Professional Documents
Culture Documents
Nameplate Details of SF6 Circuit Breaker - Explained - TheElectricalGuy
Nameplate Details of SF6 Circuit Breaker - Explained - TheElectricalGuy
In this tutorial, we are going to understand the parameters which are mentioned on nameplate of a
SF6 circuit breaker. These parameters are common for all high & extra high voltage class SF6 circuit
breakers. So, let’s start.
In most of the countries high & extra high voltage circuit breakers are manufactured based on the
IEC standard, i.e. IEC 62271-100. Parameters mentioned on the nameplate of circuit breaker are
also in line with the IEC 62271-100.
As per IEC, few parameters are mandatory, some are condition based, and some of them are
completely optional. In this tutorial, we’ll look at the all these parameters mentioned on nameplate
of SF6 circuit breaker.
Mandatory Parameters
Optional Parameters
Mandatory Parameters
As the name suggest, these parameters are mandatory. All the manufacturer producing circuit
breakers must mention these parameters on the nameplate of SF6 circuit breaker. But of course,
some of these parameters may be skipped, if it is mutually agreed between manufacturer and
customer.
Rated voltage
Rated voltage is the “Highest system voltage” for which breaker is designed. This voltage is
mentioned in kV rms [https://www.theelectricalguy.in/tutorials/what-is-rms-value-easiest-
explanation/] and refers to phase to phase voltage of 3 phase system
[https://www.theelectricalguy.in/tutorials/three-phase-balanced-vs-unbalanced-system-load/] .
Most of the time people gets confused between rated voltage and normal voltage. Rated voltage is
the highest voltage of a system for which the system is designed. Whereas, normal voltage is the
voltage which will remain in the system normally. So, in this case, 420kV is the rated voltage and
400kV is normal voltage. Similarly, for 245kV voltage level, rated voltage is 245kV and the normal
voltage is 220kV. For 145kV, rated voltage is 145kv and normal voltage is 132kV.
Unit : kV RMS
Rated frequency
It is the power frequency on which electricity is generated, transmitted and distributed. In some
countries it is 50Hz and in some it is 60Hz.
Unit : Hz
Unit : Ampere
400 A
630 A
800 A
1250 A
1600 A
2000 A
3150 A
4000 A
On some nameplates, you’ll find that short circuit current is given as symmetrical and asymmetrical
current. The difference is that, Symmetrical current is the AC component of short circuit current
which is equal to rated short circuit current. Whereas, asymmetrical current is the combination of
AC and DC components of short circuit current.
So, you can see above, asymmetrical current is greater than the symmetrical.
Unit : kA RMS
Unit : Seconds
forces caused by this current. This current is called as “short circuit making current”. Or it is also
called as rated peak withstand current.
It is generally 2.5 times the rated short circuit current. It is referred in kA peak, as it remain for very
short time.
Unit : kA Peak
And hence, breaker shall withstand power frequency voltage caused by these reasons. IEC has
defined the level of power frequency voltage that can appear across breaker contact. So, for
example, for 420kV CB the power frequency voltage defined by IEC is 610kV rms. Circuit breaker
has to undergo power frequency withstand test, in which power frequency voltage is applied to the
circuit breaker for 1 min.
Unit : kV RMS
Unit : kV Peak
So, on the nameplate you’ll find it is mentioned as 1.3 (or 1.5). This means, first pole to open will have
1.3 times the normal system voltage across it, and the pole can sustain that.
Unit : N/A
This is one of the important parameter of the breaker, it is also known as “Auto reclosing duty”.
Operating sequence denotes the opening & closing operation breaker is capable of performing
under specified conditions.
As per IEC 62271-1 there are two alternatives for operating sequence,
O – t – CO – t’ – CO
CO – t’’ – CO
where,
O = Opening operation
C = closing operation
t,t’,t’’ = time intervals between successive operations
Let me tell you how auto reclosing works. 90% of the faults (like ) on the system are transient in
nature. Which remain in the system for a very short time and then the system goes back to normal.
In such cases, it is beneficial to put the system live again, and here the auto reclosing system comes
into picture.
We’ll consider the auto reclosing duty which is mentioned on our nameplate [#nameplate] i.e. O-0.3
SEC-CO-3 MIN-CO. So, let’s say there is fault on the system the breaker will open then it will remain
open for 0.3 sec. After 0.3 sec, it will close and if the fault is cleared it will remain close. But, if the
fault is still there then the breaker will open immediately. Now breaker will remain in open condition
for 3 mins. After 3 mins the breaker will close again, and if the fault is cleared it will remain close. But
if, the fault is still there then the breaker will open immediately, and now breaker will remain open
until it is closed manually.
Unit : N/A
Unit : kg
Total weight of CB
This shows the total weight of SF6 gas in the breaker. Again, this will vary manufacturer to
manufacturer.
Unit : kg
Unit : Volts
These were the mandatory parameters as per IEC. These parameters you’ll generally find on every
nameplate [#nameplate] of high & extra high voltage SF6 circuit breaker.
Go To Top [#nameplate]
Now, let’s see condition based parameters. These parameters depends upon some specific
condition, which is also given below. If that condition is satisfied, then these parameters has to be on
nameplate of SF6 circuit breaker.
Switching surges are generally occurs above 245kV voltage level. And hence you’ll only find this
parameter on the circuit breaker above 245kV level.
It becomes important to test the breaker above 245kV voltage level for switching surges. Switching
surges are generally caused by energisation of lines or switching of transformers, etc. For 420kV
voltage level, switching voltage is specified as 1050kV peak.
Unit : kV Peak
DC component is a DC component of short circuit current. And if it is more than 20% at the time of
contact separation of CB, then it has to be on name plate.
Unit : %
This is the highest amount of line charging current a circuit breaker is capable of breaking. This type
of current is generated because of the switching of loaded or unloaded overhead lines. So, for 420kV
CB IEC has defined the rating equal to 600A.
Unit : Ampere
Classification
Condition : If class in not E1 & M1
If circuit breakers mechanical endurance class and electrical endurance class is different from M1
and E1, then it has to be on nameplate. Let me tell you what is mechanical endurance class and
electrical endurance class.
Please note, E2 class is applicable only for distribution circuit breaker below 52kV. E2 class is not
applicable for breakers above 52kV, this is in line with IEC.
So, this was about the condition based parameters. Now let’s look at the optional parameters.
Go To Top [#nameplate]
Optional Parameters
These parameters are completely optional as per the IEC standard. And hence, it can be or cannot be
on the nameplate, depends upon the manufacturer.
Unit : kV
Unit : Ampere
Unit : Ampere
a high possibility that the arc will restirke. So, if the breaker is made for back to back capacitor bank
switching, then you’ll find this parameter on the nameplate of SF6 circuit breaker.
Unit : Ampere
So, these are the optional parameters you can find on the name plate of HV or EHV circuit breaker.
Go To Top [#nameplate]