House Floor Plans 3
House Floor Plans 3
House Floor Plans 3
Olympia, WA 98512-6292
13'-10 1/8" 8'-3" 5'-9"
(360) 754-7711
TOTAL SQUARE
FEET: 32
ELECT.
PANEL HB 6 9
2
10"X10" VENT
EGRESS
MAKEUP AIR
ICE
3'-3"
DW MKR
2X6
4'-6 1/2"
REF
2X6
4'-3"
7'-3 3/4"
8'-4 3/4"
10'-0"
11'-8 3/4"
11'-6 3/4"
11'-1" 2'-0 1/2" 2'-0 1/2" 3'-4 1/2"
2'-6"
13'-3 3/4"
3'-11 1/2" 3'-2 3/4"
2X6
13'-5"
BATHROOM 2 STORAGE
BEDROOM 2
16'-3 3/8"
50
F
CFM BATHROOM
2'-10 1/2" 14
PANTRY
LAUNDRY
3'-7"
STOR
4
7
KITCHEN
3'-4"
22X30
15
3
13
ALL SMOKE/CO DETECTORS MAX. RISE 7 3/4"
3'-4 1/2"
3'-4 1/2"
W D 16
LINKED W/ BATTERY BACKUP MIN. RUN 10"
2x6
2x6
S/P
6
VENT
12
6'-9"
6'-9"
3'-6 1/2" LIN
3'-4"
3 S/P
3'-4 1/2"
3'-4 1/2"
8" 1 1
HAND RAIL S/P
STATUS: Preliminary
A302 A302
HAND 5
11
RAIL
2'-4 1/2"
2'-4 1/2"
2'-4 1/2"
914 SQUARE FEET S/P 17 S/P
1ST FLOOR
10'-4 1/8"
4
9 8 18
LIVING ROOM 3'-11 1/2" 4'-11 1/2" 3'-11"
15'-1"
BEDROOM 3
3 BEDROOM 1 BEDROOM 4
HOUSE
EGRESS EGRESS EGRESS
1
PROJECT:
1 1 8 8
HB
TOTAL SQUARE
FEET: 84
REVISIONS
# DESCRIPTION DATE
13'-10" 14'-2"
15'-2" 12'-10"
28'-4 1/8"
28'-0"
SHEET SCALE:
4
A302 1/4" = 1'-0"
6/18/2013 11:18:47 AM
2'-0"
2'-0"
PORCH ROOF 2'-0" GABLE AND EVE OVERHANG TYP.
OPEN SOFFIT
4'-0"
MANUFACTURED TRUSSES @ 24" O.C. TYP.
2'-0"
Olympia, WA 98512-6292
2011 Mottman Road SW
32'-0"
32'-0"
36'-0"
36'-0"
36'-0"
CONTINUOUS RIDGE VENT TYP.
42'-0"
STATUS: Preliminary
37th Ave SE Lacey Wa 98503
2'-0"
2'-0"
HOUSE
PROJECT:
4'-3 3/4" 13'-8 1/2" 9'-11 3/4" 13'-8 1/2"
32'-0" 32'-0"
REVISIONS
# DESCRIPTION DATE
SHEET SCALE:
1/4" = 1'-0"
6/18/2013 11:18:48 AM
SHEET TITLE:
ROOF PLANS
12
6
GUTTERS AT ALL HORIZONTAL FASCIAS.
5'-0"
5/4X4 PRIMED SPRUCE
CORNER BATTS AND WINDOW WRAP TYP. F.F.L. 2nd FLR F.F.L. 2nd FLR
9'-1 3/4" 9'-1 3/4"
LIGHT T.O.W. 1st FLR
T.O.W. 1st FLR
8'-1 1/8"
8'-1 1/8"
"HARDIE PLANK" SIDING W/ 6" REVEAL
COMMUNITY COLLEGE
Olympia, WA 98512-6292
2011 Mottman Road SW
1 FRONT 2 RIGHT
A201 1/4" = 1'-0" A201 1/4" = 1'-0"
STATUS: Preliminary
37th Ave SE Lacey Wa 98503
T.O.W. 2nd FLR T.O.W. 2nd FLR
14'-1 3/4" 14'-1 3/4"
HOUSE
8'-1 1/8" 8'-1 1/8"
PROJECT:
H.B.
