CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Cabling Cores are assembled in a concentric layer & extruded filled type sheath is provided over
assembly up to 4 core. Assembly with 5 core & above is assembled with non-hygroscopic PP
filler if necessary & wrapped with polyester tape.
Inner Sheath Flame retardant PVC Type ST-2 to IEC 60502-1 in Black Color.
Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the inner sheath.
Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1.The color of the sheath is as per dimension
sheet.
Printing on the sheath CU/XLPE/PVC/GSWA/PVC NO OF CORES C X ...MM2 600/1000V MESC YEAR IEC 60502-
1 IEC 60332-3 CAT C LENGTH METER MARKING
Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)
Page 1 of 18
Middle East Specialized Cables (MESC)
POWER & CONTROL CABLE
MULTI CORE, ARMORED FLAME RETARDANT
CU/XLPE/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-175166-01-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
UV / Sunlight Resistance (Outer Sheath) Passes after 720 hrs (UL 1581)
DIMENSIONAL DATA
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
Nos. x mm (Nom.)
APPROX. CABLE
OUTER SHEATH
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
STRAND x DIA.
NO OF CORE
MESC CODE
INSULATION
SIZE (mm2)
DIA. OVER
DIA. (mm)
ITEM NO.
COLOR
(mm)
(mm)
1 7614-05C00150-W0BK8-00 Black 5C 1.5 7x0.53 0.7 1.0 10.7 0.9 12.5 1.8 16.1 464
2 7614-05C00250-W0BK8-00 Black 5C 2.5 7x0.67 0.7 1.0 11.8 0.9 13.6 1.8 17.2 546
3 7614-07C00150-W0BK8-00 Black 7C 1.5 7X0.53 0.7 1.0 11.6 0.9 13.4 1.8 17.0 528
4 7614-07C00250-W0BK8-00 Black 7C 2.5 7X0.67 0.7 1.0 12.9 1.25 15.4 1.8 19.0 730
5 7614-12C00150-W0BK8-00 Black 12C 1.5 7X0.53 0.7 1.0 15.2 1.25 17.7 1.8 21.3 860
6 7614-12C00250-W0BK8-00 Black 12C 2.5 7X0.67 0.7 1.0 16.9 1.25 19.4 1.8 23.0 1037
7 7614-19C00150-W0BK8-00 Black 19C 1.5 7X0.53 0.7 1.0 17.8 1.25 20.3 1.8 23.9 1086
8 7614-19C00250-W0BK8-00 Black 19C 2.5 7X0.67 0.7 1.0 19.9 1.6 23.1 1.8 26.7 1485
9 7614-27C00150-W0BK8-00 Black 27C 1.5 7X0.53 0.7 1.0 21.3 1.6 24.5 1.8 28.1 1532
10 7614-32C00150-W0BK8-00 Black 32C 1.5 7X0.53 0.7 1.0 23.0 1.6 26.2 1.8 29.8 1696
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 2 of 18
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI TRIAD COLLECTIVELY SCREENED, ARMORED FIRE RESISTANCE CABLE
CU/MICA/XLPE/OS/LSZH/GSWA/LSZH
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-02-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
CONSTRUCTION
Conductor Stranded annealed plain copper to Class 2 of IEC 60228.
Two insulated conductor are uniformly twisted to form a pair with 10-14 twists per meter.
Pair Construction
Required numbers of twisted pairs are assembled with non-hygroscopic filler and the
Cabling
assembly is wrapped with a polyester binder tape.
Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
Collective Screen
down in contact with a stranded tinned copper drain wire of 0.5mm² (7x0.3mm) run
longitudinally over the binder tape.
A single layer of galvanized steel wire armor to BS EN10257-1 is applied over the inner
Wire Armor
sheath.
Outer sheath Low Smoke Zero Halogen thermoplastic to EN 50290-2-27. Outer sheath is anti-vermin,
rodent termite protected. The color of the sheath shall be as per dimension sheet.
Technical Data:
- 5°C to 50°C (During installation) - 15°C to 90°C (During Operation)
Temperature Range
Voltage Rating 500 Volts
≤ 100nF/Km
Mutual Capacitance (at 1KHz)
Capacitance Unbalance (at 1kHz) ≤ 500 pF/500m (Not applicable for single pair/triad)
Dielectric Strength Test (Core to core & 2000 VAC / 3000 VDC. For 1 minute.
core to screen)
Page 3 of 18
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI TRIAD COLLECTIVELY SCREENED, ARMORED FIRE RESISTANCE CABLE
CU/MICA/XLPE/OS/LSZH/GSWA/LSZH
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-02-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
UV / Sunlight Resistance (Outer Sheath) Passes after 720 hrs. (UL 1581)
DIMENSIONAL DATA
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
STRAND x DIA.
