03,
etc.)
c. All Detailed Design documents for review shall be issued at D01, with subsequent D02,
D03, etc. as required.
d. All documents approved for construction shall be issued at C01 with subsequent C02,
C03, etc. as required. (Management of Change is required for C02, C03, etc.)
e. All approved “As Built” documents shall be issued at Z01, with subsequent Z02, Z03, etc.
as required. (Management of Change is required for Z02, Z03, etc.

Revision History
Rev No Date of issue Reason for Issue / Change

Hold Record
Hold No Details

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 2 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Table of Contents
1. INTRODUCTION 4
1.1. Asset Description 4
1.2. Project Overview 4
1.3. Purpose 6
1.4. Standards & Codes and References 6
1.4.1. Shell Design and Engineering Practice 6
1.4.2. International Standards 6
1.5. Order of Precedence 7
1.6. Environmental Design Criteria 7
1.6.1. General 7
1.6.2. Air Ambient Temperatures 8
1.6.3. Rainfall 8
1.6.4. Wind Speed 8
1.6.5. Entomology and Vermin 8
1.6.6. Fungi and Growths 8
1.6.7. Lightning 8
1.6.8. Dust 8
1.7. Area Classification 8
2. ABBREVIATIONS AND DEFINITIONS 9
3. DESIGN CONSIDERATIONS 10
3.1. General Design Philosophy 10
3.2. Local Area Network 10
3.3. Wide Area Network 11
3.4. Voice over IP (VOIP) 11
3.5. Hotline /Omnibus 11
3.6. PCD-IT Security 11
3.7. Bandwidth and Capacity 11
4. SYSTEM REQUIREMENT 11
4.1. WAN Design 12
4.2. LAN Design 12
5. TECHNICAL SPECIFICATION OF EQUIPMENT 13
5.1. ROUTER (ISR4451-X/K9) 13
5.2. CATALYST CORE SWITCH (CISCO WS-C4503E) 14
5.3. FIREWALL (HOLD) (CISO ASA 5525-X) 15
5.4. ACCESS SWITH (CISCO CATALYST C9300-24T-E) 16
5.5. 24 Ports UTP Patch Panel (Systimax 760152561) 17
5.6. RJ45 Cat6 UTP Jack for Voice and Data (Systimax 700206667) 18
5.7. Housing Cabinet 42 RU (RITTAL TS-8) 19
5.8. 19“Cabinet 12 RU (RITTAL FlatBox) 20
6. IP ADDRESS TABLE (HOLD) 20
7. TRAININGS 20
8. SPARE HOLDINGS 21

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 3 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

9. PACKING AND SHIPPING 21


10. EARTHING AND LIGHTNING PROTECTION 21
11. WARRANTY 21

1. INTRODUCTION
1.1. Asset Description
The Gbaran Integrated Oil and Gas node, situated in the seasonal fresh-water swamp covers an
area approximately 3,000 km2 spread across Bayelsa, Rivers and Imo states in the eastern part of
the Niger Delta. It is a major oil and gas production hub in SPDC, covering the following fields –
Gbaran, Etelebou, Kolo Creek, Adibawa, Adibawa NE, Ahia, Abasere, Enwhe, Mini-Nta, Obele
and Rumuekpe – in Oil Mining Leases (OMLs) 16, 17, 21, 22, 27 and 28. The geographic centre
of the Gbaran/ node is located at Gbaran, 100 km NW of Port Harcourt and 40 km NE of
Yenagoa.

The Gbaran Central Processing Facility (CPF) came on stream in year 2010 with a gas production
capacity of 1.0Bscfd and liquid production capacity of 120 Mbpd. There are remote field
manifold locations at Zarama, Kolocreek, Gbaran, Koroama and Epu for NAG well manifolds.
The Gbaran CPF gas production capacity was debottlenecked to 1.2Bscfd in 2013 and then
1.25Bscfd in 2017. Current project scope also includes capacity upgrade of the CPF to ca
1.4Bscfd.

Uzu is a greenfield, but in close proximity to Zarama producing field and 15km NE of Gbaran
CPF. Uzu field was discussed in 1971 and located in OML 28. Uzu appraisal well was drilled
from Zarama location (tagged ZARA015 well) thereby providing opportunity to utilize existing
facilities and RoWs in Zarama area.

1.2. Project Overview


SPDC JV with Shell as operator of OMLs 16, 17, 21, 22, 27 and 28 on behalf of the joint venture
partners, embarked on the Gbaran Phase 3B - Uzu with CPF Upgrade which aims to develop
815Bscf (UR) of gas and 11.5MMbbls (UR) of oil & condensate in order to meet SPDC’s
commitment to sustain NLNG gas supply obligation and grow oil production.

The project scope includes infill drilling involving 5wells with flowlines and a bulkline from the
Uzu field as well as facility upgrade at the Gbaran Central Processing Facility involving
installation of a 200MMscfd TEG dehydration train and the ancillary units, including Brownfield
tie-ins

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 4 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

New wells to be drilled as part of this development will be from two existing well locations;
Zarama 15 and Zarama 08-11 locations. Three NAG wells and one existing NAG well to be
completed will be clustered at Zarama 15 location, while 1NAG well and 1Oil well will be drilled
from the Zarama 08-11 location. Extension of Zarama 15 location will be required to
accommodate siting of a new well cellar (4 slots with provision for relief well) and a manifold
location, while free slots at Zarama 08-11 location will be used for the 1 NAG and 1 Oil well
drilling. Four NAG wells will be hooked up to the new Uzu-1 manifold (adjacent to Zarama 15
well location) via 8” x 0.5km 1500# NAG DSS flow lines and bulk flowed to a new Uzu-2
manifold at the Zarama NAG manifold location via new 16” x 8km 1500# CS bulkline. The new
NAG well at Zarama 08-11 location will be hooked up to the new Uzu-2 manifold via new 8” x
0.5km 1500# DSS flowline. The Uzu fluids will be evacuated via the existing 20-inch
Zaramabulkline to the Koroama Slug catcher at Gbaran CPF. A connection will be provided from
the new Uzu-2 manifold (at Zarama NAG manifold location) to the existing Zaramabulkline. The
existing Zarama NAG wells will be evacuated to the CPF via a new 16” x 10km CS bulkline
connected to the Zarama slug catcher via the LP (compression) manifold.