GFCI
F.F.L. 1st FLR F.F.L. 1st FLR REVISIONS
0" 0" # DESCRIPTION DATE
SHEET TITLE:
ELEVATIONS
ELEVATIONS A201
4X8 BEAM
SCREENED
VENTING 1" CLEARANCE
GALVANIZED METAL "Z" FLASHING
F.F.L. 1st FLR
5/4 PRIMED 0"
SPRUCE FASCIA
COMMUNITY COLLEGE
EACH TRUSS
2X6 P.T. SILL PLATE
Olympia, WA 98512-6292
2011 Mottman Road SW
STAIRS: 5/4 RADIUS CEDAR DECKING
MAX RISE 7 3/4"
(360) 754-7711
TYPICAL EXTERIOR WALLS: F.F.L. 1st FLR
"HARDIE PLANK" SIDING W/6" REVEAL 0"
R-6 1" RIGID FOAM INSULATION
APPROVED BUILDING WRAP
7/16" O.S.B. SHEATHING O.A.E. R-21 BATT INSULATION 2X8 P.T. JOISTS @16" O.C.
2X6 STUDS @ 16" O.C.
R-21 WALL INSULATION
1/2" GYPSUM WALL BOARD
R-38 BATT INSULATION
LEDGER W/ FLASHING AND
4X8 P.T. BEAM ATTACHMENT
12
6
PREFAB SCISSOR TRUSSES @
24" O.C.
LOW "E" INSULATED GLAZING (SEE ROOF FRAMING)
STATUS: Preliminary
37th Ave SE Lacey Wa 98503
T.O.W. 2nd FLR
2X6 SILL PLATE 14'-1 3/4"
5/4 PRIMED SPRUCE
R-5 RIDGID
TYP. EXT. TRIM
FOAM
5'-0"
1'-0 5/8"
MIN. RUN 10"
HOUSE
9'-1 3/4"
11-7/8" ENGINEERED I-JOIST @ 16" O.C. NOSING 3/4 TO 1-1/4
T.O.W. 1st FLR
PROJECT:
8'-1 1/8"
JOIST HANGER
2X6 P.T. SILL PLATE
DOUBLE RIM
3-1/8" X 8" PARALAM JOISTS
FILTER FABRIC PER CODE
4" PVC DRAIN PIPE SLOPED
TO DRYWELL
8'-1 1/8"
2
.006 BLACK POLY VAPOR BARRIER REVISIONS
A302
# DESCRIPTION DATE
2 WALL SECTION
A302 3/4" = 1'-0"
F.F.L. 1st FLR
0"
SHEET SCALE:
.006 BLACK POLY VAPOR BARRIER CRAWL SPACE
As indicated
6/18/2013 11:18:51 AM
SHEET TITLE:
BUILDING
1 BUILDING SECTION SECTIONS
A302 3/8" = 1'-0"
Olympia, WA 98501
ALM Alarm FF Finish face
COMMUNITY COLLEGE
BEV Bevel GALV STL Galvanized steel SC Solid core 12. EGRESS WINDOWS:
Olympia, WA 98512-6292
BI FLD DR Bifolding doors
(360) 754-7711
finished sill height below adjacent ground elevation shall have a window well which shall comply with the
BLT IN Built-in GYM Gymnasium SGD Sliding glass door following: Net operable area of 9 square feet, a minimum dimension of 36” and when vertical depth is
BLVD Boulevard GWB Gypsum wall board SH Single hung (window) greater than 44” an approved affixed ladder or stairs shall be provided.