SHEATH (mm)
MESC CODE
INSULATION
SIZE (mm2)
DIA. (mm)
ITEM NO
(n x mm)
COLOR
(mm)
(mm)
PAIR
11 021G-01P00150-W0BK8-ZA Black 1P 1.5 7x0.53 0.5 0.9 9.5 0.9 11.3 1.3 13.9 340
12 021G-01P00250-W0BK8-ZA Black 1P 2.5 7x0.67 0.6 0.9 10.8 0.9 12.6 1.4 15.4 407
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 4 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/LSZH/GSWA/LSZH
SPECIFICATION: BS EN 50288-7, IEC 60331-21(180mins. @ 750ºC) & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-03-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Color Code Multi pair: Black & White with each core numbered.
Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.
Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25% with
the metallic side down in contact with a stranded annealed tinned copper drain wire of
0.5mm2 (7x0.3mm). All pair shields are electrically isolated from each other.
Cabling Required numbers of individually screened pairs are assembled with non-hygroscopic fillers
if necessary and the assembly is wrapped with a polyester binder tape.
Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic
side down in contact with a stranded annealed tinned copper drain wire of 0.5mm2
(7x0.3mm) run longitudinally over the binder tape.
Inner Sheath Low Smoke Zero Halogen thermoplastic to EN 50290-2-27 in Black color.
Armor A single galvanized steel wire armor to EN 10257-1 is applied over the inner sheath.
Outer Sheath Low Smoke Zero Halogen thermoplastic to EN 50290-2-27. Outer sheath is anti-vermin,
anti-termite and anti-rodent protected. The color of the sheath shall be as per dimension
sheet.
Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)
Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)
Page 5 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/LSZH/GSWA/LSZH
SPECIFICATION: BS EN 50288-7, IEC 60331-21(180mins. @ 750ºC) & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-03-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
DIMENSIONAL DATA
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
(n x mm) (nom.)
STRAND x DIA.
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. (mm)
COLOR
(mm)
(mm)
PAIR
13 041G-02P00150-W0BK8-ZA Black 2P 1.5 7x0.53 0.5 1.1 16.2 0.9 18.0 1.5 21.0 633
14 041G-05P00150-W0BK8-ZA Black 5P 1.5 7x0.53 0.5 1.2 21.1 0.9 22.9 1.6 26.1 981
15 041G-06P00150-W0BK8-ZA Black 6P 1.5 7x0.53 0.5 1.2 23.1 1.25 25.6 1.6 28.8 1243
16 041G-08P00150-W0BK8-ZA Black 8P 1.5 7x0.53 0.5 1.3 26.4 1.25 28.9 1.7 32.3 1514
17 041G-10P00150-W0BK8-ZA Black 10P 1.5 7x0.53 0.5 1.4 30.3 1.6 33.5 1.8 37.1 2020
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 6 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI PAIR COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-04-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
CONSTRUCTION
Conductor Stranded annealed plain circular copper to Class 2 of IEC 60228.
Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.
Cabling Required numbers of twisted pairs are assembled with non-hygroscopic fillers and the
assembly is wrapped with a polyester binder tape.
Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
down in contact with a stranded annealed tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.
Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the inner sheath.
Outer Sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.
Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)
Conductor Resistance (at 20ºC) ≤ 12.1 : 12.3 (single pair/triad : multi pair/triad for 1.5mm2) Ω/km
Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)
Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)
Page 7 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI PAIR COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-04-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
DIMENSIONAL DATA
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
(n x mm) (nom.)
STRAND x DIA.
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. (mm)
COLOR
PAIR
(mm)
(mm)
18 0214-01P00150-W0BK8-E5 Black 1P 1.5 7x0.53 0.5 0.9 7.9 0.9 9.7 1.3 12.3 291
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 8 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-05-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Color Code Multi pair: Black & White with each core numbered.
Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.
Individual Screen Aluminum Backed Mylar tape (25μm) is applied over each pair with 100% coverage and an
overlap of 25% with metal side down in contact with a stranded tinned copper drain wire of
0.5mm2 (7x0.3mm). All pair shields are electrically isolated from each other.
Cabling Required numbers of individually screened pairs/triads are assembled with non-hygroscopic
filler and the assembly is wrapped with a polyester binder tape.
