Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

MEP CONSULTANT

1430 Broadway
New York, NY 10018
V: 212.868.4660
F: 212.868.4680

WEST 37TH ST.


COPY PRIVATE PRIVATE STORAGE
AREA OFFICE OFFICE ROOM
20-33 20-34 20-35 20-36

A#53

OPEN (N)PP-20
AREA
20-37
OPEN 30AS 30AS 30AS
AREA FCU-18 FCU-19 FCU-20
20-32 A#22,24 A#26,28 LD A#26,28
LD LD
30AS
A#29 A#29 A#29 FCU-21
A#25,27 LD
A#29

PRIVATE
OFFICE
20-38

MEETING
ROOM
20-30 30AS FEC
FCU-17 BC-4
J

PRIVATE
A#22,24
LD
A#29
LD
A#29
A#10,12
30AS
30AS
A#26,28
FCU-25
PHONE
A#51
- OPEN
OFFICE LD ROOM
20-29 A#29 20-39
30AS
PHONE 30AS FCU-22 PRIVATE
ROOM FCU-16 30AS OFFICE
A#26,28 LD FCU-23
20-28 A#22,24 LD
20-40
A#29 A#25,27 LD MENS
A#29 RESTROOM
30AS
STORAGE A#29 60AS ERV-1
ROOM EWH-2 A#34,36,38 20-41 ACCU-IT
20-27 RP EWH
A#42 ELECTRICAL
LD 30AS CLOSET A#44,46,48 A#45,47,49
IDF A#29
ROOM 30AS BC-3 TX-1 20-42
FCU-15 A#10,12 A#29 30AS
20-26 FCU-24 COMMUNICATIONS
A#21,23 LD A#29 CP
LD 30AS A#32 A#25,27 CLOSET
A#29 LD A#50,52 LD 20-43 PRIVATE
A#29 OFFICE
A#29

BRO
CORRIDOR AC-IT 30AS MD
A#30 20-44
20-25
COAT
CLOSET
20-24

ADW
P. E. P. E. P. E.
PHONE
ROOM

FEC
PRIVATE
20-23 OFFICE
CONFERENCE 20-45

AY
ROOM ELEVATOR
20-22 LOBBY
ADA 20-00
RESTROOM
20-21
ADA MD A#30
MD A#30 MD A#30
RESTROOM
MD A#30 FSD A#30 FSD A#30
20-20 PANTRY
AREA

FHC
PRIVATE 20-01
OFFICE EWH-1
P. E. P. E. P. E. PRIVATE
20-19 OFFICE
A#42 RP EWH 20-46
LACTATION A#33,35,37
ROOM A#29 LD
20-18
STORAGE 30AS WOMENS
CLOSET SHAFT FCU-1 RESTROOM
20-17 A#13,15 TX-2 20-02
LD 30AS
STAIR
20-16
A#29
A#31 A#21,23
FCU-14
LD
EWH-4
EWH A#40 FEC
ELECTRICAL 20TH FLOOR MER PART PLAN
A#29
SCALE:1/2"=1'-0"
PRIVATE A#10,12
OFFICE 30AS 30AS 0' 3' 6'
20-15 FCU-4 STORAGE
F. E. LD ROOM
PRIVATE
A#14,16 LD 30AS
A#29 A#29 LD EWH-3 FCU-13 20-03
OFFICE
A#29
BC-1
A#21,23 PRIVATE
1/2"= 1'-0"
20-14 A#42 RP EWH A#39,41,43 LD OFFICE
30AS A#29
FCU-5 30AS FCU-2 20-47
MEETING
ROOM FCU-3 MD A#13,15
F. E. 30AS A#30 LD
30AS
20-13 A#13,15 30AS BC-2 PRIVATE
LD FCU-8
A#14,16 A#29 A#10,12 OFFICE
LD A#29 A#17,19 LD 30AS 20-04
A#29 LD
A#29 FCU-12
COPY
AREA A#29 A#18,20
LD
20-12
F. E. A#29

FEC

F. E. 30AS 30AS 30AS


FCU-6 A#14,16 FCU-7 FCU-9 FCU-10
30AS A#17,19
LD LD
A#17,19 LD
A#18,20 LD
A#29 A#29 A#29 A#29 30AS
FCU-11
A#18,20
SEE MER PART PLAN LD OPEN
A#29 AREA
(N)PP-20 20-05

MER
ROOM
20-11

OPEN PRIVATE PRIVATE PRIVATE PANTRY


AREA OFFICE OFFICE OFFICE AREA
20-10 20-09 20-08 20-07 20-06
N

WEST 36TH ST.

ELECTRICAL 20TH FLOOR MECHANICAL POWER PLAN PANEL LEGEND

PREFIX PANEL VOLTAGE LOCATED


3 ISSUED FOR ADDENDUM #1 5/2/2024 JB
SCALE:1/8"=1'-0"
3 ISSUED FOR BID 4/26/2024 JB
8' 4' 0' 8' 'A' PP-20 120/208V MECHANICAL ROOM
2 ISSUED FOR DOB FILING 4/5/2024 MYS

1/8"= 1'-0" 1 ISSUED FOR REVIEW 3/22/2024 MYS

NO. REVISION DATE BY

TPG ARCHITECTURE, LLP


31 PENN PLAZA
132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001
212.768.0800 | TPGARCHITECTURE.COM

IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN


AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT
PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE
LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND
COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF,
OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION,
OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED
BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.

PROJECT
S:\CAD\1359 BWAY\20FL_PROGYNY_DEMO BUILDOUT_23043.08\03-DWGS\E-201.DWG / Plot Date: May, 2, 2024 - 4:54 :PM

PROGYNY
2ND AND 20TH FLOOR
1359 BROADWAY
NEW YORK, NY 10018
DRAWING

ELECTRICAL
20TH FLOOR
MECHANICAL POWER
PLAN
SEAL DATE
1.29.24
PROJECT NO.
11523048-00
Last Saved By: AMETA / Save Date: 5/2/2024 4:51:41 PM

SCALE
AS SHOWN
CAD FILE NO. DOB PAGE
X of #
DWG NO.

NYC DOB NO.


E-201.00
MEP CONSULTANT

1430 Broadway
New York, NY 10018
V: 212.868.4660
F: 212.868.4680

GENERAL POWER NOTES


1. FIRE STOP ALL NEW PENETRATIONS CREATED WITH NEW INSTALLATION. FIRE
RATING SHALL MATCH EXISTING WALL OR CEILING RATING.
2. WIRING IN AREAS WHERE THERE IS NO CEILING, OPEN OR EXPOSED WALLS, AND
MECHANICAL ROOMS SHALL BE INSTALLED IN CONDUIT. MINIMUM SIZE OF
CONDUIT SHALL BE 3/4". CONDUIT TO BE RAN HIGH AND TIGHT TO THE BUILDING
STRUCTURE AND CLOSE TO SIDE OF BEAMS AND COLUMNS. MAIN CONDUIT
RUNS SHALL BE RAN A MINIMUM OF ONE COLUMN BAY FROM THE WINDOW LINE
AND AS CLOSE TO THE BUILDING CORE AS POSSIBLE. CONTRACTOR TO ISSUE
SHOP DRAWING ON CONDUIT ROUTES FOR REVIEW PRIOR TO INSTALLATION.
3. ALL EQUIPMENT (PULL BOXES, DISCONNECT SWITCHES, ETC) SHALL BE
N.I.C INSTALLED IN CONJUNCTION WITH THE MANUFACTURERS RECOMMENDATIONS,
THE NATIONAL ELECTRIC CODE AND THE NYC ELECTRIC CODE. IN CASES OF
CONFLICT, THE MORE STRINGENT REQUIREMENT SHALL BE MAINTAINED.
4. CIRCUIT ALL DEVICES TO PANEL BOARDS INDICATED BY MATCH LINES.
5. TYPICAL CIRCUITING SHOWS A MAXIMUM OF FOUR (4) COMPUTER OUTLETS PER
CIRCUIT AND A MAXIMUM OF SIX (6) CONVENIENCE OUTLETS PER 20A CIRCUIT.
6. EACH RECEPTACLE BRANCH CIRCUIT SHALL UTILIZE A SEPARATE NEUTRAL
CONDUCTOR.
7. RECEPTACLES FOR ALL COMPUTER CONTROLLED EQUIPMENT, INCLUDING
PERSONAL COMPUTERS, WILL BE CIRCUITED SEPARATELY FROM ALL OTHER
RECEPTACLES AND WILL BE CONNECTED WITH A CONTINUOUS GROUND
CONDUCTOR TO THE GROUND BUS IN THE SERVING BRANCH CIRCUIT PANEL
BOARD. ALL CIRCUITS SERVING COMPUTER EQUIPMENT SHALL CONTAIN AN
OVERSIZED NEUTRAL.
8. ALL DEDICATED OR COMPUTER RECEPTACLES IN THE RAISED FLOOR BOXES
ACCU-1 ACCU-2 ACCU-3 A#8 SHALL BE A DIFFERENT COLOR THAN CONVENIENCE RECEPTACLES.
GFCI COORDINATE COLOR WITH COLORS AS FOLLOWS:
GRAY - COMPUTER
WHITE - CONVENIENCE
9. DUPLEX RECEPTACLES COLORS SHALL BE AS FOLLOWS:
WP 200AS WP 200AS WP 200AS GRAY - COMPUTER
WHITE - CONVENIENCE
A#1,3,5 A#2,4,6 A#7,9,11 10. ALL 15A OR 20A 120V RECEPTACLES THAT ARE ACCESSIBLE SHALL BE GFCI
(GROUND FAULT CIRCUIT INTERRUPTER). RECEPTACLES THAT ARE NOT
ACCESSIBLE SHALL BE GIVEN A GFCI CIRCUIT BREAKER. TRIP RATING OF GFCI
SHALL NOT BE LESS THAN 30mA.
11. FOR EXISTING DEVICES, ASSOCIATED FEEDERS AND CONDUIT TO REMAIN,
CONTRACTOR SHALL INSTALL REQUIRED EQUIPMENT TO MAINTAIN CONTINUITY
AND FUNCTION OF THE EXISTING SYSTEM.
12. THE CONTRACTOR MUST COORDINATE WITH ARCHITECTURAL LAYOUTS AND
COORDINATE SPECIFICALLY WITH THE ARCHITECT AND ENGINEERS FOR ALL
TRADE LAYOUTS WITHIN THE SHOP DRAWING FOR REVIEW AND APPROVAL.
13. EQUIPMENT IS SHOWN FOR DIAGRAMMATIC PURPOSES ONLY. PHYSICAL
DIMENSIONS OF EQUIPMENT AND EXACT LOCATIONS SHALL BE FIELD VERIFIED.
14. CONDUITS FOR FLOOR BOXES WILL BE DONE THROUGH TRENCHING ONLY.
15. CONTRACTOR SHALL PERFORM GROUND PENETRATING RADAR ALLFOR
LOCATIONS WHERE GROUND PENETRATION IS REQUIRED PRIOR TO
COMMENCEMENT OF ALL WORK.

