Air System Sizing Summary for Default System

Project Name: Untitled 01/24/2023


Prepared by: WORKSYSTEM 11:38p. m.

Air System Information


Air System Name ............................. Default System Number of zones ............................................................ 1
Equipment Class ...................................... SPLT AHU Floor Area ............................................................... 945,0 ft²
Air System Type ............................................. SZCAV Location .......................................... Guayaquil, Ecuador

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ..................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................. Individual peak space loads Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 7,9 Tons Load occurs at .................................................. Feb 1600
Total coil load ...................................................... 94,2 MBH OA DB / WB .................................................... 91,6 / 75,9 °F
Sensible coil load ................................................ 68,6 MBH Entering DB / WB ............................................ 79,7 / 66,5 °F
Coil CFM at Feb 1600 ........................................ 2651 CFM Leaving DB / WB ............................................. 55,8 / 54,6 °F
Max block CFM .................................................. 2651 CFM Coil ADP .................................................................... 53,1 °F
Sum of peak zone CFM ..................................... 2651 CFM Bypass Factor ......................................................... 0,100
Sensible heat ratio ............................................ 0,728 Resulting RH ................................................................ 49 %
ft²/Ton ................................................................ 120,3 Design supply temp. .................................................. 55,0 °F
BTU/(hr-ft²) ......................................................... 99,7 Zone T-stat Check .................................................. 1 of 1 OK
Water flow @ 10,0 °F rise .................................... N/A Max zone temperature deviation ................................. 0,0 °F

Supply Fan Sizing Data

Actual max CFM ................................................ 2651 CFM Fan motor BHP ......................................................... 0,00 BHP
Standard CFM ................................................... 2648 CFM Fan motor kW ........................................................... 0,00 kW
Actual max CFM/ft² ............................................. 2,80 CFM/ft² Fan static .................................................................. 0,00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 613 CFM CFM/person ............................................................ 24,54 CFM/person
CFM/ft² ................................................................ 0,65 CFM/ft²

Hourly Analysis Program v4.70 Page 1 of 7


Zone Sizing Summary for Default System
Project Name: Untitled 01/24/2023
Prepared by: WORKSYSTEM 11:38p. m.

Air System Information


Air System Name ............................. Default System Number of zones ............................................................ 1
Equipment Class ...................................... SPLT AHU Floor Area ............................................................... 945,0 ft²
Air System Type ............................................. SZCAV Location .......................................... Guayaquil, Ecuador
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ..................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................. Individual peak space loads Sizing Data ..................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft²) CFM/ft²
Zone 1 57,2 2651 2651 Feb 1600 0,9 945,0 2,80

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
SPA 1 57,2 Feb 1600 2651 0,9 945,0 2,80

Hourly Analysis Program v4.70 Page 2 of 7


Air System Design Load Summary for Default System
Project Name: Untitled 01/24/2023
Prepared by: WORKSYSTEM 11:38p. m.

Hourly Analysis Program v4.70 Page 3 of 7


Air System Design Load Summary for Default System
Project Name: Untitled 01/24/2023
Prepared by: WORKSYSTEM 11:38p. m.

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91,6 °F / 75,9 °F HEATING OA DB / WB 67,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 201 ft² 15382 - 201 ft² - -
Wall Transmission 235 ft² 3250 - 235 ft² 319 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 201 ft² 2408 - 201 ft² 498 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 33 ft² 2964 - 33 ft² 57 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 1000 W 3140 - 0 0 -
Task Lighting 1000 W 3140 - 0 0 -
Electric Equipment 5000 W 15967 - 0 0 -
People 25 5744 6750 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5199 675 0% 0 0
>> Total Zone Loads - 57193 7425 - 874 0
Zone Conditioning - 58383 7425 - 8 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2651 CFM 0 - 2651 CFM 0 -
Ventilation Load 613 CFM 10207 18218 613 CFM 117 0
Supply Fan Load 2651 CFM 0 - 2651 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 68589 25643 - 125 0
Central Cooling Coil - 68589 25644 - 0 0
>> Total Conditioning - 68589 25644 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.70 Page 4 of 7


System Psychrometrics for Default System
Project Name: Untitled 01/24/2023
Prepared by: WORKSYSTEM 11:38p. m.

February DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 91,6 0,01565 613 400 10207 18218
Vent - Return Mixing Outlet 79,7 0,01084 2651 832 - -
Central Cooling Coil Outlet 55,8 0,00880 2651 832 68589 25644
Supply Fan Outlet 55,8 0,00880 2651 832 0 -
Cold Supply Duct Outlet 55,8 0,00880 2651 832 - -
Zone Air - 76,2 0,00939 2651 963 58383 7425
Return Plenum Outlet 76,2 0,00939 2651 963 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 1,079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4741,6 BTU/(hr-CFM)
Site Altitude = 29,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 57193 Cooling 58383 76,2 2651 963 0 0

Hourly Analysis Program v4.70 Page 5 of 7


System Psychrometrics for Default System
Project Name: Untitled 01/24/2023
Prepared by: WORKSYSTEM 11:38p. m.

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 67,0 0,00703 613 400 -117 0
Vent - Return Mixing Outlet 67,1 0,00703 2651 429 - -
Central Cooling Coil Outlet 67,1 0,00703 2651 429 0 0
Supply Fan Outlet 67,1 0,00703 2651 429 0 -
Cold Supply Duct Outlet 67,2 0,00703 2651 429 - -
Zone Air - 67,2 0,00703 2651 437 -8 0
Return Plenum Outlet 67,2 0,00703 2651 437 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 1,079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4741,6 BTU/(hr-CFM)
Site Altitude = 29,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -874 Deadband -8 67,2 2651 437 0 0

Hourly Analysis Program v4.70 Page 6 of 7


Psychrometric Analysis for Default System
Project Name: Untitled 01/24/2023
Prepared by: WORKSYSTEM 11:38p. m.

Location: Guayaquil, Ecuador


Altitude: 29,0 ft.
Data for: February DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air
1
0,016

Specific Humidity ( lb/lb )


0,014

2
0,012

5 0,010
34

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program v4.70 Page 7 of 7