Collective Screen Aluminum Backed Mylar tape (25μm) is applied with 100% coverage and an overlap of 25%
with metal side down in contact with a stranded tinned copper drain wire of 0.5mm2
(7x0.3mm) run longitudinally over the binder tape.
Armor A single layer of galvanized steel wire armor to EN 10257-1 applied over the inner sheath.
Outer Sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.
Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)
Conductor Resistance ≤ 12.1 : 12.3 (single pair/triad : multi pair/triad for 1.5mm2) Ω/km
Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)
Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)
Page 9 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-05-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
DIMENSIONAL DATA
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
(n x mm) (nom.)
STRAND x DIA.
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. (mm)
COLOR
PAIR
(mm)
(mm)
19 0414-02P00150-W0BK8-E5 Black 2P 1.5 7x0.53 0.5 1.1 13.4 0.9 15.2 1.5 18.2 527
20 0414-05P00150-W0BK8-E5 Black 5P 1.5 7x0.53 0.5 1.2 17.3 0.9 19.1 1.6 22.3 800
21 0414-10P00150-W0BK8-E5 Black 10P 1.5 7x0.53 0.5 1.4 24.6 1.25 27.1 1.8 30.7 1482
22 0414-12P00150-W0BK8-E5 Black 12P 1.5 7x0.53 0.5 1.5 25.7 1.25 28.2 1.8 31.8 1619
23 0414-15P00150-W0BK8-E5 Black 15P 1.5 7x0.53 0.5 1.5 28.6 1.25 31.1 1.8 34.7 1874
24 0414-20P00150-W0BK8-E5 Black 20P 1.5 7x0.53 0.5 1.7 32.3 1.6 35.5 2.0 39.5 2535
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 10 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/OS/AL/HDPE/PA/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-05-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.
Cabling Required numbers of pairs are assembled with non-hygroscopic filler if necessary and the
assembly is wrapped with a polyester binder tape.
Collective Screen & An Aluminum (Al) foil (0.20mm) coated on up side with a protective plastic coating (0.05mm)
Multilayer Sheath is applied longitudinally over the assembly to form laminated aluminum moisture barrier
sheath. A stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run longitudinally in
contact with the Aluminum side of the Aluminum tape. A Black extruded bedding of High
Density Polyethylene compound meeting the requirement of EN 50290-2-24 shall be applied
over the Aluminum foil and shall be bonded to the Aluminum foil. Over the High Density
Polyethylene bedding, a protective sheath 0.3mm of Black Polyamide shall be extruded.
Armor A single layer of galvanized steel wire armor to EN 10257-1 applied over the multilayer
sheath.
Outer Sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.
Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)
Conductor Resistance (at 20ºC) ≤ 12.1 : 12.3 (single pair/triad : multi pair/triad for 1.5mm2) Ω/km
Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)
Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)
Page 11 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/OS/AL/HDPE/PA/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-05-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
DIMENSIONAL DATA
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
(n x mm) (nom.)
STRAND x DIA.
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. (mm)
COLOR
PAIR
(mm)
(mm)
25 0214-01P00150-WABK8-E5 Black 1P 1.5 7x0.53 0.5 1.0 9.7 0.9 11.5 1.4 14.3 352
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 12 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/AL/HDPE/PA/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-07-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Color Code Multi pair: Black & White with each core numbered.
Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.
Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25% with
the metallic side down in contact with a stranded annealed tinned copper drain wire of
0.5mm2 (7x0.3mm). All pair shields are electrically isolated from each other.
Cabling Required numbers of individually screened pairs/triads are assembled with non-hygroscopic
filler and the assembly is wrapped with a polyester binder tape.
Collective Screen & An Aluminum (AL) foil (0.20mm) coated on up side with a protective plastic coating (0.05mm)
Multilayer Sheath is applied longitudinally over the assembly to form laminated aluminum moisture barrier
sheath. A stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run longitudinally in
contact with the Aluminum side of the Aluminum tape. A Black extruded bedding of High
Density Polyethylene compound meeting the requirement of EN 50290-2-24 shall be applied
over the Aluminum foil and shall be bonded to the Aluminum foil. Over the High Density
Polyethylene bedding, a protective sheath 0.3mm of Black Polyamide shall be extruded.
Armor A single layer of galvanized steel wire armor to EN 10257-1 applied over the multilayer
sheath.
Outer Sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.
Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)
Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)
Page 13 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/AL/HDPE/PA/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-07-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
DIMENSIONAL DATA
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
APPROX. CABLE
OUTER SHEATH
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
STRAND x DIA.
