Zone CFM ..................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................. Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 7,9 Tons Load occurs at .................................................. Feb 1600
Total coil load ...................................................... 94,2 MBH OA DB / WB .................................................... 91,6 / 75,9 °F
Sensible coil load ................................................ 68,6 MBH Entering DB / WB ............................................ 79,7 / 66,5 °F
Coil CFM at Feb 1600 ........................................ 2651 CFM Leaving DB / WB ............................................. 55,8 / 54,6 °F
Max block CFM .................................................. 2651 CFM Coil ADP .................................................................... 53,1 °F
Sum of peak zone CFM ..................................... 2651 CFM Bypass Factor ......................................................... 0,100
Sensible heat ratio ............................................ 0,728 Resulting RH ................................................................ 49 %
ft²/Ton ................................................................ 120,3 Design supply temp. .................................................. 55,0 °F
BTU/(hr-ft²) ......................................................... 99,7 Zone T-stat Check .................................................. 1 of 1 OK
Water flow @ 10,0 °F rise .................................... N/A Max zone temperature deviation ................................. 0,0 °F
Actual max CFM ................................................ 2651 CFM Fan motor BHP ......................................................... 0,00 BHP
Standard CFM ................................................... 2648 CFM Fan motor kW ........................................................... 0,00 kW
Actual max CFM/ft² ............................................. 2,80 CFM/ft² Fan static .................................................................. 0,00 in wg
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 1,079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4741,6 BTU/(hr-CFM)
Site Altitude = 29,0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 1,079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4741,6 BTU/(hr-CFM)
Site Altitude = 29,0 ft
2
0,012
5 0,010
34
0,008
0,006
0,004
0,002
0,000
30 40 50 60 70 80 90 100
Temperature ( °F )