POWER PLAN KEY NOTES:


N.I.C CONTRACTOR SHALL FOLLOW THE REFRIGERANT PIPING FOR THE NEW
ELECTRICAL CONDUITS THAT ARE FEEDING THE NEW AC UNITS FROM THE
20TH FLOOR MECHANICAL ROOM. REFER TO MECHANICAL DRAWINGS FOR
ROUTING. REFER TO E-200 FOR PANEL LOCATION.

PANEL LEGEND
PREFIX PANEL VOLTAGE LOCATED
'A' PP-20 120/208V 20TH FLOOR
MECHANICAL ROOM

N.I.C

N.I.C

N.I.C
3 ISSUED FOR ADDENDUM #1 5/2/2024 JB

3 ISSUED FOR BID 4/26/2024 JB

2 ISSUED FOR DOB FILING 4/5/2024 MYS

1 ISSUED FOR REVIEW 3/22/2024 MYS


ELECTRICAL 22ND FLOOR ROOF POWER PLAN NO. REVISION DATE BY
SCALE:1/4"=1'-0"
4' 2' 0' 4'

1/4"= 1'-0"
TPG ARCHITECTURE, LLP
31 PENN PLAZA
132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001
212.768.0800 | TPGARCHITECTURE.COM

IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN


AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT
PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE
LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND
COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF,
OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION,
OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED
BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.

PROJECT
S:\CAD\1359 BWAY\20FL_PROGYNY_DEMO BUILDOUT_23043.08\03-DWGS\E-202.DWG / Plot Date: May, 2, 2024 - 4:54 :PM

PROGYNY
2ND AND 20TH FLOOR
1359 BROADWAY
NEW YORK, NY 10018
DRAWING

ELECTRICAL
22ND FLOOR
ROOF POWER PLAN

SEAL DATE
1.29.24
PROJECT NO.
11523048-00
Last Saved By: AMETA / Save Date: 5/2/2024 4:50:36 PM

SCALE
AS SHOWN
CAD FILE NO. DOB PAGE
X of #
DWG NO.

NYC DOB NO.


E-202.00
MEP CONSULTANT

(E)BUS DUCT 1430 Broadway


New York, NY 10018
V: 212.868.4660
F: 212.868.4680
ELEC. CLOSET ELEC. CLOSET SUITE

NOTES
1. SEE DRAWING E-001 FOR GENERAL NOTES, REMOVAL NOTES, ABBREVIATIONS, AND SYMBOL LISTS.
2. SEE DRAWING E-400 FOR ELECTRICAL PANEL SCHEDULES.
3. SEE DRAWING E-600 FOR ELECTRICAL SPECIFICATIONS.
4. PRIOR TO THE COMMENCEMENT OF WORK, THE CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FOR ALL ELECTRICAL
CLOSETS, INDICATING NEW AND EXISTING EQUIPMENT AND NOTING ALL CODE REQUIRED CLEARANCES.

600AS
500AF REMOVED REMOVED REMOVED REMOVED REMOVED REMOVED REMOVED KEY NOTES
200AS 100AS LP-20H DP-20 RP-20 RP-20A RP-20B ELEC. PNL ELEC. PNL 1. SUB METERING TO BE INSTALLED BY CPL.
200AF 100AF 225A MLO 500A MCB 225A MLO 225A MLO 225A MLO CR CS 2. EXISTING FEEDER THAT IS FEEDING PANEL LP-19H TO BE SWUNG OVER TO PANEL P19A LOCATED IN THE BUS DUCT
400AS 120/208V 120/208V 120/208V 120/208V 120/208V 225A MLO 225A MLO CLOSET ON THE 19TH FLOOR. PROVIDE NEW 60A 3-POLE BREAKER IN PANEL P19A TO FEED PANEL LP-19H. PROVIDE 4#6 +
200AF 1#10G IN 1"C. COORDINATE WITH CPL FOR SUB METERING.
24 POLE 30 POLE 42 POLE 42 POLE 42 POLE 120/208V 120/208V
42 POLE 42 POLE

LEGEND
ROOM
DEMARCATION

CONDUIT AND WIRE


20TH FLOOR 20TH FLOOR
TO BE REMOVED

ELECTRICAL PARTIAL DEMOLITION RISER DIAGRAM NEW CONDUIT AND


WIRE
N.T.S.
EXISTING CONDUIT
AND WIRE TO REMAIN

(E)BUS DUCT

ELEC. CLOSET FREIGHT ELEV. MECH. ROOM IT ROOM


LOBBY

F3 F2
600AS NEW
F1
600AF LP-20
100A MCB FEED THROUGH
120/208V F1
400AS 24 POLE
NEW NEW NEW NEW
400AF 30, 4W
RP-20A RP-20B PP-20 IT PANEL
400A MCB 400A MLO 600A MCB 100A MLO
F2
F1
120/208V 120/208V 120/208V 120/208V
84 POLE 42 POLE 54 POLE 24POLE
30, 4W 30, 4W 30, 4W 30, 4W

20TH FLOOR 20TH FLOOR

FEEDER LEGEND:
NEW ELECTRICAL PARTIAL RISER DIAGRAM
N.T.S. F1

F2

F3

3 ISSUED FOR ADDENDUM #1 5/2/2024 JB

3 ISSUED FOR BID 4/26/2024 JB

2 ISSUED FOR DOB FILING 4/5/2024 MYS

1 ISSUED FOR REVIEW 3/22/2024 MYS

NO. REVISION DATE BY

TPG ARCHITECTURE, LLP


31 PENN PLAZA
132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001
212.768.0800 | TPGARCHITECTURE.COM

IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN


AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT
PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE
LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND
COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF,
OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION,
OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED
BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.

PROJECT
S:\CAD\1359 BWAY\20FL_PROGYNY_DEMO BUILDOUT_23043.08\03-DWGS\E-300.DWG / Plot Date: May, 2, 2024 - 4:54 :PM

PROGYNY
2ND AND 20TH FLOOR
1359 BROADWAY
NEW YORK, NY 10018
DRAWING

ELECTRICAL
RISER DIAGRAM

SEAL DATE
1.29.24
PROJECT NO.
11523048-00
Last Saved By: AMETA / Save Date: 5/2/2024 4:50:34 PM

SCALE
AS SHOWN
CAD FILE NO. DOB PAGE
X of #
DWG NO.

NYC DOB NO.


E-300.00
MEP CONSULTANT

1430 Broadway
New York, NY 10018
V: 212.868.4660
F: 212.868.4680

3 ISSUED FOR ADDENDUM #1 5/2/2024 JB

3 ISSUED FOR BID 4/26/2024 JB

2 ISSUED FOR DOB FILING 4/5/2024 MYS

1 ISSUED FOR REVIEW 3/22/2024 MYS

NO. REVISION DATE BY

TPG ARCHITECTURE, LLP


31 PENN PLAZA
132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001
212.768.0800 | TPGARCHITECTURE.COM

IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN


AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT
PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE
LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND
COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF,
OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION,
OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED
BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.