(n x mm) (nom.)
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. (mm)
COLOR
PAIR
(mm)
(mm)
26 0414-02P00150-WABK8-E5 Black 2P 1.5 7x0.53 0.5 1.1 14.9 0.9 16.7 1.5 19.7 582
27 0414-05P00150-WABK8-E5 Black 5P 1.5 7x0.53 0.5 1.2 18.8 1.25 21.3 1.6 24.5 980
28 0414-10P00150-WABK8-E5 Black 10P 1.5 7x0.53 0.5 1.5 26.4 1.25 28.9 1.8 32.5 1556
Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.
Page 14 of 18
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI PAIR COLLECTIVELY SCREENED, LEAD, ARMORED, FLAME RETARDANT CABLE
CU/XLPE/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-08-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.
Cabling Required numbers of individually pairs are assembled with non-hygroscopic filler and the
assembly is wrapped with a polyester binder tape.
Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
down in contact with a stranded tinned copper drain wire of 0.5mm² (7x0.3mm) run
longitudinally over the binder tape.
Wire Armour A single layer of galvanized steel wire armor to BS EN10257-1 is applied over the Bedding.
Outer sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.
Technical Data:
Temperature Range - 5°C to 50°C (During installation) & - 15°C to 90°C (During Operation)
Capacitance Unbalance (at 1kHz) ≤ 500 pF/500m (Not applicable for single pair/triad)
Dielectric Strength Test (Core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)
Page 15 of 18
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI PAIR COLLECTIVELY SCREENED, LEAD, ARMORED, FLAME RETARDANT CABLE
CU/XLPE/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-08-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
UV /Sunlight resistance (outer sheath) Passes after 720 hrs. (UL 1581)
DIMENSIONAL DATA
THICKNESS (mm)
OUTER SHEATH
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
BEDDING THICK.
APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
(n x mm) (Nom.)
BEDDING (mm)
STRAND x DIA.
LEAD SHEATH
SHEATH (mm)
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. OVER
DIA. (mm)
COLOR
TRIAD
(mm)
(mm)
(mm)
Nom.
Min.
29 0214-01P00150-WLBK8-LV Black 1P 1.5 7x0.53 0.5 0.9 7.8 0.9 9.4 1.0 11.5 0.9 13.3 1.5 1.00 15.9 665
Note: The tolerance on the cable overall diameter shall be +/- 2.5mm up to 30mm & +/- 3.0mm above 30mm.
Page 16 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-09-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.
Color Code Multi pair: Black & White with each core numbered.
Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per
meter.
Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25%
with metallic side down in contact with a stranded tinned copper drain wire of 0.5mm²
(7x0.3mm). All pair shields are electrically isolated from each other.
Cabling Required numbers of individually screened pairs are assembled with non-hygroscopic
filler and the assembly is wrapped with a polyester binder tape.
Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with metallic
side down in contact with a stranded tinned copper drain wire of 0.5mm² (7x0.3mm) run
longitudinally over the binder tape.
Wire Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the bedding.
Outer Sheath Flame retardant PVC to EN 50290-2-22. The color of the sheath is as per dimension
sheet.
Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)
Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)
Dielectric Strength Test (core to core 2000 VAC / 3000 VDC for 1 minute
& core to screen)
Page 17 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-09-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019
DIMENSIONAL DATA
THICKNESS (mm)
OUTER SHEATH
APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)
THICKNESS (mm)
THICKNESS (mm)
BEDDING THICK.
APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH
WEIGHT (kg/km)
INNER SHEATH
(n x mm) (Nom.)
BEDDING (mm)
STRAND x DIA.
LEAD SHEATH
SHEATH (mm)
SHEATH (mm)
MESC CODE
INSULATION
SERIAL NO.
SIZE (mm2)
DIA. OVER
DIA. (mm)
COLOR
TRIAD
(mm)
(mm)
(mm)
Nom.
Min.
30 0414-02P00150-WLBK8-LV Black 2P 1.5 7x0.53 0.5 1.1 13.3 1.0 15.1 1.0 17.2 1.25 19.7 1.6 1.08 22.5 1263
31 0414-05P00150-WLBK8-LV Black 5P 1.5 7x0.53 0.5 1.2 17.2 1.1 19.2 1.0 21.3 1.25 23.8 1.7 1.16 26.6 1768
Note: The tolerance on the cable overall diameter shall be +/- 2.5mm up to 30mm & +/- 3.0mm above 30mm.
Page 18 of 18