BLW Below SHR Shower
BM Beam
H
HB SHTHG Sheathing
Hose bib
HC Hollow core SHV Shelving 13. SMOKE DETECTORS AND CARBON MONOXIDE ALARMS: LIVING AREA SQ. FOOTAGE
BOT
BP
Bottom
HCP Handicapped
SLD WDW Horizontal sliding window A Smoke Detector shall be installed in each sleeping area and in the corridor leading to them. DECK SQUARE FOOTAGE
BR
Building Paper
Bedroom
HD Heavy duty
SND
SPEC
Sanitary napkin dispenser
Specification
Detectors shall be hard wired, installed on each floor level, and shall have a battery back-up feature. LEVEL AREA
BRCG Bracing
HDR Header The Carbon Monoxide alarm shall be installed on each floor and in the corridor serving the sleeping F.F.L. 1st FLR 846 SF FRONT PORCH: 84 SQUARE FEET
HDWD SQ Square
Hardwood areas.
BRDG Bridging SQ IN Square inch F.F.L. 2nd FLR 842 SF
HF Hemlock fir 14. STAIR DESIGN CRITERIA: REAR PORCH: 32 SQUARE FEET
BRG Bearing SQ YD Square yard
HGR Hanger 7-3/4” maximum rise / 10” minimum run. Minimum head room shall be 6’-8”. Place handrails 34” –
BSMT Basement ST Street
HLDN Holdown 38” above tread nosing. Guard rails minimum 36” high with intermediate members installed not more
BT Bathtub STD Standard
HNDRL Handrail than 4” apart. Minimum size of stair nosing shall be ¾” with a maximum of 1-3/4”.
BTR Better STOR Storage
HORIZ Horizontal
Btu
BTWN
British thermal unit
Between
HT Height
STRUCT
SUB FL
Structural
Subfloor
15. SAFETY GLAZING:
All glazing in I.R.C. deemed hazardous Ares must be safety glazing including: All ingress and egress SYMBOL LEGEND
HVY Heavy
SURF Surface door glazing, any sliding door assemblies and panels (exclude wardrobe doors). Tub/shower
C HW Hot water
SUSP Suspended enclosures and any glazing in walls within 60” of standing area, Glazing in any opening adjacent to a door
C TO C
CAB
Center to center
Cabinet
HWY Highway
SWR Sewer within 12” where the bottom is less than 60” above the walking surface, All glazing less than 18” Sheet List
I SIM 101 1t
SYM Symbol above the floor, All glazing in stairwell landings and railings.
CANTIL
CAP
Cantilever
Capacity
ID Identification
T 16. EXHAUST FAN DESIGN CRITERA:
1
1 Ref DOOR TAGS WINDOW TAG
Sheet Number Sheet Name
INSTL Install The point of discharge of exhaust air shall be at least 3’-0” from any building opening. Exhaust fans are A101
G001 COVER SHEET
CD Construction Documents T&G Tongue and groove
Ref
Ref
INT Interior required in each kitchen bathroom, water closets, laundry facility and any other areas where excess
CEM Cement T/S Tub/shower BUILDING SECTION A101 FLOOR PLANS
IRC International Residential Code water vapor or cooking odor is produced. Each dwelling shall be equipped with a whole house fan 1 A101 1
CHK Check TB Towel bar A106 ROOF PLANS
CJ Control joint J TD Towel dispenser that provides a continuous exhaust of 1 sone or less, 45 cfm for 2-3 bedrooms or 60 cfm for a 4 NAME
A201 ELEVATIONS
CL Center line JAL Jalousie TEL Telephone bedroom house. A label is to best installed at the location of the whole house fan switch that states: SIM 1 Ref ELEVATION
1 A302 BUILDING SECTIONS
CLG Ceiling J-BOX Junction box TEMP Temporary “Whole House Fan”. S101 FOUNDATION PLAN
17. WATER CLOSET DESIGN CRITERA: A101 INTERIOR ELEVATION
CLO Closet K TFF Top of finished floor S102 FLOOR FRAMING PLAN
CLR Color K Thousand THK Thickness Water closets shall be installed in a clear space of no less than 30” in width and the clear space in
S105 LATERAL PLAN
CMPTR Computer KD Kiln dried TO FND Top of foundation front of the toilet shall not be less than 24”. WALL SECTION LEVEL WITH ELEVATION
CMU Concrete masonry unit KIT Kitchen TOC Top of concrete 18. WATER HEATERS:
CNR Corner KO Knockout TOPO Topography Water heaters shall be anchored or strapped to resist horizontal displacement due to earth quake
CNTR Counter TOS Top of slab motion. Temperature and pressure relief valves shall be drained to the exterior of the building. All
L TOW Top of wall electric water heaters shall be placed in a metal pan when installed over wood framing and if installed
COL Column L CL Linen closet TPD Toilet paper dispenser in an unheated space or on a concrete floor on an R-10 insulated pad.