PROJECT
S:\CAD\1359 BWAY\20FL_PROGYNY_DEMO BUILDOUT_23043.08\03-DWGS\E-400.DWG / Plot Date: May, 2, 2024 - 4:54 :PM

PROGYNY
2ND AND 20TH FLOOR
1359 BROADWAY
NEW YORK, NY 10018
DRAWING

ELECTRICAL
PANEL
SCHEDULES

SEAL DATE
1.29.24
PROJECT NO.
11523048-00
Last Saved By: AMETA / Save Date: 5/1/2024 10:50:52 AM

SCALE
AS SHOWN
CAD FILE NO. DOB PAGE
X of #
DWG NO.

NYC DOB NO.


E-400.00
MEP CONSULTANT

1430 Broadway
New York, NY 10018
V: 212.868.4660
FIRE ALARM NOTES F: 212.868.4680
1. PRIOR TO SUBMISSION OF BIDS: THE ELECTRICAL CONTRACTOR SHALL CONTACT FIRE ALARM SYMBOL LIST
THE BUILDING FIRE ALARM VENDOR AND BUILDING CHIEF ENGINEER FOR
DIRECTIONS.
2. ALL FIRE ALARM DEVICES SHALL BE PURCHASED FROM BUILDING FIRE ALARM
VENDOR TO ASSURE COMPATIBILITY WITH THE EXISTING SYSTEM. ALL FIRE ALARM SMOKE DETECTOR
DEVICES SHALL BE UL LISTED AND NYC APPROVED. THE FIRE ALARM VENDORS EL DENOTES ELEVATOR RECALL
PRICE SHALL INCLUDE ALL REQUIRED DEVICES (ZONES, BATTERIES, ETC.) TO MAKE
THIS A COMPLETE WORKING SYSTEM.
3. THIS IS NOT A POINT TO POINT WIRING DIAGRAM. USE THIS DIAGRAM FOR DUCT MOUNTED SMOKE DETECTOR
ESTIMATING PURPOSES ONLY. PRIOR TO STARTING ANY WORK, A WORKING POINT
TO POINT WIRING DIAGRAM SHALL BE OBTAINED FROM BUILDING FIRE ALARM
VENDOR. THE EXACT LOCATION AND QUANTITIES OF FIRE ALARM DEVICES, REFER
STROBE
TO FLOOR PLANS.
4. CONTRACTOR TO PROTECT AND MAINTAIN ALL REMAINING FIRE ALARM DEVICES
AND CABLING DURING CONSTRUCTION. FIRE STOP ALL OPENINGS IN FLOOR AND B
WALL. C SPEAKER STROBE
5. ALL REPROGRAMMING OF SOFTWARE, HARDWARE AND THE FINAL CONNECTIONS
TO EXISTING FIRE DATA GATHERING PANEL SHALL BE DONE BY BUILDING FIRE TO NEAREST
ALARM VENDOR, BUT THIS CONTRACTOR SHALL INCLUDE PRICE OF THIS WORK IN ADDRESSABLE FIRE ALARM EL EL EL EL FOR DOOR RELEASE PULL STATION
THE BID PRICE. THE FIRE ALARM VENDOR SHALL ALSO INCLUDE ALL EQUIPMENT DATA GATHERING PANEL
(DGP, CABLES STROBE PANEL, PROGRAMMING, ETC.) REQUIRED TO MAKE THE
SYSTEM OPERABLE.
6. STROBE LIGHTS SHALL BE ADA APPROVED TYPE AND SHALL BE MOUNTED AT 80" EX RELAY
ABOVE FINISHED FLOOR OR 6" BELOW CEILING, WHICHEVER IS LOWER. STROBE A
LIGHTS SHALL BE RATED AT 75 CANDELA.
7. ALL EXISTING BASE BUILDING DEVICES ARE TO REMAIN UNLESS OTHERWISE NOTED. WARDEN STATION
REACTIVATE AND LEAVE IN WORKING CONDITION UPON COMPLETION OF THIS
PROJECT.
8. IF EXISTING BASE BUILDING DEVICES ARE NOT IN WORKING ORDER, THE 20TH FLOOR 20TH FLOOR
CONTRACTOR SHALL REPAIR/REPLACE AS PART OR THIS SCOPE OF WORK. FIRE SMOKE DAMPER
9. THE INSTALLATION SHALL COMPLY WITH THE BUILDING CODE OF THE CITY OF NEW
YORK, NATIONAL ELECTRICAL CODE WITH NEW YORK CITY AMENDMENTS TO THE
NATIONAL ELECTRICAL CODE AND RELATED ADMINISTRATIVE PROVISIONS AND THE
PARTIAL FIRE ALARM RISER DIAGRAM FAN SHUTDOWN RELAY
NYC FIRE DEPARTMENT REQUIREMENTS. N.T.S.
10. THE CONTRACTOR SHALL FILE A-433 AND OBTAIN APPROVAL FROM THE FIRE
DEPARTMENT.
11. PROVIDE ALTERNATE STROBE LIGHT AND SPEAKER CIRCUITS A & B TO FEED NEW STROBE BOOSTER PANEL
DEVICES TO BALANCE LOAD AND TO ELIMINATE ADJACENT DEVICES WIRED TO SAME
CIRCUITS.
12. LOCATIONS FOR ALL SPEAKER/STROBES & OTHER F.A. & SECURITY DEVICES ARE TO
BE VERIFIED WITH ARCHITECT PRIOR TO INSTALLATION. PARTIAL RISER DIAGRAM NOTES: EXISTING WIRING

13. CONTRACTOR SHALL VERIFY EXACT LOCATION OF NEAREST USABLE DGP WITHE
BASE BLDG FIRE ALARM REPRESENTATIVE PRIOR TO SUBMISSION OF BID. 1. CONTRACTOR SHALL REMOVE ALL EXISTING FIRE ALARM DEVICES WITHIN AREA OF
14. CONNECT ALL SPEAKERS (IN SPEAKER/STROBE DEVICES) INDEPENDENTLY TO THE WORK. PROVIDE NEW DEVICES AS SHOWN ON PLAN. NEW WIRING
EXISTING FIRE ALARM CONTROL PANEL. 2. WIRE SECURITY RELAY TO FIRE ALARM LOOP AS PER THE BUILDING FIRE ALARM
15. ALL INACCESSIBLE DUCT DETECTORS SHALL HAVE A REMOTE LED INDICATOR. VENDOR'S REQUIREMENTS & NYC FIRE DEPARTMENT RULES. PROVIDE NECESSARY
16. CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMISSION OF AS-BUILTS TO WIRING, DEVICES, ACCESSORIES & RE-PROGRAMING TO ENSURE THAT THE EX EXISTING TO REMAIN
ENGINEER MINIMUM 1 WEEK PRIOR TO FIRE DEPARTMENT TESTING OR CLIENT ELECTRO-MAGNETIC LOCK SYSTEMS WILL FUNCTION PROPERLY DURING
MOVE-IN, WHICHEVER COMES FIRST. EMERGENCY SITUATIONS.
17. FIRE ALARM WIRING SHALL BE CLASS B AND LEVEL OF SURVIVABILITY SHALL BE 3. PROVIDE ALL NECESSARY MODULES TO OBTAIN SYNCHRONIZATION OF ALL FIRE
R TO BE REMOVED
LEVEL 1. ALARM STROBES (NEW AND EXISTING)
18. PRIOR TO BID, CONTACT THE FIRE ALARM VENDOR FOR COMPLETE AND TOTAL BID
PACKAGE INCLUDING ANY NEW STROBE POWER PANELS AND DATA GATHERING
PANELS REQUIRED FOR A FULLY FUNCTIONAL SYSTEM. PROVIDE THESE DEVICES AS RL TO BE RELOCATED
REQUIRED
19. ALL HVAC UNITS 2,000 CFM OR MORE SHALL BE PROVIDED WITH DUCT DETECTORS FIRE ALARM WIRING SCHEDULE
AND A RELAY FOR SHUT DOWN. COORDINATE WITH THE FIRE ALARM VENDOR AND RE
HVAC CONTRACTOR RELOCATED
20. ALL WIRING FOR THE FIRE ALARM SYSTEM (NEW AND EXISTING TO REMAIN) IN OPEN 1 PAIR #16 AWG FPLP PER CIRCUIT - ADDRESSABLE LOOP
OR EXPOSED CEILING AREAS SHALL BE IN CONDUIT. EXISTING WIRING TO REMAIN
SHALL BE REINSTALLED IN CONDUIT. 1 PAIR #14 AWG FPLP PER CIRCUIT - VISUAL CIRCUIT

1 PAIR #14 AWG FPLP PER CIRCUIT - SPEAKER CIRCUIT FIRE ALARM MATRIX
DEVICES
1 PAIR #16 AWG FPLP PER CIRCUIT - TELEPHONE CIRCUIT

ELEVATOR MACHINE ROOM SMOKE DETECTOR


ELEVATOR LOBBY SMOKE DETECTOR

DUCT DETECTOR (RETURN)


DUCT DETECTOR (SUPPLY)

SMOKE/HEAT DETECTOR
* FIRE ALARM ZONE IS DEFINED AS

MANUAL PULL STATION

WATERFLOW SWITCH
THE FLOOR ABOVE AND BELOW THE
FLOOR, AS WELL AS THE FLOOR THAT

TAMPER SWITCH
IS IN ALARM.

