Water supply pump calculation for ANAND Vihar Station (Hydropneumatic pump)

Qty. of As per NBC TABLE-2 TOTAL LPM


Sr. No fixtures as (Clause 4.7.3.1) Total Fixture Units (AS PER NBC TABLE -2 ,3
Descriptions
per drg. in Water Supply Fixture for water supply & CLAUSE NO. 4.7.3.1 &
nos. Units / Fixures 4.7.3.2)

1 Bidet/Spray 9 1 9

2 Wash Basins 12 1.5 18

3 Fountains / Tap 15 0.75 11.25

4 hose bib 13 2.5 32.5

5 Ancillary building tap 3 0.75 2.25

6 WC 9 3 27

7 Urinal 5 2 10

TOTAL FIXTURE UNIT 110 175.02 (lpm)

192.53 LPM
FOR SAFE DESIGN CONSIDERATION TAKE 10% EXTRA FOR FACTOR OF SAFETY SAY
195 LPM

Therefore we have considered two pump (1 W +1 ST) each of 195 lpm