CONC Concrete LAM Laminate TRANS Transom 19. ATTIC ACCESS:
CONC FLR Concrete floor LATL Lateral TV Television Attics with a minimum vertical height of 30” must be provided with an access of not less than 22” X
CONSTR Construction
STATUS: Preliminary
LAV Lavatory TYP Typical
CONT Continue 30”. If an access is provided it must be installed with a curb of not less than 12”.
LBR Lumber
CR Closet rod LC Laundry chute U
CSMT Casement LD BRG Load-bearing UBC Uniform Building Code
CSWK Casework LF Linear feet UFC Uniform Fire Code ENERGY CODE NOTES
HOUSE
MW Microwave
DIM W/O Without
Dimension
DIST Distance
N WC Water closet
PROJECT:
N North WD Wood
DJ Double joist NO Number WDW Window
DL Dead load NTS Not to scale WH Water heater
DF Douglas fir WL
O Water line
DR Door WP
OC On center Weatherproof
DS Down spout WSCT
OH Overhang Wainscot
DW Dishwasher WT Weight
OPT Optional
DWG Drawing WTR Water
OUT Outlet
DX OUT Duplex outlet WWF Wire welded fabric
P REVISIONS
E X # DATE
PERIM Perimeter DESCRIPTION
E East
PL Property line XL Extra large
EA Each
PLYWD Plywood
EH Electric heater Y
PREFAB Prefabrication YD
EJ Expansion joint Yard
PRELIM Preliminary YR
ELEC Electric Year
PRKG Parking
ENGR Engineer PT Pressure treated Z
EOS Edge of slab PTD Paper towel dispenser N/A N/A
EQ Equal PVC Polyvinyl chloride (plastic)
SHEET SCALE:
As indicated
6/18/2013 11:18:53 AM
SHEET TITLE:
COVER SHEET
6'-9"
BUILDING OFFICIAL MAY DETERMINE THE IN PLACE SOILS MAY HAVE LESS CAPACITY THAN 1500 PSF SLAB
AND MAY REQUIRE BEARING CAPACITY TO BE DETERMINED BY A SOILS INVESTIGATION.
BLOCKING
2. FOR ALL BUILDINGS, PLATE WASHERS A MINIMUM OF 1/4" x 3" x 3" IN SIZE SHALL BE PROVIDED
BETWEEN THE FOUNDATION SILL PLATE AND THE NUT.
3. ALL FOUNDATION POST COLUMNS REQUIRE A POSITIVE CONNECTION AT THE BOTTOM END TO PREVENT
2X6 DBL. TOP PLATE
LATERAL DISPLACEMENT.