STATUS INDICATION AT FACP X X X X X X X X


AUDIBLE NOTIFICATION FIRE ZONE * X X X X X X X
VISUAL NOTIFICATION FIRE ZONE * X X X X X X X
FAN SHUTDOWN X X X X X X X
DAMPER CLOSE X X X X X X X
DOOR RELEASE X X X X X X X
ELEVATOR RECALL X X X
CENTRAL OFFICE NOTIFICATION X X X X X X X X

3 ISSUED FOR ADDENDUM #1 5/2/2024 JB

3 ISSUED FOR BID 4/26/2024 JB

2 ISSUED FOR DOB FILING 4/5/2024 MYS

1 ISSUED FOR REVIEW 3/22/2024 MYS

NO. REVISION DATE BY

TPG ARCHITECTURE, LLP


31 PENN PLAZA
132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001
212.768.0800 | TPGARCHITECTURE.COM

IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN


AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT
PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE
LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND
COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF,
OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION,
OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED
BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.

PROJECT
S:\CAD\1359 BWAY\20FL_PROGYNY_DEMO BUILDOUT_23043.08\03-DWGS\FA-001.DWG / Plot Date: May, 2, 2024 - 4:54 :PM

PROGYNY
2ND AND 20TH FLOOR
1359 BROADWAY
NEW YORK, NY 10018
DRAWING

FIRE ALARM
SYMBOLS, NOTES
AND ABBREVIATIONS

SEAL DATE
1.29.24
PROJECT NO.
11523048-00
Last Saved By: AMETA / Save Date: 5/2/2024 4:50:31 PM

SCALE
AS SHOWN
CAD FILE NO. DOB PAGE
X of #
DWG NO.

NYC DOB NO.


FA-001.00
MEP CONSULTANT

1430 Broadway
New York, NY 10018
V: 212.868.4660
F: 212.868.4680

WEST 37TH ST. FIRE ALARM NOTES:

COPY PRIVATE PRIVATE STORAGE


AREA OFFICE OFFICE ROOM
20-33 20-34 20-35 20-36

75CD N

OPEN
AREA
N N N N
N N 20-37
OPEN
AREA
N N
20-32
N

75CD

PRIVATE
OFFICE
20-38

MEETING
ROOM N N
20-30 FEC N N

TP
PRIVATE PHONE
OFFICE ROOM
20-29 20-39

PHONE PRIVATE
ROOM TP OFFICE
TP N N ”
20-28 N N 20-40
N 15CD MENS
STORAGE RESTROOM
ROOM N N 15CD 20-41
N N
20-27
N 15CD DOOR RELEASE N ELECTRICAL
IDF N 15CD CLOSET
ROOM N 30CD 20-42
N
20-26 N COMMUNICATIONS
N
CLOSET
N N PRIVATE
N 20-43
N 15CD OFFICE

BRO
CORRIDOR
20-44
20-25
COAT
CLOSET
20-24

ADW
75CD
P. E. P. E. P. E.
PHONE TP
ROOM

FEC
N PRIVATE
20-23 OFFICE
CONFERENCE 20-45

AY
ROOM ELEVATOR
20-22 TP LOBBY
ADA 75CD 20-00
N N
RESTROOM EL EL
15CD
20-21 N N N 15CD
ADA N
RESTROOM TP
N
20-20 PANTRY
AREA
PRIVATE 20-01
OFFICE P. E. P. E. P. E. PRIVATE
N OFFICE
20-19 15CD N N
LACTATION 20-46
75CD
ROOM N 15CD N
20-18
STROBE BOOSTED
STORAGE PANEL N N WOMENS
CLOSET SHAFT 15CD
RESTROOM
20-17 15CD
N 20-02
STAIR N
20-16 FEC
N N
PRIVATE
OFFICE 75CD
TP
20-15 STORAGE
F. E. N N N ROOM
PRIVATE 20-03
OFFICE TP N N
N N N PRIVATE
20-14 EL 15CD OFFICE
N N
N N 20-47
MEETING N
ROOM
F. E.
20-13 PRIVATE
OFFICE
N N 20-04
COPY
AREA N N
20-12
F. E.
TP
FEC
N
EL

F. E.

N 30CD N N N N N N N N
15CD N
OPEN
AREA
N N N N 20-05

MER N
ROOM
N N
20-11
N 75CD N 75CD
N 75CD

N N OPEN PRIVATE PRIVATE PRIVATE PANTRY


AREA OFFICE OFFICE OFFICE AREA
20-10 20-09 20-08 20-07 20-06
N

WEST 36TH ST.

3 ISSUED FOR ADDENDUM #1 5/2/2024 JB

3 ISSUED FOR BID 4/26/2024 JB

FIRE ALARM 20TH FLOOR PLAN 2

1
ISSUED FOR DOB FILING

ISSUED FOR REVIEW


4/5/2024

3/22/2024
MYS

MYS
SCALE:1/8"=1'-0"
8' 4' 0' 8' NO. REVISION DATE BY

1/8"= 1'-0"

TPG ARCHITECTURE, LLP


31 PENN PLAZA
132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001
212.768.0800 | TPGARCHITECTURE.COM

IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN


AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT
PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE
LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND
COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF,
OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION,
OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED
BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.

PROJECT
S:\CAD\1359 BWAY\20FL_PROGYNY_DEMO BUILDOUT_23043.08\03-DWGS\FA-100.DWG / Plot Date: May, 2, 2024 - 4:54 :PM

PROGYNY
2ND AND 20TH FLOOR
1359 BROADWAY
NEW YORK, NY 10018
DRAWING

FIRE ALARM
20TH FLOOR PLAN

SEAL DATE
1.29.24
PROJECT NO.
11523048-00
Last Saved By: AMETA / Save Date: 5/2/2024 4:52:43 PM

SCALE
AS SHOWN
CAD FILE NO. DOB PAGE
X of #
DWG NO.

NYC DOB NO.


FA-100.00
MEP CONSULTANT
GENERAL NOTES 1430 Broadway
1. ALL PIPING PENETRATING THROUGH FIRE-RATED PARTITIONS SHALL BE SEALED
New York, NY 10018
WITH MATCHING FIRE-RATED MATERIAL. V: 212.868.4660
F: 212.868.4680
2. ALL PIPING AND CONDUIT RUNS SHALL BE COORDINATED WITH ALL TRADES.
CONTRACTORS SHALL ADVISE OF ANY CONFLICTS OR INTERFERENCES PRIOR TO
INSTALLATION.

3. CONTRACTOR SHALL SUBMIT COORDINATED SHOP DRAWING FOR THE


REFRIGERANT PIPING AND CONDENSATE PIPING FOR REVIEW AND APPROVAL BY
ENGINEER OF RECORD PRIOR TO ANY INSTALLATIONS.

4. CONTRACTOR SHALL SUBMIT COORDINATED PIPING SHOP DRAWING TO VRF


MANUFACTURER FOR REFRIGERANT PIPING SIZE CONFIRMATION. CONTRACTOR
SHALL NOT INSTALL ANY PIPING UNTIL SIZES ARE CONFIRMED WITH
MANUFACTURER.

N.I.C 5. REFRIGERANT PIPING SHALL BE HARD TEMPER TYPE 'L' COPPER PIPING WITH
BRAZED SEAMS. ALL FITTINGS SHALL BE WROUGHT COPPER TYPE MEETING
ANSIB16.22 SPECIFICATION.

6. FLUX SHALL NOT BE USED FOR BRAZING PROCEDURE. USE PHOSPHOR-COPPER


BRAZING FILLER METAL.

NEW OUTDOOR VRF UNITS TO INSTALLED ON STEEL 7. ALL REFRIGERANT PIPING SHALL BE CLEANED OF ALL DUST, DIRT, CUTTING OIL,
MOISTURE OR ANY OTHER CONTAMINATION PRIOR TO CHARGING THE SYSTEM
1 DUNNAGE W/ SPRING VIBRATION ISOLATORS.
COORDINATE WITH THE STRUCTURAL DRAWINGS FOR WITH REFRIGERANT.
UNIT SUPPORT.
8. CONTRACTOR SHALL PROVIDE ALL TRAPS, INVERTED TRAPS AND INTERMEDIATE
TYP. FOR (3) TRAPS IN REFRIGERANT PIPING AS REQUIRED BY UNIT MANUFACTURERS IOM DUE
TO CHANGE IN ELEVATION.

9. PRIOR TO FINAL CONNECTIONS AND ADDITION OF REFRIGERANT CHARGE,


CONTRACTOR SHALL PRESSURE TEST ALL REFRIGERANT PIPING TO 300PSIG FOR
30 MINUTES WITH DRY NITROGEN. THERE SHALL BE NO DROP IN TEST PRESSURE
OVER 30 MINUTE DURATION.
ACCU-1 ACCU-2 ACCU-3 10. ALL REFRIGERANT PIPING SHALL BE INSULATED WITH 1-1/2" CLOSED CELL FOAM
INSULATION WITH ALL JOINTS AND SEAMS SEALED AND TAPED.