One oil well will also be drilled, completed and a new 6” x 1km 1500# CS Oil pipeline will be
tied in to existing 16” x 17.5km Zarama Oil bulkline en-route Gbaran CPF via a barred tee.

The CPF upgrade scope involves installation of a 200MMscfd TEG dehydration gas processing
train to existing Gbaran CPF in order to increase overall plant capacity to ca. 1.4Bscfd

Figure 1.1: Uzu field Development Scope Schematic

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 5 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

1.3. Purpose
The purpose of this document is to specify the minimum requirements of cables (fibre and
copper) for Telecommunication System to be installed for the Gbaran Phase 3B – Uzu Project.
Telecommunication Cabling System provides the wiring infrastructure facilities inside the Uzu
project site. The Cabling System includes Fiber Optic Cabling (FOC) and Copper Cabling
installations
FOC Network is able to provide inter-building LAN connectivity and CCTV cameras connection
to the central equipment.
Copper Cabling Network is able to provide both inter and intra-building connection of the various
equipment of LAN & Telephone, PAGA, ACS and Power Supply Systems.

1.4. Standards & Codes and References


Telecommunications systems in this project shall be developed in conjunction with this
philosophy and shall comply with the relevant SHELL Standard and Nigerian statutes and Rules
identified in the Project Specification for the Uzu Project. All telecommunication systems to be
provided shall comply with the Codes and standards listed below, as applicable. Deviations from
these must be identified by the Contractor and agreed with the Buyer (SPDC).

1.4.1. Shell Design and Engineering Practice

DEP NUMBER TITLE/DESCRIPTION


DEP.32.71.00.10-GEN (Version 41) Telecommunication for Onshore Facilities
DEP 32.71.00.30 -GEN Structured Cabling Systems for Telecommunications
DEP 32.71.00.11 -GEN Telecommunication Standards

1.4.2. International Standards


The National and International Standards and Codes listed below are the main reference
documents for the supply of the equipment. The list is not a definitive list, and shall be complied
with in addition to those standards/codes referenced within these documents. Latest editions of all
referenced documents shall apply.

CODE/STANDARD NUMBER TITLE/DESCRIPTION


ATEx 100a Products for Use in Hazardous Areas
BS 3939 Drawings
BS 5750 Part1 Quality Systems
BS 6656 Guide to Prevention of inadvertent ignition of
flammable atmospheres by RF Radiation

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 6 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

BS 6701 Installation of apparatus


IEC 61034 Measurement of smoke density of cables burning
under defined conditions
IEC 60754 Test on gases evolved during combustion of
materials from cables – Part1Graphic symbols for
Electrical Power, Telecommunications and
Electronic
IEC 60331 Fire-resisting characteristics of electrical cables
IEC 60502 Cables construction characteristics
IEC 60228 Conductors of insulated cables

1.5. Order of Precedence


In the event of any conflict in the application of specifications, regulations, codes and standards
listed, referenced or sub-referenced in the equipment specification as applicable to this project
and the associated Contract Documents, the following priority order shall apply:
 Nigeria national standards (Regulatory requirements, Statutory law and regulations)
 Specific project approved documents
 Corporate mandatory requirements and other DEP requirements
 International codes and standards

Latest editions of all International Codes and Standards shall be applicable in accordance with the
issue date of the documents to which they apply with reference to the date that the contract is
signed. In case of conflict, the regulations, codes and standards listed shall be applied in the
following priority order:
a) Government Legislation
b) Purchase order and subsequent change orders
c) Project Specification (PEFs, Project drawings, Data Sheets, Specification)
d) Shell DEPs and Standards
e) Industry Standards

1.6. Environmental Design Criteria

1.6.1. General
The environmental data listed below give an overview of the conditions prevalent in the Assa
North node. Further surveys are required during the execution phase to confirm the available
information. The information below forms the environmental basis of the design. The Vendor
shall give details of any design or operational limitations due to the climatic site conditions.

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 7 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

1.6.2. Air Ambient Temperatures


Mean minimum temperature: 23oC
Minimum temperature: 18oC
Mean maximum temperature: 31oC
Maximum air temperature: 41oC
Minimum swamp temperature: 25 oC (NB 23oC to be used wherever a
margin is required)
Ground temperature: 25 – 27.5 oC
Black-bulb temperature for oil: 80 oC
Humidity: 45 – 100 %

1.6.3. Rainfall
Heavy rainfall can be expected in the wet season during months of April through October.
Average annual rainfall: 3800 mm
Mean maximum hourly rainfall: 100 mm
Max daily rainfall: 180 mm

1.6.4. Wind Speed


Design Wind Speed: 35.6 m/s

1.6.5. Entomology and Vermin


As prevalent in the Niger Delta with thick forest and swamp habitat

1.6.6. Fungi and Growths


As prevalent in the Niger Delta with thick forest and swamp habitat

1.6.7. Lightning
Very frequent in the rainy season

1.6.8. Dust
During November / December of every year in the Harrmatan season, the atmosphere is laden
with extremely fine dust (particle size of 5 microns or less), which can penetrate equipment, block
air filters, etc.

1.7. Area Classification


Equipment will be located in areas classified hazardous as well as non-hazardous, as shown on
the Hazardous Area Classification Drawings documents, (UZU-SEDO-GBRG1-EA2310-00001).
Hazardous area equipment will, as a minimum, be certified for gas group IIC with a maximum
temperature classification of T4.

