Professional Documents
Culture Documents
Camara de Combustion
Camara de Combustion
Camara de Combustion
Customer Information
Name
Address
City, State ZIP
Page 1 of 10
C-Linx Configuration Software Fike Corporation
Miscellaneous Settings
AC Trouble Delay 2 hours
Abort Type 2
Panel Walktest Enabled
Fan Restart Automatic Restart
Auxiliary Loop Module No Module
Auxiliary Power Module No Module
Aux Battery Supervision Enabled
Transformer Type 120VAC
Main Battery Supervision Enabled
SLC Wiring Style Style 4 - Class B
Ground Fault Supervision L1 Enb L2 Enb
Unsilence Time 24 hours
Silence Reminder Disabled
Silence Inhibit Disabled
Silence Mode UL Silence Mode
Panel Sync Protocol Gentex
Panel Switch Operation Drill/Silence/Acknowledge Switches Enabled
Positive Alarm Sequence Disabled
New Device Record Missing Trb Enabled
Auto Message Sent at 12:00AM Disabled
Eclipse Device Error Device Error is Trouble
AHU Fire Dept Key Not Required to restart AHU
Latch Super/Trb event on LCD First Supervisory or Trouble Event Latched on LCD
Common Settings
Custom Message Line 1 'RELE DISPONIBLE '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 001 '
Zone Assignments 001
Drill Operation Drill Operation Disabled
Silence Output is Non Silenceable
Positive Alarm Sequence PAS is Disabled
Relay Monitoring Relay Monitoring is Disabled
Dry Contact Dry Contact Not Used
Common Settings
Custom Message Line 1 'RELE DISPONIBLE '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 002 '
Zone Assignments 001
Drill Operation Drill Operation Disabled
Silence Output is Non Silenceable
Positive Alarm Sequence PAS is Disabled
Relay Monitoring Relay Monitoring is Disabled
Dry Contact Dry Contact Not Used
Common Settings
Custom Message Line 1 'DESCARGA AGENTE '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 003 '
Zone Assignments 002 003
Common Settings
Custom Message Line 1 'DESCARGA AGENTE '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 004 '
Zone Assignments 002 003
Common Settings
Custom Message Line 1 'CHAPA BLOQUEO '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 005 '
Input Function Zone Disable
Input Latching Type Non-Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 002 003
Page 3 of 10
C-Linx Configuration Software Fike Corporation
Common Settings
Custom Message Line 1 'CHAPA BLOQUEO '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 006 '
Input Function Zone Disable
Input Latching Type Non-Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 002 003
Common Settings
Custom Message Line 1 'PULSADOR DESCARGA '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 007 '
Input Function Manual Release
Zone Assignments 001 003
Common Settings
Custom Message Line 1 'PULSADOR DESCARGA '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 008 '
Input Function Manual Release
Zone Assignments 001 003
Common Settings
Custom Message Line 1 'ALARMA CAMARA 1 '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 009 '
Input Function Manual Release
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001 002
Common Settings
Custom Message Line 1 'FALLA CAMARA 1 '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 010 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Common Settings
Custom Message Line 1 'ALARMA CAMARA 2 '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 011 '
Input Function Manual Release
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001 002
Common Settings
Custom Message Line 1 'FALLA CAMARA 2 '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 012 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Page 5 of 10
C-Linx Configuration Software Fike Corporation
Common Settings
Custom Message Line 1 'SW PRESION '
Custom Message Line 2 'CILINDRO A '
Custom Message Line 3 'ADDRESS 013 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Common Settings
Custom Message Line 1 'SW PRESION '
Custom Message Line 2 'CILINDRO B '
Custom Message Line 3 'ADDRESS 014 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Common Settings
Custom Message Line 1 'SW PRESION ALTA '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 015 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Page 6 of 10
C-Linx Configuration Software Fike Corporation
Common Settings
Custom Message Line 1 'SW PRESION BAJA '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 016 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Common Settings
Custom Message Line 1 'PRESION DESCARGA '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 017 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Common Settings
Custom Message Line 1 'VALVULA CORTA 3 '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 018 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Page 7 of 10
C-Linx Configuration Software Fike Corporation
Common Settings
Custom Message Line 1 'VALVULA CORTA 2 '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 019 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Common Settings
Custom Message Line 1 'VALVULA CORTA 1 '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 020 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Common Settings
Custom Message Line 1 'SIRENAS '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 021 '
Zone Assignments 001 002 003
Drill Output Pattern On Continuous
Silence Output is Silenceable
Positive Alarm Sequence PAS is Disabled
Power Supply Monitor Monitor is Enabled
Page 8 of 10
C-Linx Configuration Software Fike Corporation
Common Settings
Custom Message Line 1 'SIRENAS '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 022 '
Zone Assignments 001 002 003
Drill Output Pattern On Continuous
Silence Output is Silenceable
Positive Alarm Sequence PAS is Disabled
Power Supply Monitor Monitor is Enabled
Common Settings
Custom Message Line 1 'ELECTRO VALVULA 2 '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 023 '
Input Function Manual Alarm
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001 002
Common Settings
Custom Message Line 1 'ELECTRO VALVULA 1 '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 024 '
Input Function Manual Alarm
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001 002
Page 9 of 10
C-Linx Configuration Software Fike Corporation
Common Settings
Custom Message Line 1 'SW PRESION CILINDRO '
Custom Message Line 2 'LOOP 1 '
Custom Message Line 3 'ADDRESS 025 '
Input Function Supervisory
Verification Time 0 seconds
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Page 10 of 10