11. ALL REFRIGERANT AND CONDENSATE PIPING INSTALLED IN EXTERIOR SPACES


SHALL BE COVERED WITH ALUMINUM JACKETING.

12. ALL REFRIGERANT PIPING SHALL BE SUPPORTED WITH CLAMP ON KINDORF


MAIN REFRIGERANT PIPING FROM OUTDOOR VRF UNITS SIZED PER THE TRAPEZE HANGERS AS PER DESIGN DETAIL. PIPE CLAMPS SHALL BE
MANUFACTURERS SPECIFICATIONS. PIPING SHALL BE RUN TIGHT TO THE CUSH-A-THERM CLAMPS WITH RIGID CLOSED CELL FOAM INSULATION. CLAMPS
PARAPET AND STACKED ON TOP OF ONE ANOTHER. EXISTING ROOFTOP AC UNITS MOUNTED ON STEEL SHALL NOT BE INSTALLED IN DIRECT CONTACT WITH PIPING.
DUNNAGE SHALL REMAIN AND BE PROTECTED.
(6) PIPES IN TOTAL.

N.I.C

EXISTING ROOFTOP AC UNIT TO


REMAIN AND BE PROTECTED.

PIPING TO BE RUN DOWN ALONG THE EXTERIOR OF THE BUILDING DOWN TO THE
20TH FLOOR. PIPING SHALL BE INSTALLED TIGHT TO THE WALL. COORDINATE WITH
BUILDING ENGINEERING FOR FINAL ROUTING. REFER TO DWG M-106 FOR 20TH
FLOOR PENETRATION LOCATION AND ROUTING CONTINUATION.

(6) PIPES IN TOTAL

N.I.C

N.I.C

N.I.C

1 3 ISSUED FOR ADDENDUM #1 5/2/2024 JB

3 ISSUED FOR BID 4/26/2024 JB

2 ISSUED FOR DOB FILING 4/5/2024 MYS

1 ISSUED FOR REVIEW 3/22/2024 MYS


MECHANICAL 22ND FLOOR ROOF PLAN NO. REVISION DATE BY
SCALE:1/4"=1'-0"
4' 2' 0' 4'

1/4"= 1'-0"
TPG ARCHITECTURE, LLP
31 PENN PLAZA
132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001
212.768.0800 | TPGARCHITECTURE.COM

IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN


AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT
PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE
LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND
COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF,
OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION,
OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED
BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.
S:\CAD\1359 BWAY\20FL_PROGYNY_DEMO BUILDOUT_23043.08\03-DWGS\M-105-ROOF.DWG / Plot Date: May, 2, 2024 - 4:47 :PM

PROJECT

PROGYNY
2ND AND 20TH FLOOR
1359 BROADWAY
NEW YORK, NY 10018
DRAWING

MECHANICAL
22ND FLOOR ROOF PLAN

SEAL DATE
1.29.24
PROJECT NO.
11523048-00
Last Saved By: CHIRST / Save Date: 5/2/2024 10:07:18 AM

SCALE
AS SHOWN
CAD FILE NO. DOB PAGE
8 of 13
DWG NO.

NYC DOB NO.


M-105.00
MEP CONSULTANT

1430 Broadway
SPLIT AIRCOOLED VRF HEAT RECOVERY INDOOR UNITS MFR. (AS STD.) "MITSUBISHI ELECTRIC - TRANE" New York, NY 10018
ELECTRICAL
V: 212.868.4660
RATED PERFORMANCE CLG. DESIGN PERFORMANCE HTG. DESIGN PERFORMANCE FAN INFORMATION REFRIGERANT PIPE
F: 212.868.4680
AC UNIT SERVICE LOCATION MODEL OUTDOOR UNIT BRANCH UNIT UNIT TYPE REFRIGERANT COOLING HEATING T.C S.C. EAT DB EAT WB T.C EAT DB LOW MED HIGH NOISE UNIT WEIGHT LIQUID PIPE GAS PIPE
(CFM) (CFM) (CFM) VOLTS Ø HZ MCA MAX FUSE (db(A)) (LBS) (INCHES) (INCHES)
BTU/HR BTU/HR BTU/HR BTH/HR DEG F DEG F BTU/HR DEG F

FCU-1 20-22 20-19 TPEFYP015MA144A ACCU-1 BC-1 CEILING-CONCELED (DUCTED) R410A 15,000 17,000 15,018 11,371 80 67 12,341 70 - - 494 208 1 60 2.9 15 - - - -

FCU-2 20-00/12 20-15 TPEFYP018MA144A ACCU-1 BC-1 CEILING-CONCELED (DUCTED) R410A 18,000 20,000 18,022 13,724 80 67 14,519 70 - - 600 208 1 60 2.9 15 - - - -

FCU-3 20-19 20-14 TPEFYP015MA144A ACCU-1 BC-1 CEILING-CONCELED (DUCTED) R410A 15,000 17,000 15,018 11,371 80 67 12,341 70 - - 494 208 1 60 2.9 15 - - - -

FCU-4 20-18/23 20-13 TPEFYP015MA144A ACCU-1 BC-1 CEILING-CONCELED (DUCTED) R410A 15,000 17,000 15,018 11,371 80 67 12,341 70 - - 494 208 1 60 2.9 15 - - - -

FCU-5 20-13 20-13 TPEFYP006MA144A ACCU-1 BC-1 CEILING-CONCELED (DUCTED) R410A 6,000 6,700 6,007 5,763 80 67 4,864 70 - - 300 208 1 60 1.8 15 - - - -

FCU-6 20-10 20-10 TPEFYP036MA144A ACCU-1 BC-1 CEILING-CONCELED (DUCTED) R410A 36,000 40,000 36,044 28,406 80 67 29,039 70 - - 1271 208 1 60 4.3 15 - - - -

FCU-7 20-10 20-10 TPEFYP036MA144A ACCU-1 BC-1 CEILING-CONCELED (DUCTED) R410A 36,000 40,000 36,044 28,406 80 67 29,039 70 - - 1271 208 1 60 4.3 15 - - - -

FCU-8 20-9/8/7/4 20-09 TPEFYP018MA144A ACCU-1 BC-1 CEILING-CONCELED (DUCTED) R410A 18,000 20,000 18,022 13,724 80 67 14,519 70 - - 600 208 1 60 2.9 15 - - - -

FCU-9 20-10 20-10 TPEFYP036MA144A ACCU-2 BC-2 CEILING-CONCELED (DUCTED) R410A 36,000 40,000 32,124 26,902 80 67 24,398 70 - - 1271 208 1 60 4.3 15 - - - -

FCU-10 20-10 20-10 TPEFYP036MA144A ACCU-2 BC-2 CEILING-CONCELED (DUCTED) R410A 36,000 40,000 32,124 26,902 80 67 24,398 70 - - 1271 208 1 60 4.3 15 - - - -

FCU-11 20-05 20-05 TPEFYP042MA144A ACCU-2 BC-2 CEILING-CONCELED (DUCTED) R410A 48,000 54,000 42,832 31,477 80 67 32,937 70 - - 1306 208 1 60 4.4 15 - - - -

FCU-12 20-05 20-04 TPEFYP012MA144A ACCU-2 BC-2 CEILING-CONCELED (DUCTED) R410A 12,000 13,500 10,708 7,832 80 67 8,234 70 - - 371 208 1 60 2.1 15 - - - -

FCU-13 20-05 20-46/47 TPEFYP024MA144A ACCU-2 BC-2 CEILING-CONCELED (DUCTED) R410A 24,000 27,000 21,416 18,228 80 67 16,469 70 - - 883 208 1 60 2.9 15 - - - -

FCU-14 20-01 20-06 TPEFYP036MA144A ACCU-2 BC-2 CEILING-CONCELED (DUCTED) R410A 36,000 40,000 32,124 26,902 80 67 24,398 70 - - 1271 208 1 60 4.3 15 - - - -

FCU-15 20-30 20-27 TPEFYP015MA144A ACCU-3 BC-3 CEILING-CONCELED (DUCTED) R410A 15,000 17,000 13,409 10,742 80 67 9,030 70 - - 494 208 1 60 2.9 15 - - - -

FCU-16 20-28/29 20-29 TPEFYP008MA144A ACCU-3 BC-3 CEILING-CONCELED (DUCTED) R410A 8,000 9,000 7,151 6,105 80 67 4,780 70 - - 300 208 1 60 1.8 15 - - - -

FCU-17 20-32 20-32 TPEFYP024MA144A ACCU-3 BC-3 CEILING-CONCELED (DUCTED) R410A 24,000 27,000 21,454 18,242 80 67 14,341 70 - - 883 208 1 60 2.9 15 - - - -