All telecom equipment for installation in hazardous areas shall be certified for use in the
particular classified area, shall have the correct temperature classification and equipment group
and shall be suitable for the particular environmental conditions, all as described in IEC 60079

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 8 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

2. Abbreviations and Definitions

Ø Diameter
ºC Degree Centigrade
A Ampere
AC Alternating Current
ACS Access Control System
AWG American Wire Gauge
BS British Standard
CAT6 Category Six
CCTV Closed Circuit Television
cm Centimetre
dB Decibel
DEP Design and Engineering Practice
FAT Factory Acceptance Test
FOC Fiber Optic Cable
FO Fiber Optic
FOPP Fiber Optic Patch Panel
g Gram
GB Gigabyte
GHz Gigahertz
GRP Glass Reinforced Plastic
HD High Definition
HDPE High Density Polyethylene
Hz Hertz
IEC International Electrotechnical Commission
IP Internet Protocol
Kbps Kilobits Per Second
Kg Kilogram
Kv Kilovolt
LAN Local Area Network

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 9 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

LSZH Low Smoke Zero Halogen


m Meter
m² Square Meter
mm Millimeter
Mbps Megabits Per Second
ms Millisecond
N Newton
PAGA Public Address and General Alarm
RU Rack Unit
SAT Site Acceptance Test
UTP Unshielded Twisted Pair
V Volt
VDC Volts Direct Current
VLAN Virtual Local Area Network

3. SYSTEM REQUIREMENTS
Telecommunication Cabling System provides the wiring infrastructure facilities inside the
Gbaran Phase 3B – Uzu with CPF Upgrade Project
site.
The Cabling System design provides an infrastructure predominately engineered for LAN
technologies, but also capable of supporting voice, terminal, video, and common legacy
telecommunications technologies; each telecom system is able to perform their particular
functionality by means of a dedicated FO and Copper Cabling infrastructure.

4. System Architecture and Description


Cabling topology to be implemented is hierarchical star – wired for all parts of the cabling
infrastructure by dedicated cables or by shared cables like for the interconnection of the CCTV
cameras on perimeter fence.
4.1. Fiber Optic Cabling System Description
FOC System comprises of
1.1.1 LAN System Cabling
 24 Cores Single Mode FO Armoured Cables (for LAN connectivity inter-building)
 24 Way Fiber Optic Patch Panel (for termination and distribution of LAN signals)
equipped with SC FO connector type
 Single Mode FO Pig Tails (to perform splicing of FO Cables).

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 10 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

1.1.2 CCTV System Cabling


 24 Cores Single Mode FO Armoured Cables (to provide CCTV perimeter and process
cameras connectivity towards central control equipment)
 24 Way Fiber Optic Patch Panel (for termination and distribution of CCTV signals)
equipped with SC FO connector type
 Closure for T-Joints (to provide branch splicing between 24 and 4 core cables)
 Single Mode FO Pig Tails (to perform splicing of FO Cables).

4.2. Copper Cabling System Description


Copper Cabling System comprises of:
1.1.3 Telephone System Cabling
 2 pairs x 0.6 mm Armoured Shielded Cable
 4 pairs x 0.6 mm Armoured Shielded Cable
 50 pairs x 0.6 mm Armoured Shielded Cable.

1.1.4 ACS Cabling


 2x1.3 mm² (16 AWG) Armoured Shielded Control Cable
 2x1.3 mm² (16 AWG) Un-Armoured Shielded Control Cable
 4x1 mm² Un-Armoured Shielded Cable
 8x0.3 mm² (22 AWG) Un-Armoured Shielded Cable
 2x2.5 mm² Un-Armoured Shielded Cable.

1.1.5 PAGA System Cabling


 2 pairs x 2.5 mm² Armoured Shielded Twisted Fire Resistant Cable for outdoor
loudspeakers
 2 pairs x 6 mm² Armoured Shielded Twisted Fire Resistant Cable for outdoor
loudspeakers
 2 pairs x 2.5 mm² Un-Armoured Shielded Twisted Fire Resistant Cable for indoor
loudspeakers
 3x2.5 mm² Armoured Shielded Fire Resistant Cable for outdoor flashing beacons
 3x6 mm² Armoured Shielded Fire Resistant Cable for outdoor flashing beacons

1.1.6 LAN and Supervisory System Cabling


 4 pairs UTP Cat6 Cable.

1.1.7 CCTV System Cabling


 4 pairs UTP Cat6 Cable.

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 11 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

5. SPECIFICATION OF FOC SYSTEM


This Section defines the technical specifications related to the FO Cables and accessories.
The following FO Cables will be provided:
 Outdoor 48 Cores Single Mode FO Armoured Cable
 Outdoor 24 Cores Single Mode FO Armoured Cable

5.1. Outdoor 24 and 48 Cores Single Mode FO Armoured Cables


As shown in the diagram below, the cables consist of 6 elements stranded around a Glass
Reinforced Plastic (GRP) central member. The elements are a combination of filled loose tubes
(each containing up to 12 optical fibers maximum), and solid fillers to give the required fiber
count. The tubes are filled with a synthetic oil based jelly, non-nutritive to fungus, electrically non
conductive, homogeneous and free from dirt and foreign matter. The tubes are stranded using the
reverse oscillating lay method. The cable core interstices are water blocked by means of water-
swellable elements. Non-metallic peripheral strength members are applied over the cable core, in
order to provide the required tensile strength. An inner polyethylene sheath is applied over the
cable core, followed by a copolymer coated corrugated steel tape, longitudinally applied over the
cable core acting as moisture barrier and rodent protection. Over the steel tape is then applied an
outer HDPE sheath.
1 - Dielectric central strength member
2 - Optical fibers
3 - Plastic loose tube, jelly filled
4 - Water-swellable elements (dry core)
5 - Peripheral strength members: glass yarns
6 - Inner black PE sheath
7 - Corrugated steel tape, longitudinally
applied with thermo bonded overlap (steel
thickness 0.15 mm)
Individual fibers in a multi-fiber cable are
often distinguished from one another by 8 - Outer black HDPE
color-coded jackets or buffers on each fiber
and are based on the standard EIA/TIA-598.