4. EXCEPT FOUNDATION WALLS SUPPORTING LESS THAN 4'-0" OF UNBALANCED BACKFILL, THE BACKFILL
3'-10 1/4"
SHALL NOT BE PLACED AGAINST THE FOUNDATION WALL UNTIL IT HAS CURED FOR 14 DAYS. 6'-0" 3'-0" 5'-10 3/4" 6'-0" 5'-4 3/4"
5. THE GRADE AWAY FROM THE FOUNDATION WALLS SHALL FALL A MINIMUM OF 6 INCHES WITHIN THE 2X6 PONY WALL CONT.
2'-1 1/2"
FIRST 10 FEET. W/ NO SHEATHING
4'-0"
10 1/4" 10 1/4"
COMMUNITY COLLEGE
3'-0 1/4"
Olympia, WA 98512-6292
9. ANY DETAIL SHOWING A "SIMPSON" CONNECTOR MAY HAVE THE CONNECTOR REPLACED WITH ANOTHER CONTINUOUS RIBBON
www.spscc.ctc.edu
36" X 24" COVERED CRAWL ACCESS
FOUNDATION SCREENED VENTS AND ACCESS WELLS. .006 BLACK POLY 2X6 PONY WALL
(360) 754-7711
11. MINIMUM FOOTING DEPTHS VAPOR BARRIER DBL. TOP PLATE
ONE-STORY: 12" BELOW UNDISTURBED SOIL
7"
P.T. SOLE PLATE
4'-6 1/4"
TWO-STORY: 18" BELOW UNDISTURBED SOIL
NOTE:
6X6 POSTS @
FOUNDATION VENTS 2/150
1'-3" POINT LOADS
S.F. PER CODE
3'-5"
900 S.F./150=6(2)=12 VENTS
7'-9 1/4"
32'-0"
32'-0"
.006 BLACK POLY VAPOR BARRIER
13'-3 1/4"
FLOOR SYSTEM
2X6 P.T. CONTINUOUS MIN. 1/2" A.B. @ 6'-0" O.C. 11-7/8" RIM BOARD FLOOR JOISTS
SILL PLATE W/7" EMBEDMENT PER PLAN
STATUS: Preliminary
- (2) A.B. PER PLATE SECTION 2X6 P.T. SILL PLATE
-4-1/2" FROM END OF PLATE
-3"X3"-1/4" PLATE WASHER
MAINTAIN 1/2" AIRSPACE
ALTERNATE:
BETWEEN PONY WALL AND CONCRETE.
MFR'D MUDSILL ANCHORS
5'-10 1/4"
2X6 PONY WALL CONT. W/
5'-10 1/4"
WITHIN THE TOP 12" NO SHEATHING
6'-0"
1'-1"
#4 @ 48" O.C.
4" STD. HOOK 2X6 P.T. SOLE PLATE 4'-3 3/4" 6'-0 1/4" 6'-0" 1'-8 1/4" 9'-11 3/4"
W/ POSITIVE CONNECTION
IN FOOTING
3"
HOUSE
6'-6"
PROJECT:
28'-0"
REVISIONS
# DESCRIPTION DATE
2 TYPICAL FOUNDATION - RIM JOIST 3 BEAM CONNECTION AT FOUNDATION 1 FOUNDATION PLAN
S101 1" = 1'-0" S101 1" = 1'-0" S101 1/4" = 1'-0"
SHEET SCALE:
As indicated
6/18/2013 11:18:54 AM
SHEET TITLE:
FOUNDATION PLAN
4'-0"
NOTE: RIM BOARD REQUIRED UNDER SECOND FLOOR WALLS
@ PORCH CONNECTIONS
COMMUNITY COLLEGE
Olympia, WA 98512-6292
11-7/8" ENGINEERED I-JOIST @ 16" O.C. 11-7/8" ENGINEERED I-JOIST @16" O.C. TYP.
(360) 754-7711
2X8 LEDGER W/ TYP. FLASHING HANGER ALL JOIST-LEDGER CONNECTIONS TYP.
(SEE PORCH SECTION VIEW)
15'-10 1/4"
5/4 RADIUS CEDAR DECKING TYP.
STAGGERED BLOCKING @ GIRDER BEAM TYP.