FCU-18 20-32 20-32 TPEFYP024MA144A ACCU-3 BC-3 CEILING-CONCELED (DUCTED) R410A 24,000 27,000 21,454 18,242 80 67 14,341 70 - - 883 208 1 60 2.9 15 - - - -

FCU-19 20-32 20-32 TPEFYP024MA144A ACCU-3 BC-3 CEILING-CONCELED (DUCTED) R410A 24,000 27,000 21,454 18,242 80 67 14,341 70 - - 883 208 1 60 2.9 15 - - - -

FCU-20 20-37 20-37 TPEFYP024MA144A ACCU-3 BC-3 CEILING-CONCELED (DUCTED) R410A 24,000 27,000 21,454 18,242 80 67 14,341 70 - - 883 208 1 60 2.9 15 - - - -

FCU-21 20-37 20-37 TPEFYP036MA144A ACCU-3 BC-4 CEILING-CONCELED (DUCTED) R410A 36,000 40,000 32,182 26,923 80 67 21,246 70 - - 1271 208 1 60 4.3 15 - - - -

FCU-22 20-34/35/39 20-34 TPEFYP015MA144A ACCU-3 BC-4 CEILING-CONCELED (DUCTED) R410A 15,000 17,000 13,409 10,742 80 67 9,030 70 - - 494 208 1 60 2.9 15 - - - -

FCU-23 20-38/40 20-39 TPEFYP024MA144A ACCU-3 BC-4 CEILING-CONCELED (DUCTED) R410A 24,000 27,000 21,454 18,242 80 67 14,341 70 - - 883 208 1 60 2.8 15 - - - -

FCU-24 20-44/45 20-01 TPEFYP024MA144A ACCU-3 BC-4 CEILING-CONCELED (DUCTED) R410A 24,000 27,000 21,454 18,242 80 67 14,341 70 - - 883 208 1 60 2.9 15 - - - -

FCU-25 20-32 20-32 TPEFYP024MA144A ACCU-3 BC-4 CEILING-CONCELED (DUCTED) R410A 24,000 27,000 21,454 18,242 80 67 14,341 70 - - 883 208 1 60 2.9 15 - - - -

NOTES:

1. SELECTION BASED ON EQUIPMENT MANUFACTURED BY MITSUBISHI ELECTRIC / TRANE.


2. SEE OUTDOOR CONDENSING UNIT SCHEDULE FOR DETAILS REGARDING CONNECTION CAPACITY, OUTDOOR CONDITIONS AND OTHER FACTORS ASSOCIATED WITH CORRECTED CAPACITIES.
3. INDOOR (FAN COIL UNIT) AND OUTDOOR (CONDENSING UNIT) SHALL BE OF THE SAME MANUFACTURER AND SHALL BE CERTIFIED FOR USE WITH EACH OTHER. REMOTE CONDENSING UNITS SHALL BE SECURELY MOUNTED AS DETAILED IN THE MANUFACTURERS INSTALLATION MANUAL AND THE
DESIGN DOCUMENTS.
4. CONTRACTOR TO CONFIRM REFRIGERANT PIPING SIZES WITH THE MANUFACTURER BASED ON ACTUAL FIELD ROUTING OF REFRIGERANT PIPING. ROUTE AS SHOWN ON DESIGN DOCUMENTS IS SCHEMATIC AND SHALL BE VERIFIED BY THE CONTRACTOR. CONTRACTOR TO SUBMIT REFRIGERANT
PIPING SHOP DRAWING FOR MANUFACTURER AND ENGINEER OF RECORD REVIEW.
5. ALL FCUs SHALL BE PROVIDED WITH AN INTERNAL, FACTORY INSTALLED CONDENSATE PUMP CAPABLE OF 25" OF LIFT.
6. PROVIDE MITSUBISHI PAR-40MAAU FACTORY REMOTE CONTROLLER FOR EACH EVAPORATOR UNIT.
7. PROVIDE MITSUBISHI FBM2-1-A, FBM2-2-A, FBM2-3-A, OR FBM2-4-A MERV 13 FILTER BOX FOR EACH FCU, COORDINATE INVERTIBLE FILTER ACCESS SIDE AND FIELD CONVERTIBLE INLET OPENING CONFIGURATION WITH FIELD CONDITIONS. INSTALL NEW MERV 13 FILTERS.
8. OUTSIDE AIR DUCTWORK SHALL BE CONNECTED TO OPENING ON UNIT CASING W/ FLEXIBLE CONNECTION, REFER TO MANUFACTURER IOM .
9. BMS CONTRACTOR SHALL PROVIDE REQUIRED CONTROLLERS TO INTERLOCK RADIATOR CONTROL VALVE AND LEAK DETECTION.
10. PROVIDE SECONDARY STAINLESS STEEL DRIP PAN BELOW EACH EVAPORATOR WITH LEAK DETECTOR. UPON ACTIVATION OF LEAK DETECTOR, ASSOCIATED AC/FCU, BRANCH CONTROLLER OR CONDENSING UNIT SHALL SHUT DOWN AND SOUND LOCAL AND BMS ALARM.
11. CONTRACTOR SHALL CONSTANT AIR REGULATOR (CAR) AND VOLUME DAMPERS AT EACH FCU OA CONNECTION, AND BALANCE TO CFM VALUES INDICATED ONPLAN.
12. CONTRACTOR TO PROVIDE MODULATING MOTORIZED DAMPER AT OA CONNECTION TO EACH CONFERENCE ROOM FCU. MOTORIZED DAMPER ACTUATORS BY BMS CONTRACTOR (BUILDING STD.); DAMPER MATERIAL SHALL BE EXTRUDED ALUMINUM BODY WITH INSULATED BLADES AND LOW
LEAKAGE SILICONE SEALS (MFR. TAMCO MODEL NO. 9000 PER BUILDING STD. -CONTACT TIM DAILY: 212-643-8001).

CEILING DIFFUSERS/RETURN GRILLES MFR. (AS STD.) "TITUS" SPLIT AIRCOOLED VRF HEAT RECOVERY OUTDOOR UNITS MFR. (AS STD.) "MITSUBISHI ELECTRIC - TRANE"

RATED PERFORMANCE CLG. DESIGN PERFORMANCE HTG. DESIGN PERFORMANCE ELECTRICAL REFRIGERANT PIPE CONNECTION SIZE
CFM NOMINAL MAX. CFM MAX S.P. UNIT
FACE SIZE MODEL REMARKS FAN NOISE AHRI AHRI
RANGE NECK SIZE NC (IN. H 0)
2 AC SERVICE LOCATION MODEL UNIT TYPE REFRIGERANT EAT EAT WEIGHT LIQUID SUCTION HP GAS
T.C. HEATING T.C. T.C. (CFM) MAX (dB(A)) IEER/EER COP
UNIT DB DB VOLTS Ø HZ MCA SCCR (LBS) PIPE PIPE PIPE
BTU/H BTU/H BTU/H BTU/H FUSE
DEG F DEG F (INCHES) (INCHES) (INCHES)
0-130 6"Ø 10 0.OO3 24"x24" OMNI
ACCU-1 BC-1 22ND FL ROOFTOP TURYE1683AN41AN N GENERATION R-2, VRF, HEAT RECOVERY R-410A 168,000 188,000 159,950 90 126,820 10.8 - 208 3 60 70 110 5 85.5 887 7/8" - 1-1/8" 19.4/10.5 3.42
131-220 8"Ø 10 0.029 24"x24" OMNI
10 ACCU-2 BC-2 22ND FL ROOFTOP TURYE1923AN41AN N GENERATION R-2, VRF, HEAT RECOVERY R-410A 192,000 215,000 171,330 90 130,835 10.8 - 208 3 60 80 125 5 85.5 887 7/8" - 1-1/8" 26.5/12.2 3.76
221-330 10"Ø 0.038 24"x24" OMNI

431-600 21 0.101 ACCU-3 BC-3 & BC-4 22ND FL ROOFTOP TURYE2403AN40AN N GENERATION R-2, VRF, HEAT RECOVERY R-410A 240,000 255,000 216,330 90 143,950 10.8 - 208 3 60 82 125 5 68 887 7/8" - 1-1/8" 22.8/10.5 3.42
12"Ø 24"x24" OMNI

601-750 14"Ø 20 0.124 24"x24" OMNI NOTES:

1. SELECTION BASED ON EQUIPMENT MANUFACTURED BY MITSUBISHI ELECTRIC / TRANE.


- 24"x12" - - 12"x24" 350RL GRILLE 2. UNIT SHALL BE CERTIFIED, LISTED AND LABELED PER AHRI1230.
3. CONDENSING UNITS TO BE PROVIDED WITH MODULATING INVERTER DRIVEN SCROLL COMPRESSORS.
- 24"x24" - - 24"x24" 350RL GRILLE 4. INSTALLING CONTRACTOR MUST HAVE SUCCESSFULLY COMPLETED MANUFACTURERS CERTIFIED INSTALLATION CLASS WITHIN THE PAST 36 MONTHS.
5. ENTIRE SYSTEM SHALL BE PROVIDED WITH A 10 YEAR, PARTS ONLY WARRANTY, INCLUDING COMPRESSORS. CONTRACTOR TO COMPLY WITH MANUFACTURER PROCEDURES FOR EXTENDED SYSTEM WARRANTY INCLUDING PIPING DOCUMENTATION, INSTALLATION QUALITY MANAGEMENT, INSTALLER TRAINING,
AND MANUFACTURER INSPECTIONS. CONTRACTOR SHALL OBTAIN AND PROVIDE MANUFACTURER'S EXTENDED WARRANTY.
NOTES: 6. CONTRACTOR TO CONFIRM REFRIGERANT PIPING SIZES WITH THE MANUFACTURER BASED ON ACTUAL FIELD ROUTING OF REFRIGERANT PIPING. ROUTE AS SHOWN ON DESIGN DOCUMENTS IS SCHEMATIC AND SHALL BE VERIFIED BY THE CONTRACTOR.
7. CONDENSING UNIT STATIC PRESSURE SETTING TO BE FIELD CHANGED TO MAX. AVAILABLE FOR DUCTED EXHAUST CONFIGURATION. REFER TO MANUFACTURERS IOM.
1. COORDINATE EXACT LOCATION WITH ARCHITECTS DRAWINGS. 8. PROVIDE FACTORY ACCESSORY BASE PAN HEATER AND REQUIRED CONTROL BOX, TO BE FIELD INSTALLED BY THE CONTRACTOR. INSTALL PER MANUFACTURER IOM.
9. AIR SOURCE CONDENSING UNITS SHALL HAVE RATED CAPACITY DATA FROM -13F TO 122F.
2. PROVIDE DIFFUSERS WITH EQUALIZING GRID AND OPPOSED BLADE DAMPERS 10. PROVIDE MITSUBISHI TE-200A SYSTEM CENTRALIZED CONTROLLER WITH BACNET INTERFACE W/ ACTIVATED LICENSE FOR CONNECTION OF EQUIPMENT TO BASE BUILDING BMS. INTEGRATION TO BMS SHALL BE COMPLETED BY BMS CONTRACTOR.
3. PROVIDE IN LAY-IN CEILINGS WITH TYPE 3 FRAME. 11. MOTORIZED DAMPER ACTUATORS BY BMS CONTRACTOR (BUILDING STD.); DAMPER MATERIAL SHALL BE EXTRUDED ALUMINUM BODY WITH INSULATED BLADES AND LOW LEAKAGE SILICONE SEALS (MFR. TAMCO MODEL NO. 9000 PER BUILDING STD. -CONTACT TIM DAILY: 212-643-8001).
4. FOR 2-WAY OR 3-WAY BLOW, BLANK OFF NEXT (NECK TO BE NEXT SIZE. 12. CONTRACTOR TO PROVIDE 16 GAUGE STAINLESS STEEL DRIP PAN W/ 2" LIP AND SOLDERED SEAMS. BENEATH CONDENSING UNIT. PITCH PAN TOWARDS DRAIN CONNECTION AND PROVIDE 3/4" DRAIN PIPE TO FLOOR DRAIN IN MER. REFER TO MER PART PLANS FOR ADDITIONAL INFORMATION.
5. ALL SUPPLY REGISTERS SHALL BE DOUBLE DEFLECTING TYPE, FRONT BLADES VERTICAL AS MANUFACTURED BY "TITUS", 13. CONTRACTOR SHALL PROVIDE (4) 1" DEFLECTION SPRING VIBRATION ISOLATORS FOR EACH CONDENSING UNIT.
MODEL 300RS.
6. PROVIDE TITUS "LIGHTSHIELD" FOR ALL CEILING RETURN GRILLES.
7. PROVIDE CORD OPERATED DAMPERS WHERE GRILLES ARE INSTALLED IN INACCESSIBLE CEILINGS.
MFR. (AS STD.)
CONSTANT AIR REGULATORS (CAR) "ALDES" VRF BRANCH SELECTOR MFR. (AS STD.) "MITSUBISHI ELECTRIC - TRANE"

LOW PRESSURE DIA X DIMENSIONS ELECTRICAL


CFM NOMINAL DEPTH
RANGE MODEL REMARKS MAXIMUM CAPACITY UNIT WEIGHT
MINIMUM PIPE INSULATION THICKNESS (THICKNESS IN INCHES) (PER EC403.2.10) RANGE NECK SIZE
(IN WG) (IN) UNIT TAG SERVICE LOCATION MODEL UNIT TYPE REFRIGERANT (BTU) (PER PORT)
WIDTH HEIGHT DEPTH VOLTS Ø HZ MCA
MAX (LBS)
FUSE
30-85 4"Ø 0.12-1.2 4.1"X3.0" CAR3
FLUID OPERATING INSULATION CONDUCTIVITY NOMINAL PIPE OF TUBE SIZE (INCHES)
TEMPERATURE RANGE CONDUCTIVITY MEAN RATING 86-180 5"Ø 0.12-1.2 5.2"X3.8" CAR3 BC-1 FCU-1 to FCU-8 OFFICE 20-14 TCMBM1012JA21N4 MAIN R410A 54,000 - - - 208 1 60 1.19 20 133
AND USAGE (°F) (BTU×IN/(H×FT2×°F)) TEMPERATURE, (°F) <1 1 TO < 1½ 1½ TO < 4 4 TO < 8 8≥
BC-2 FCU-9 to FCU-14 OFFICE 20-07 TCMBM0108JA11N4 MAIN R410A 54,000 - - - 208 1 60 0.83 20 108
181-260 6"Ø 0.12-1.2 6.1"X4.6" CAR3
> 350 0.32-.34 250 4.5 5.0 5.0 5.0 5.0
251-350 0.29-0.32 200 3.0 4.0 4.5 4.5 4.5 261-385 8"Ø 0.12-1.2 8.2"X6.7" CAR3 BC-3 FCU-15 to FCU-20 PHONE RM 20-28 TCMBM0108JA11N4 MAIN R410A 54,000 - - - 208 1 60 0.83 20 108

201-250 0.27-0.30 150 2.5 2.5 2.5 3.0 3.0 386-620 10"Ø 0.12-1.2 10.2"X8.3" CAR3 BC-4 FCU-21 to FCU-25 OFFICE 20-34 TCMBS0108KB21N4 SUB R410A 54,000 - - - 208 1 60 0.74 20 70
141-200 0.25-0.29 125 1.5 1.5 2.0 2.0 2.0
105-140 0.21-0.28 100 1.0 1.0 1.5 1.5 1.5 NOTES:
NOTES:

40-60 0.21-.027 75 0.5 0.5 1.0 1.0 1.0 1.


2.
PROVIDE WITH BALANCING DAMPER AT EACH FCU OA CONNECTION, BALANCE TO CFM VALUES INDICATED ON DRAWING M-100.
PROVIDE WITH DOUBLE LIP GASKET, DUCT COLLARS, ETC. 1. SELECTION BASED ON EQUIPMENT MANUFACTURED BY MITSUBISHI ELECTRIC / TRANE.
2. UNIT SHALL BE CERTIFIED, LISTED AND LABELED PER AHRI1230.
< 40 0.20-0.26 50 0.5 1.0 1.0 1.0 1.5 3.
4.
COORDINATE SUPPLY/EXHAUST ORIENTATIONS WITH EACH SYSTEM, REFER TO PLANS.
INSTALL AS PER MANUFACTURER'S INSTALLATION REQUIREMENTS WITH APPROPRIATE DUCT DIAMETER LENGTHS 3. INSTALLING CONTRACTOR MUST HAVE SUCCESSFULLY COMPLETED MANUFACTURERS CERTIFIED INSTALLATION CLASS WITHIN THE PAST 36 MONTHS.
5. UPSTREAM AND DOWNSTREAM OF THE CAR DAMPER. 4. ALL VRF EQUIPMENT SHALL BE PROVIDED WITH A 10 YEAR, PARTS ONLY WARRANTY, INCLUDING COMPRESSORS.
6. ANTI-MICROBIAL, ANTI-STATIC, AND FLAME RETARDANT. 5. PROVIDE CONDENSATE DRAIN FROM EACH BRANCH SELECTOR TO FLOOR DRAIN. REFER TO PLANS.
7. 7-YEAR WARRANTY. 6. PROVIDE SECONDARY STAINLESS STEEL DRIP PAN BELOW EACH BRANCH SELECTOR WITH LEAK DETECTOR. UPON ACTIVATION OF LEAK DETECTOR, ASSOCIATED AC/FCU, BRANCH CONTROLLER OR CONDENSING UNIT SHALL SHUT DOWN AND SOUND LOCAL AND BMS ALARM.
8. UL-2043 LISTED. 7. CONTRACTOR TO CONFIRM REFRIGERANT PIPING SIZES WITH THE MANUFACTURER BASED ON ACTUAL FIELD ROUTING OF REFRIGERANT PIPING. ROUTE AS SHOWN ON DESIGN DOCUMENTS IS SCHEMATIC AND SHALL BE VERIFIED BY THE CONTRACTOR.
9. CONTRACTOR TO FIELD VERIFY AND ADJUST TO INDICATED CFM. PROVIDE AD OR FLANGED DUCT JOIN UPSTREAM FOR SERVICE.