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 12 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Fiber SM MagniLight TM
Type

Fiber Extended Band Dispersion unshifted fiber


Description
ITU-T G.652 C/D
Reference IEC 60793-2-50 B1.3
Standards

Glass Geometry
Index Profile Step index, Match Cladding

Cladding Non- ≤1%


Circularity

Cladding 125 + 0.7 μm


Diameter

Core/Cladding Concentricity ≤ 0.8 μm


Error

Coating geometry
245 ± 5μm
Primary Coating Diameter
(Uncoloured)
250 ± 10μm
Primary Coating Diameter (Coloured)
Coating/Cladding concentricity error ≤ 12 μm

Mechanical characteristics

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 13 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Proof Test for 1 sec ≥1%

Coating mechanical removal with fiber stripper


Optical Characteristics of Cabled Fibers
Mode Field Diameter @ 1310 nm 9.2 ± 0.4 μm

Cable Cut Off Wavelength ≤ 1260 nm


Group Refractive Index @ 1310 nm 1.467
Group Refractive Index @ 1550 nm 1.468
Attenuation @ 1310 nm ≤0.37 dB/km
Attenuation @ 1383 nm ≤0.37 dB/km
Attenuation @ 1550 nm ≤0.23 dB/km
Attenuation @ 1625 nm ≤0.25 dB/km
Dispersion coefficient ≤3.5 ps/(nm*km)
in the range 1285-1330
nm

Dispersion coefficient ≤18 ps/(nm*km)


@ 1550 nm
Dispersion coefficient ≤22 ps/(nm*km)
@ 1625 nm
Zero Dispersion Wavelength 1302 – 1322 nm
(λ0)

Zero Dispersion ≤ 0.089 ps/(nm2 *km)


Slope

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 14 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Typical Dispersion ≤ 0.087 ps/(nm2 *km)


Slope
Attenuation Uniformity/Point Discontinuities ≤ 0.05 dB

These cables shall have the following mechanical characteristics:


Fiber Count UoM 24FO 48FO
Cable Diameter(nominal) Mm 18 18
Cable Weight (nominal) Kg/km 255 255
Tensile Strength (short term- N 3000
fibre strain ≤ 0,33%)

Tensile Strength (long term- N 1400


zero fibre strain )
Minimum Bend Radius mm 15 x cable Ø (Static)
20 x cable Ø (Dynamic)

Crush Resistance (short term) N/100mm 3000

Impact Resistance Nm 20
Temperature Performance •°C -20/+60 (Operation)
-10/+40 (Installation)
-40/+70 (Storage)

5.2. SYSTIMAX 360G2 1U Sliding Modular Cassette 24 Ways FO Patch Panel


In order to terminate the 24 Cores Outdoor SM FO Cables inside the relevant cabinet (LAN or
CCTV), a suitable FO Patch Panel will be provided. For this scope, FOPP model will be
SYSTIMAX 360G2 1U Sliding Modular Cassette Shelf.

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 15 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

SYSTIMAX 360G2 1U Sliding Modular Cassette Shelf shares a common panel style footprint
with system fiber connector panels and modules enabling field termination, field splicing and
factory termination in a single unit.
SYSTIMAX 360G2 1U Sliding Modular Cassette Shelf will have the following technical
specifications:.

Dimensions
Depth 457.2 mm
Height 44.45 mm
Width 482.60 mm
Weight 5.4 kg
General Specifications
Brand SYSTIMAX 360™ |
Product Type Modular cassette shelf
Rack Units 1
Shelf Movement Sliding

The above mentioned FOPP will be provided with necessary Adaptors, fusion splice trays, blank
panels and FO Pig Tails.

5.3. SYSTIMAX 360G2 1U Sliding Modular Cassette 48 Ways FO Patch Panel

In order to terminate 24 and 48 Cores Outdoor CCTV FO Cables inside the relevant CCTV
Cabinet, a suitable FO Patch Panel will be provided. For this scope, FOPP model will be
SYSTIMAX 360G2 1U Sliding Modular Cassette Shelf.
The above mentioned FOPP will be provided with necessary Adaptors, fusion splice trays and FO
Pig Tails.

1. The Emergency Glass Break Box will be directly connected to the Electromagnetic lock
feeding. Once it’s broken, the feeding will be interrupted and consequently the Electromagnetic
lock (Fail Safe type), always powered, will be unlocked and the door can be freed to open. The
break glass will be installed in series with electromagnetic lock feeding (Card controller → Break
glass → EM lock).

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 16 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

2. In the event of power failure on turnstile, it will be unlocked automatically (Fail safe type), so it
will allow the exit from Plant or the entry to the Plant.
3. In the event of F&G System alarm, all access points, either doors or gates, will be
automatically open exit way only.
4. In the event of power failure on vehicle barrier, vehicle barrier will be able to be manually
overridden.

5.4. 360G2 Mod Panel Blank


This Blank panel will be provided for all 24 Way FOPP in order to cover the adapter slots not
used as per relevant system application.
Technical Specification

Dimensions
Depth 2.5 mm
Height 30.48 mm
Width 91.44 mm
General Specifications
Brand SYSTIMAX 360™
SYSTIMAX®
Product Type Blank panel
Interface Feature, front Standard

5.5. 360G2 Mod Panel Blank


SYSTIMAX 360 Distribution Panel 12 SC, will have the following technical specifications:
Construction Materials
Fiber Type Zero water peak single mode fiber (G.652.D or
G.652.D | OS2)
General Specifications
Product Type Panel
Interface SC
Body Style Ganged

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 17 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Interface Feature Standard


Adapter Color Blue
Application Used in conjunction with 360 G2 1U
Brand SYSTIMAX 360™
Total Ports, quantity 12

5.6. Fusion Splice Tray Kit, stackable, large format


SYSTIMAX 360G2 1U/2U Sliding Modular Cassette will be provided with a proper fusion splice
kit depending on the number of fibers to terminate. Fusion Splice Tray Kit, stackable, large
format will be able to organize up to 48 fiber splices.

General Specifications
Product Type Fusion splice tray kit
Application For 360G2 1U and 2U shelves
Package, quantity 1
Splice Trays Included
Splice Trays, quantity 1
Splices, quantity 48

5.7. Compact Closure for FO Cable T-Joint


In order to connect each CCTV Peripheral Cabinet, installed on perimeter fence, with the Outdoor
24 Cores SM FO Backbone Cable, a FOCUS-CODC Compact Closure will be provided. This
Closure, suitable for direct buried installation, is able to joint several fiber optic cables in order to
realize a customized optical network for connection of field equipment.
Compact Closure will be available in a single base configuration with Nr. 1 oval port for looped
cable and Nr. 6 round ports for drop cables. The cable entries can be sealed using a mechanical
cold applied kit. The internal frame can accommodate Single Circuit (SC) splice trays suitable for
up to 24 fibers splicing. The base and dome of the Closure are sealed with O-ring and a clamp
mechanism. The space behind the frame can be used either as storage for uncut loose buffer tubes
or as a patching point if necessary. Heat shrink splice protection will be provided.