2X8 P.T. JOISTS @ 16" O.C. TYP.
6'-5 1/2"
DOUBLE AND HANGER @ INTERRUPTED HANGING JOISTS
32'-0"
32'-0"
32'-0"
32'-0"
11-7/8" RIM BOARD DOUBLE JOISTS BELOW LATERAL PANELS TYP. 11-7/8" RIM BOARD
4X8 P.T. BEAM SUPPORTING DECK UNDER SECOND FLOOR WALLS
16'-1 3/4"
FACE-MOUNT HANGER TYP.
STAGGERED BLOCKING @ BEARING WALL TYP.
13'-6 1/4"
4X4 POST STEPS
STATUS: Preliminary
37th Ave SE Lacey Wa 98503
NOTE: RIM BOARD REQUIRED
@ PORCH CONNECTIONS
6'-0"
28'-0"
HOUSE
PROJECT:
6'-8" 5'-0" 2'-4"
28'-0"
REVISIONS
# DESCRIPTION DATE
3 PORCH FRAMING PLAN - FRONT 1 FLOOR FRAMING PLAN - 1ST FLOOR 2 FLOOR FRAMING PLAN - 2ND FLOOR
S102 1/2" = 1'-0" S102 1/4" = 1'-0" S102 1/4" = 1'-0"
SHEET SCALE:
As indicated
6/18/2013 11:18:55 AM
SHEET TITLE:
FLOOR FRAMING
PLAN
4'-2 1/8"
4'-2 1/8"
PROVIDED AND IF MORE THAN ONE OFFSET OCCURS IN THE SAME INTERIOR BRACED WALL
LINE, THE CODE LIMITS THE SUM OF THE OFFSETS TO 8 FEET.
3. BRACED WALL PANELS SHALL START AT NO MORE THAN 8" FROM EACH END OF A BRACED
WALL LINE. THE CODE LIMITS THE SUM OF THE OFFSETS TO 8 FEET.
INTERIOR FINISH
4. ONE STORY BUILDINGS MUST HAVE 20% OF THE EXTERIOR WALL AREA CONSIST OF BRACED
PROVIDE CORNER CLIPS
WALL PANELS. THE FIRST STORY OF A TWO-STORY BUILDING MUST HAVE 45% OF THE
OR BLOCKING AS NEEDED
EXTERIOR WALL AREA CONSIST OF BRACED WALL PANELS IN ADDITION TO THE SECOND
FLOOR HAVING A MINIMUM OF 20% WALL PANEL AREA.
4'-0"
4'-0"
CONSTRUCTION OF BRACED WALL PANELS
"CALIFORNIA CORNER" 1. OPTIONAL SHEATHING MATERIALS:
A. WOOD STRUCTURAL PANEL SHEATHING WITH A THICKNESS NOT LESS THAN 5/16" FOR
16" O.C. SPACING AND NOT LESS THAN 3/8" FOR A 24" O.C. STUD SPACING.
B. G.W.B. 1/2" THICK AND 4'-0" WIDE ON STUDS NO MORE THAN 24" O.C. W/NAILS @ 7" O.C.
C. HARDBOARD PANEL SIDING.
12'-0"
6" O.C. ALL EDGES & 12" O.C. 1. IN ONE STORY BUILDINGS, ALTERNATE PANELS SHALL BE NOT LESS THAN 2'-8" WIDE WITH
IN THE FIELD 10'_0" MAX. HEIGHT. TWO ANCHOR BOLTS PER PANEL WITH EACH PANEL END STUD
4'-0" CONNECTED TO THE FOUNDATION WITH A TIE-DOWN DEVICE PROVIDING AN UPLIFT CAPACITY
16'-0"
OF AT LEAST 1,800 LBS.
2. IN THE FIRST STORY OF TWO STORY BUILDINGS, EACH PANEL SHALL BE PROVIDED WITH INTERIOR LATERAL EXEMPTION
WOOD STRUCTURAL PANEL SHEATHING ON BOTH SIDES WITH MINIMUM TIE-DOWN DEVICE 896 S.F.