ENERGY RECOVERY VENTILATOR MFR. (AS STD.) "RENEWAIRE"

ELECTRICAL DATA SUMMER AIR DATA WINTER AIR DATA SUMMER/WINTER FILTER
INTAKE BLOWER EXHAUST BLOWER
UNIT LOCATION OUTDOOR AIR RETURN AIR OUTDOOR AIR RETURN AIR WEIGHT LBS. MODEL
MAX. LOAD SAVINGS RATIO TYPE
ESP IN. ESP IN. RPM VOLTS Ø HZ MCA
QTY. HP CFM RPM QTY. HP CFM FUSE D.B. W.B. D.B. W.B. D.B. W.B. D.B. W.B. (%)
H2O H2O

ERV-1 MER-20-10 1 2 2000 1 1650 1 2 1470 0.45 1200 208 3 60 16.5 20 89.7 77.0.0 75.0 62.7 12.8 10.2 72.0 56 64.3/62.6 MERV-8 712 ERV-20-30L
CP-IT AC-IT DRIP PAN 70 20 1/30 115 1 60 4.5 VCMA-P LITTLE GIANT PLENUM RATED

1 3 ISSUED FOR ADDENDUM #1 5/2/2024 JB


NOTES:
NOTES:
3 ISSUED FOR BID 4/26/2024 JB
1. UNIT SHALL BE CERTIFIED, LISTED AND LABELED PER UL AND AHRI1060.
1. PROVIDE FLOAT OPERATED HIGH WATER ALARM AND AUTOMATIC CUT-OUT SWITCH TO PREVENT RECEIVER OVERFLOW.
2. PROVIDE FACTORY EC DIRECT DRIVE FAN MOTORS FOR BOTH AIRSTREAMS.
2. OVERFLOW SWITCH SHALL SHUT DOWN AC UNIT & SOUND ALARM UPON HIGH WATER LEVEL. ALARM SHALL SOUND ON BMS. 2 ISSUED FOR DOB FILING 4/5/2024 MYS
3. PROVIDE FACTORY PREMIUM RENEWAIRE CONTROLS PACKAGE WITH BACNET FACTORY ACTIVATION FOR TIE IN TO BASE BUILDING BMS.
4. PROVIDE FACTORY NON-FUSED DISCONNECT AS STANDARD, MOUNTED ON ENCLOSURE.
5. MECHANICAL CONTRACTOR SHALL FIELD MODIFY UNIT TO REMOVE HOODS AND ADD DUCT FLANGE FOR DUCT CONNECTIONS TO ERV. 1 ISSUED FOR REVIEW 3/22/2024 MYS
6. CONTRACTOR SHALL PROVIDE 1" DEFLECTION SPRING VIBRATION ISOLATORS FOR EACH ERV UNIT.
NO. REVISION DATE BY
CEILING DIFFUSERS/RETURN GRILLES MFR. (AS STD.) "TITUS"
1
CFM NOMINAL MAX. CFM MAX S.P.
FACE SIZE MODEL REMARKS
RANGE NECK SIZE NC (IN. H20)

0-130 6"Ø 10 0.OO3 24"x24" OMNI


TPG ARCHITECTURE, LLP
131-220 8"Ø 10 0.029 24"x24" OMNI AC-IT IDF 20-26 850 36.7 25.2 80° 67° - - R-410A 208 1 1/3 1.0 - 0.8 15 15 - TGE031-36K-WALH ACCU-IT 95° 1710 0.5 1 0.75 18.8 22.1 88 13.2 35 208 3 270 13.8 TGC033-HE SEE NOTES BELOW 31 PENN PLAZA
10 132 WEST 31ST STREET, 5TH FLOOR, NEW YORK, NY 10001
221-330 10"Ø 0.038 24"x24" OMNI NOTES: 212.768.0800 | TPGARCHITECTURE.COM
1. PROVIDE WALL MOUNTED THERMOSTAT, HOT GAS BY-PASS, FLOODED CONDENSER, OIL SEPARATOR, SUCTION LINE ACCUMULATOR FIVE YEAR COMPRESSOR PARTS WARRANTY, POWER AND
431-600 12"Ø 21 0.101 24"x24" OMNI CONTROL WIRING, DISCONNECT SWITCH, HANGER RODS, VIBRATION ISOLATORS, CONDENSATE PUMP, PIPING, ADDITIONAL REFRIGERANT AND SPARE PARTS, DRIP PANS.
IN CONSIDERATION OF RECEIVING DRAWINGS FROM TPG ARCHITECTURE LLP IN
2. AC AND ACCU SHALL BE WIRED SEPARATELY
601-750 20 0.124 AN ELECTRONIC FORM, THE RECIPIENT AGREES, TO THE FULLEST EXTENT
14"Ø 24"x24" OMNI 3. CONTRACTOR TO FURNISH AND INSTALL ALL REFRIGERANT PIPING AND TRIM ACCESSORIES. PERMITTED BY LAW, TO HOLD HARMLESS AND INDEMNIFY TPG ARCHITECTURE
4. INSULATE PIPING AS REQUIRED LLP FROM AND AGAINST ALL CLAIMS, LIABILITIES, LOSSES, DAMAGES, AND
- 24"x12" - - 12"x24" 350RL GRILLE 5. PROVIDE HANGERS, VIBRATION ISOLATORS. COSTS, INCLUDING BUT NOT LIMITED TO ATTORNEY'S FEES, ARISING OUT OF,
6. PROVIDE FILTERS OR IN ANY WAY CONNECTED WITH THE USE, RE-USE, MIS-USE, MODIFICATION,
- 24"x24" - - 24"x24" 350RL GRILLE 7. CONDENSER INTAKE/DISCHARGE DUCTWORK SHALL BE INSTALLED WITH 2" RIGID INSULATION PER DESIGN SPECIFICATIONS OR MISINTERPRETATION OF THE MACHINE-READABLE INFORMATION PROVIDED
8. ROUTE 3/4" CONDENSATE PIPING TO FUNNEL DRAIN IN RESTROOM. SEE PLUMBING DRAWINGS FOR LOCATION. BY TPG ARCHITECTURE LLP UNDER THIS AGREEMENT.
S:\CAD\1359 BWAY\20FL_PROGYNY_DEMO BUILDOUT_23043.08\03-DWGS\M-400, 401.DWG / Plot Date: May, 2, 2024 - 4:47 :PM

PROJECT
NOTES:

1. COORDINATE EXACT LOCATION WITH ARCHITECTS DRAWINGS. EXHAUST FANS MFR. (AS STD.) GREENHECK PROGYNY
2. PROVIDE DIFFUSERS WITH EQUALIZING GRID AND OPPOSED BLADE DAMPERS FAN DATA MOTOR DATA 2ND AND 20TH FLOOR
3. PROVIDE IN LAY-IN CEILINGS WITH TYPE 3 FRAME.
4. FOR 2-WAY OR 3-WAY BLOW, BLANK OFF NEXT (NECK TO BE NEXT SIZE. UNIT No. SERVICE LOCATION
CFM
S.P.
IN. RPM TYPE SIZE FLA HP DRIVE
ELECTRICAL DATA WEIGHT MODEL REMARKS 1359 BROADWAY
5. ALL SUPPLY REGISTERS SHALL BE DOUBLE DEFLECTING TYPE, FRONT BLADES VERTICAL AS MANUFACTURED BY "TITUS",
MODEL 300RS.
W.G. VOLTS PH. HZ
NEW YORK, NY 10018
6. PROVIDE TITUS "LIGHTSHIELD" FOR ALL CEILING RETURN GRILLES. TX-1 MEN'S & ADA RESTROOMSMEN'S 300 0.2 1103 INLINE 390 1.5 1/10 DIRECT 115 1 60 24 CSP-A390-VG -
RESTROOM
7. PROVIDE CORD OPERATED DAMPERS WHERE GRILLES ARE INSTALLED IN INACCESSIBLE CEILINGS. DRAWING
8. ALL ROUND DIFFUSERS SHALL BE TITUS MODEL TMRA. TX-2 WOMEN'S RESTROOM WOMEN'S 230 0.2 949 INLINE 390 1.5 1/10 DIRECT 115 1 60 24 CSP-A390-VG -
RESTROOM
NOTES:
MECHANICAL
2. PROVIDE ISOLATION KIT, HANGERS, & SUPPORTS.
SCHEDULES
3. PROVIDE FLEXIBLE CONNECTIONS. (1 OF 2)
4. PROVIDE DISCONNECT SWITCHES.
5. PROVIDE UNIT MOUNTED SPEED CONTROLLERS.
6. PROVIDE BMS TIMECLOCK CONTROLS.
SEAL DATE
1.29.24
PROJECT NO.
11523048-00
Last Saved By: CHIRST / Save Date: 5/2/2024 2:01:24 PM

SCALE
AS SHOWN
CAD FILE NO. DOB PAGE
9 of 13
DWG NO.

NYC DOB NO.


M-400.00

You might also like