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 18 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Compact Closure will have the following technical specifications:

Dimensions
Depth 150 mm
Height 380 mm
Width 290 mm
Weight TBD kg
General Specifications
Brand OPTOTEC
Product Type FOCUS-CODC-A-C-H-00xx
Splice Trays, type Single Circuit
Splice Trays, quantity 12
Splice quantity 24

6. TECHNICAL SPECIFICATION OF COPPER CABLE


This Section defines the technical specifications related to the Copper Cables of various Telecom
systems.
The following Copper Cables will be provided:
 Outdoor Telephone Copper Cables
 Outdoor ACS Copper Cables
 Indoor ACS Copper Cables
 Outdoor PAGA Copper Cables
 Indoor PAGA Copper Cables
 Indoor LAN Cable
 Outdoor CCTV Copper Cables.

All outdoor copper cables will be Armoured and shielded, with HDPE outer sheath suitable for
direct buried installation.
All indoor copper cables will be shielded and un-Armoured, suitable for installation inside
conduits or in cable tray with cover.
All indoor copper cables will have LSZH outer sheath and will be Fire Retardant / Flame
Retardant according to IEC 60332.

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 19 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

All indoor and outdoor copper cables for Public Address and General Alarm (PAGA) System will
be Fire Resistant according to IEC 60331.

6.1. Telephone Copper Cable Technical Specifications


1.1.8 Armoured Shielded Telephone Cable 2, 4 and 50 pairs x 0.6 mm

This cable shall have the following characteristics:

Description Specification/Value
Electrical Characteristics
Operating Voltage 300V
Test
Voltage 1000 VDC at 20 °C x 1 min
Norms of
Reference IEC 60708
Max. Resistance at 20
°C 67 Ω/km
Insulation Resistance at 20
°C ≥ 5 GΩ/km
Max. Attenuation 800 Hz: < 1.5 dB/Km
1 MHz: < 19 dB/Km
Physical/Mechanical characteristics

Conductor Solid Bare Copper


Material
Conductor Nominal 0.6 mm
Diameter
Pair Two insulated conductors twisted together to form a
Assembly pair
Number of 2,4,50
Pairs
Insulation Cross Linked Polyethylene
Material
Insulation Nominal 0.3 mm

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 20 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Thickness
Moisture and Chemical Barrier Aluminium Tape/PE/ Tape (H5)
Material
Drain Stranded Tinned Copper 7 x 0.30 mm
Wire
Coverag Longitudinal applied and bonded to inner sheath
e
Minimum 0.15 mm
Thickness
Pair Colour Identification
Pair 1: White-Blue 2 pairs cable
Pair 2: White-Orange

Pair 1: White- Blue


Pair 2: White- Orange 4 pairs cable
Pair 3: White- Green
Pair 4: White- Brown

10 pairs are assembled


together and identified
White-blue
by a coloured
White-orange yarn(Blue-Orange-
Green-Brown- Grey) to
White-green form a 50 pairs cable
White brown
White-grey
Red-blue
Red-orange
Red-green
Red-brown
Red-grey

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 21 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Inner Sheath Black Polyethylene


Material
Inner Sheath Nominal Thickness 1.0 mm for 2 and 4 pairs cables
1.2 mm for 50 pairs cable
Inner Sheath Nominal Diameter 7.8 mm for 2 pairs cable
8 mm for 4 pairs cable
21.5 mm for 50 pairs cable
Intermediate Sheath Material Polyamide

Intermediate Sheath Nominal 0.5 mm


Thickness
Intermediate Sheath Nominal Diameter 8.8 mm for 2 pairs cable
9 mm for 4 pairs cable
22.5 mm for 50 pairs cable
Armour Material Galvanized Steel Wire

Armour Nominal Wire Diameter 0.9 mm

Outer Sheath Material Black Polyethylene

Outer Sheath Nominal Thickness 1.6 mm for 2, 4 and 50 pairs cables

Outer Sheath Nominal Diameter 13.8 mm for 2 pairs cable


14 mm for 4 pairs cable
28 mm for 100 pairs cable
Nominal Weight 280 kg/km for 2 pairs cable
290 kg/km for 4 pairs cable

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 22 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

900 kg/km for 50 pairs cable


Minimum Bending Radius 15 x Ø mm static
20 x Ø mm dynamic
Operating Temperature - 40°C to + 70°C

6.2. ACS Copper Cable Technical Specifications


1.1.1 Armoured Shielded Control Cable 2 x 1.3 mm² (16 AWG)
This cable shall have the following characteristics

Description
Specification/Value
Electrical Characteristics
Max. Capacitance 120 nF/Km

Max. DC Resistance at 20°C 14 Ohm/Km


Nominal Voltage 0.6/1 KV
Test Voltage 3.5 kV AC x 5 min

Insulation Resistance at 20°C ≥ 5 GΩ/km

Physical/Mechanical Characteristics
Conductor Material Stranded Bare Copper

Conductor Nominal Formation 19 wires 0.30 mm nominal diameter each

Nominal Cross Section 2 x 1.3 mm2 (2x16AWG)


Conductor Nominal Diameter 1.29 mm
Pair Assembly Two insulated conductors twisted

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 23 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

together to form a pair

Insulation Material Cross Linked Polyethylene


Insulation Colour Black - Blue
Insulation Nominal Thickness 0.5 mm
Moisture and Chemical Barrier Material Aluminium Tape/PE/ Tape (H5)
Drain Wire Stranded Tinned Copper 7 x 0.30 mm

Coverage Longitudinal applied and bonded to inner


sheath

Minimum Thickness 0.15 mm


Inner Sheath Material Black Polyethylene

Inner Sheath Nominal Thickness 1.0 mm


Inner Sheath Nominal Diameter 8.5 mm
Intermediate Sheath Material Polyamide
Intermediate Sheath Nominal Thickness 0.5 mm
Intermediate Sheath Nominal Diameter 9.5 mm
Armour Material Galvanized Steel Wire
Armour Nominal Wire Diameter 0.9 mm
Outer Sheath Material and Colour Black Polyethylene
Outer Sheath Nominal Thickness 1.6 mm
Outer Sheath Nominal Diameter 14 mm
Nominal Weight 230 Kg/Km
Max. Pull Tension 165 N
Min. Bending Radius 15 x Ø mm
Operating Temperature - 40°C to + 70°C