UPLIFT CAPACITY OF 3,000 LBS. ALL REQUIRED BRACED WALL PANELS IN BUILDINGS
WITH PLAN DIMS. GREATER THAN 50' SHALL BE SUPPORTED BY CONTINUOUS FOOTINGS.
4'-0 1/8"
COMMUNITY COLLEGE
Olympia, WA 98512-6292
2011 Mottman Road SW
STANDARD 2x4 FRAMED 4'-0" LATERAL PANEL
www.spscc.ctc.edu
4'-0"
(360) 754-7711
STANDARD 2x6 FRAMED 4'-0" LATERAL PANEL
28'-4 1/8"
FASTEN W/8d
COMMON NAILS 14'-3 5/8" 14'-0 5/8"
@ 6" O.C. ALL EDGES
& 12" O.C. FIELD
4'-2 1/8" 20'-0" 4'-2 1/8"
TOP NAILING
(3) 16d @
4'-2 1/8"
4'-2 1/8"
16" O.C.
TOP PLATE
TO FRAMING NOTE:
ABOVE. BRACING
PANELS ATTACH
STATUS: Preliminary
TO PARALLEL
0" ROOF FRAMING
8'-
TO ABOVE.
4'-0"
4'-0"
UP PROVIDE FLAT
LADDER
16'-0 3/8"
18'-7 7/8"
2x BLOCK @ ANY NEEDED
WALL
PLYWOOD JOINT BETWEEN ROOF
PANELS NEED NOT
INTERSECT EXTERIOR FRAMING
WALLS BUT MUST MEMBERS.
BEGIN WITHIN 8'-0" OF WHEN FRAMING
SOLE PLATE RUNS
EXTERIOR WALL.
PERPENDICULAR
SUB-FLOOR TO BRACING
12'-0"
NAIL DIRECTLY
TO
ROOF FRAMING
16'-0"
MEMBERS.
HOUSE
1/2" GYPSUM WALL
BOARD MAY BE
P.T. SOLE PLATE BEARING PLATE WASHER NOTE:
INSTALLED VERTICALLY
PROJECT:
OR HORIZONTALLY ALL VERTICAL
W/ SCREWS OR NAILS JOINTS OF
@ 7" O.C. PANEL
(2) 1/2" A.B. W/7" SHEATHING
EMBEDMENT MIN. SHALL OCCUR
4'-0"
OVER STUDS.
1'-0" HORIZONTAL
JOINTS SHALL
OCCUR OVER
BLOCKING REVISIONS
EQUAL IN SIZE
# DESCRIPTION DATE
STEM WALL TO THE
4'-0"
STUDS.
BOTTOM
NAILING
FOOTING
(3) 16d @
16 O.C.
SOLE
PLATE TO
FRAMING
BELOW.
NOTE:
WHEN JOISTS RUN PARALLEL TO BRACED WALL LINES 4'-2 1/8" 20'-0" 4'-2 1/8"
ABOVE, PROVIDE DOUBLE JOISTS UNDER AND IN LINE WITH SHEET SCALE:
BRACED WALL PANELS.
14'-3 5/8" 14'-0 5/8" As indicated
WHERE JOISTS ARE PERPENDICULAR TO BRACED WALL
6/18/2013 11:18:56 AM
LINES ABOVE, FULL DEPTH BLOCKING SHALL BE PROVIDED 28'-4 1/8"
UNDER AND IN LINE WITH BRACED WALL PANELS.
SHEET TITLE:
STANDARD LATERAL PANEL - STANDARD LATERAL - INTERIOR LATERAL PLAN
2 ELEVATION 5 DETAIL 7 LATERAL PLAN - 2ND FLOOR
S105 1" = 1'-0" S105 1" = 1'-0" S105 1/4" = 1'-0"