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 24 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Max Delivery Drum Length 2000 m

1.1.2 Un-Armoured Shielded Control Cable 2x1.3 mm² (16 AWG)


This cable shall have the following characteristics

Description Specification/Value
Electrical Characteristics
Max. Capacitance 120 nF/Km
Max. DC Resistance at 20°C 14 Ohm/Km

Nominal Voltage 0.6/1 KV


Test Voltage 3.5 kV AC x 5 min
Insulation Resistance at 20°C ≥ 5 GΩ/km
Physical/Mechanical Characteristics
Conductor Material Stranded Bare Copper
Conductor Nominal Formation 19 wires 0.30 mm nominal diameter each

Nominal Cross Section 2x1.3 mm2 (2x16AWG)

Conductor Nominal Diameter 1.29 mm


Pair Assembly Two insulated conductors twisted
together to form a pair
Insulation Material Cross Linked Polyethylene
Insulation Colour Black - Blue
Insulation Nominal Thickness 0.5 mm
Moisture and Chemical Barrier Material Aluminium Tape/PE/ Tape (H5)
Drain Wire Stranded Tinned Copper 7 x 0.30 mm

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 25 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Coverage Longitudinal applied and bonded to inner


sheath
Minimum Thickness 0.15 mm
Outer Sheath Material and Colour Black LSZH
Outer Sheath Nominal Thickness 1.5 mm
Outer Sheath Nominal Diameter 8.5 mm

Nominal Weight 90 Kg/Km

Min. Bending Radius 12 x Ø mm


Operating Temperature - 40°C to + 70°C
Max Delivery Drum Length 2000 m
Fire Performance
Halogen acid gas emission ≤ 0,5% IEC 60754-1 ; IEC 60754-2
Degree of acidity of gases evolved during IEC 60754-1 ; IEC 60754-2
of the combustion (pH value ≥ 4,3 and
conductivity ≤ 10μS/mm
Smoke emission (transmittance) ≥ 70% IEC 61034-1 ;IEC 61034-2
Flame Retardant IEC 60332-1
Fire Retardant IEC 60332-3-24

1.1.3 Un-Armoured Shielded Cable 4x1 mm²


The cable shall have the following characteristics,
Characteristic Specification
Electrical Characteristics
Operating Voltage 0.6/1 KV
Test Voltage 3.5 kV AC x 5 min
Max. DC Resistance at 20°C 7.98 Ohm/Km
Insulation Resistance at 20°C ≥ 5 GΩ/Km
Max. Capacitance 120 nF/Km

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 26 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Physical/Mechanical Characteristics
Conductor Material Stranded Bare Copper
Conductor Nominal Formation 50 wires 0.25 mm nominal diameter each
Nominal Cross Section 2 x 2.5 mm2
Conductor Nominal Diameter 0.9 mm
Conductor Assembly Two insulated conductors twisted
together to form a pair
Insulation Material Cross Linked Polyethylene
Insulation Colour Black Numbered
Insulation Nominal Thickness 0.7 mm
Moisture and Chemical Barrier Material Aluminium Tape/PE/ Tape (H5)
Drain Wire Stranded Tinned Copper 7 x 0.30 mm
Coverage Longitudinal applied and bonded to inner
sheath
Minimum Thickness 0.15 mm
Outer Sheath Material and Colour Black LSZH
Outer Sheath Nominal Thickness 1.5 mm
Outer Sheath Diameter 12 mm
Nominal Unit Weight 175 Kg/Km
Max. Pull Tension 250 N
Min. Bending Radius 12 x Ø mm
Operating Temperature - 40°C to + 70°C
Max Delivery Drum Length 2000 m

Fire Performance
Halogen acid gas emission ≤ 0,5% IEC 60754-1 ; IEC 60754-2
Degree of acidity of gases evolved during IEC 60754-1 ; IEC 60754-2
of the combustion (pH value ≥ 4,3 and

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 27 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

conductivity ≤ 10μS/mm
Smoke emission (transmittance) ≥ 70% IEC 61034-1 ;IEC 61034-2
Flame Retardant IEC 60332-1
Fire Retardant IEC 60332-3-24

1.1.4 Un-Armoured Shielded Cable 4x1 mm²


The cable shall have the following characteristics,

Characteristic Specification
Electrical Characteristics
Operating Voltage 0.6/1 KV
Test Voltage 3.5 kV AC x 5 min
Max. DC Resistance at 20°C 7.98 Ohm/Km
Insulation Resistance at 20°C ≥ 5 GΩ/Km
Max. Capacitance 120 nF/Km

Physical/Mechanical Characteristics
Conductor Material Stranded Bare Copper
Conductor Nominal Formation 50 wires 0.25 mm nominal diameter each
Nominal Cross Section 2 x 2.5 mm2
Conductor Nominal Diameter 0.9 mm
Conductor Assembly Two insulated conductors twisted
together to form a pair
Insulation Material Cross Linked Polyethylene
Insulation Colour Black Numbered
Insulation Nominal Thickness 0.7 mm
Moisture and Chemical Barrier Material Aluminum Tape/PE/ Tape (H5)
Drain Wire Stranded Tinned Copper 7 x 0.30 mm
Coverage Longitudinal applied and bonded to inner

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 28 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

sheath
Minimum Thickness 0.15 mm
Outer Sheath Material and Colour Black LSZH
Outer Sheath Nominal Thickness 1.5 mm
Outer Sheath Diameter 12 mm
Nominal Unit Weight 175 Kg/Km
Max. Pull Tension 250 N
Min. Bending Radius 12 x Ø mm
Operating Temperature - 40°C to + 70°C
Max Delivery Drum Length 2000 m
Fire Performance
Halogen acid gas emission ≤ 0,5% IEC 60754-1 ; IEC 60754-2
Degree of acidity of gases evolved during IEC 60754-1 ; IEC 60754-2
of the combustion (pH value ≥ 4,3 and
conductivity ≤ 10μS/mm
Smoke emission (transmittance) ≥ 70% IEC 61034-1 ;IEC 61034-2
Flame Retardant IEC 60332-1
Fire Retardant IEC 60332-3-24

1.1.5 Un-Armoured Shielded Cable 2x2.5 mm²


This cable shall have the following characteristics:

Characteristic Specification
Electrical Characteristics
Nominal Voltage 300 VRMS
Test Voltage 1.5 kV AC x 1 min
Max. DC Resistance at 20°C 56 Ohm/Km
Insulation Resistance at 20°C ≥ 350 MΩ/Km
Max. Capacitance 250 nF/Km

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 29 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Nominal Inductance 1.5 mH/Km


Physical/Mechanical Characteristics
Conductor Material Stranded Tinned Copper
Conductor Nominal Formation 7 wires 0.25 mm nominal diameter each
Nominal Cross Section 8x0.35 mm2 (22 AWG)
Conductor Nominal Diameter 0.9 mm
Assembly Eight conductors assembly together
with Mylar Tape
Insulation Material Cross Linked Polyethylene
Insulation Colour Black Numbered
Insulation Nominal Thickness 0.6 mm
Moisture and Chemical Barrier Material Aluminium Tape/PE/ Tape (H5)
Drain Wire Stranded Tinned Copper 7 x 0.30 mm
Coverage Longitudinal applied and bonded to
inner sheath
Minimum Thickness 0.15 mm
Outer Sheath Material and Colour Black LSZH
Outer Sheath Nominal Thickness 1.6 mm
Outer Sheath Diameter 11.5 mm
Nominal Unit Weight 160 Kg/Km
Min. Bending Radius 8 x Ø mm
Operating Temperature - 5°C to + 70°C
Max Delivery Drum Length 2000 m
Fire Performance
Halogen acid gas emission ≤ 0,5% IEC 60754-1 ; IEC 60754-2
Degree of acidity of gases evolved IEC 60754-1 ; IEC 60754-2
during of the combustion (pH value ≥
4,3 and conductivity ≤ 10μS/mm

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 30 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Smoke emission (transmittance) ≥ 70% IEC 61034-1 ;IEC 61034-2


Flame Retardant IEC 60332-1
Fire Retardant IEC 60332-3-24

6.3. PAGA Copper Cable Technical Specifications


1.1.6 Fire Resistant Shielded Armoured Cable 2x2x2.5 mm2 for Outdoor Loudspeakers
This cable shall have the following characteristics:
Characteristic Specification
Electrical characteristics
Nominal Voltage 0.6/1 KV
Test voltage. 3.5 KV AC x 5 min
Insulation Resistance at 20°C ≥ 5 GΩ/Km
Max. Resistance at 20°C 7.98 Ohm/Km
Max. Capacitance 120 nF/Km
Physical characteristics
Conductor Material Stranded Bare Copper (Cl.5 IEC
60228)
Conductor Nominal Formation 50 wires 0.25 mm nom. diam. each
Nominal Cross Section 2 x 2 x 2.5 mm2
Fire Protection Material MICA Tape
Insulation Material Cross Linked Polyethylene
Insulation Colour Black - Blue Numbered
Insulation Nominal Thickness 0.7 mm
Moisture and Chemical Barrier Aluminium Tape/PE/ Tape (H5)
Material
Drain Wire Stranded Tinned Copper 7 x 0.30 mm
Coverage Longitudinal applied and bonded to
inner sheath

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 31 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Minimum Thickness 0.15 mm


Inner Sheath Material Black Polyethylene

Inner Sheath Nominal Thickness 1.0 mm


Inner Sheath Nominal Diameter 16 mm
Intermediate Sheath Material Polyamide
Intermediate Sheath Nominal 0.5 mm
Thickness
Intermediate Sheath Nominal 17 mm
Diameter
Armour Type Galvanized Steel Wire
Armour Nominal Wire Diameter 0.9 mm
Outer Sheath Material and Colour Black Polyethylene
Outer Sheath Nominal Thickness 1.6 mm
Outer Sheet Diameter 22,5 mm
Nominal Weight 700 Kg/Km
Minimum Bending Radius 15 x Ø mm
Operating Temperature - 40°C to + 70°C
Max Delivery Drum Length 2000 m
Fire Performance
Halogen acid gas emission ≤ 0,5% IEC 60754-1 ; IEC 60754-2

1.1.7 Fire Resistant Shielded Armoured Cable 3x2.5 mm2 for Outdoor Flashing Beacons
This cable shall have the following characteristics:

Characteristic Specification

Electrical characteristics

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 32 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Nominal Voltage 0.6/1 KV


Test voltage. 3.5 KV AC x 5 min
Insulation Resistance at 20°C ≥ 5 GΩ/Km
Max. Resistance at 20°C 7.98 Ohm/Km
Physical characteristics
Conductor Material Stranded Bare Copper (Cl.5 IEC 60228)
Conductor Nominal Formation 50 wires 0.25 mm nom. diam. each
Nominal Cross Section 3x2.5 mm2
Fire Protection Material MICA Tape
Insulation Material Cross Linked Polyethylene
Insulation Colour Black - Blue - Yellow/Green
Insulation Nominal Thickness 0.7 mm
Moisture and Chemical Barrier Aluminium Tape/PE/ Tape (H5)
Material

Drain Wire Stranded Tinned Copper 7 x 0.30 mm


Coverage Longitudinal applied and bonded to
inner sheath
Minimum Thickness 0.15 mm
Inner Sheath Material Black Polyethylene
Inner Sheath Nominal Thickness 1.0 mm
Inner Sheath Nominal Diameter 11.5 mm
Intermediate Sheath Material Polyamide
Intermediate Sheath Nominal 0.5 mm
Thickness
Intermediate Sheath Nominal 12.5 mm
Diameter
Armour Type Galvanized Steel Wire

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 33 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Armour Nominal Wire Diameter 0.9 mm


Outer Sheath Material and Colour Black Polyethylene
Outer Sheath Nominal Thickness 1.6 mm
Outer Sheet Diameter 18 mm
Nominal Weight 450 Kg/Km
Minimum Bending Radius 15 x Ø mm
Operating Temperature - 40°C to + 70°C
Max Delivery Drum Length 2000 m
Fire Performance
Halogen acid gas emission ≤ 0,5% IEC 60754-1 ; IEC 60754-2
Degree of acidity of gases evolved IEC 60754-1 ; IEC 60754-2
during of the combustion (pH value ≥
4,3 and conductivity ≤ 10μS/mm
Smoke emission (transmittance) ≥ IEC 61034-1 ;IEC 61034-2
70%
Fire Resistant IEC 60331-11 (90 min -750°C @110
V)

1.1.8 Fire Resistant Shielded Un-Armoured Cable 2x2x2.5 mm2 for Indoor Loudspeakers
This cable shall have the following characteristics:
Characteristic Specification
Electrical characteristics
Nominal Voltage 0.6/1 KV
Test voltage. 3.5 KV AC x 5 min
Insulation Resistance at 20°C ≥ 5 GΩ/Km
Max. Resistance at 20°C 7.98 Ohm/Km
Max. Capacitance 120 nF/Km

Physical characteristics

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 34 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Conductor Material Stranded Bare Copper (Cl.5 IEC 60228)


Conductor Nominal Formation 50 wires 0.25 mm nom. diam. each
Nominal Cross Section 2 x 2 x 2.5 mm2
Fire Protection Material MICA Tape
Insulation Material Cross Linked Polyethylene
Insulation Colour Black - Blue Numbered
Insulation Nominal Thickness 0.7 mm
Moisture and Chemical Barrier Aluminium Tape/PE/ Tape (H5)
Material
Drain Wire Stranded Tinned Copper 7 x 0.30 mm
Coverage Longitudinal applied and bonded to inner
sheath
Minimum Thickness 0.15 mm
Outer Sheath Material and Colour Black LSZH
Outer Sheath Nominal Thickness 1.6 mm
Outer Sheet Diameter 17 mm
Nominal Weight 260 Kg/Km
Minimum Bending Radius 12 x Ø mm
Operating Temperature - 40°C to + 70°C
Max Delivery Drum Length 2000 m
Fire Performance
Halogen acid gas emission ≤ 0,5% IEC 60754-1 ; IEC 60754-2
Degree of acidity of gases evolved IEC 60754-1 ; IEC 60754-2
during of the combustion (pH value
≥ 4,3 and conductivity ≤ 10μS/mm
Smoke emission (transmittance) ≥ IEC 61034-1 ;IEC 61034-2
70%
Flame Retardant IEC 60332-1
Fire Retardant IEC 60332-3-24
Fire Resistant IEC 60331-11 (90 min -750°C @110 V)

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 35 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

6.4. LAN Cable Technical Specifications


1.1.9 Category 6 U/UTP Cable
The CAT6 cable transmits reliable voice, data and video, with excellent quality of service. This
cable will be used also by others Telecom System such as PAGA, Telephone, CCTV, Supervisory
etc.
This cable shall have the following characteristics:

Construction Materials
Jacket Material Low Smoke Zero Halogen (LSZH)
Conductor Material Bare copper
Separator Material Polyolefin
Dimensions
Cable Length 305 m
Jacket Thickness 0.508 mm
Electrical Specifications
ANSI/TIA Category 6
Mutual Capacitance 5.6 nF/100 m @ 1 kHz

Nominal Velocity of Propagation 69 %


(NVP)
Operating Frequency, maximum 300 MHz
Operating Voltage, maximum 80 V

Environmental Specifications
Environmental Space Low Smoke Zero Halogen (LSZH)
Flame Test Method IEC 60332-3-22
Installation Temperature 0 °C to +60 °C

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 36 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

Operating Temperature -20 °C to +60 °C


Smoke Test Method IEC 61034-2
General Specifications
Cable Type U/UTP (unshielded)
Pairs, quantity 4
Cable Component Type Horizontal
Jacket Color White
Conductor Gauge, singles 23 AWG
Conductor Type, singles Solid
Conductors, quantity 8

6.5. Cable Drum Specifications


 All cables shall be delivered coiled on wooden drums, capable of withstanding the sea
transport and storage stresses.
 Strong wooden battens shall be fixed (nailed) onto circumference of the flanges of the
drums, preferably in two layers and further blocked with two turns of adequate metallic
strip.
 The drum length will be equal to a maximum drum length make available by Supplier.
Tolerance on the total length of cable per each drum will be ±1% of the specified nominal
length.
 The diameter of the drums shall be large enough to prevent damage to the cable from
reeling and unreeling.
 Both ends of each cable length shall be sealed to prevent entry of moisture. The seal shall
be applied in such a manner as to avoid damage to the conductors. The outer end of the
cable shall be securely fastened to the drum in order to prevent the cable to become loose
during transportation.
 The finished cable coil will be further protected with a plastic sheet, black colour, to be
applied prior to the close-out of the drum.

7. TRAININGS
The CONTRACTOR shall organize full training for the systems package. Training shall consist
of software and hardware. Training shall include but not limited to users mode, installer mode and
any other mode that shall equip the operators for effective and seamless operation of the system
by the COMPANY operations team.

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 37 of 38

This document is controlled electronically and is uncontrolled when printed.


Gbaran Phase 3B – Uzu with CPF
Upgrade Project UZU-SEDO-ZRMS2-TA773
Specification for Structured Cabling
System (Fiber and Copper)

8. SPARE HOLDINGS
The CONTRACTOR shall provide two years spare part according to OEM recommendation for
all Telecoms systems deployed as part of the projects. The spare shall be kept either in the
COMPANY’s stores/ warehouse or any approved location.

9. PACKING AND SHIPPING


Packaging and shipping shall comply with ETS 300019, class 2.3.

10. EARTHING and LIGHTNING PROTECTION


The earthing of the system shall conforms with appendix 3 “Lightning Protection and Earthing”
on page 51 of DEP 32.71.00.10-Gen.

11. WARRANTY
The CONTRACTOR shall replace defective/faulty items within two years of installation.

Doc. no.: UZU-SEDO-ZRMS2-TA7739-00002 Page 38 of 38