Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

Middle East Specialized Cables (MESC)

POWER & CONTROL CABLE


MULTI CORE, ARMORED FLAME RETARDANT
CU/XLPE/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-175166-01-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation Cross linked polyethylene (XLPE) to IEC 60502-1.

Color Code 2C: Red & Black


3C: Red, Yellow & Blue
4C: Red, Yellow, Blue & Black
5C& Above: White Core with Black number.

Cabling Cores are assembled in a concentric layer & extruded filled type sheath is provided over
assembly up to 4 core. Assembly with 5 core & above is assembled with non-hygroscopic PP
filler if necessary & wrapped with polyester tape.

Inner Sheath Flame retardant PVC Type ST-2 to IEC 60502-1 in Black Color.

Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the inner sheath.

Outer Sheath Flame retardant PVC Type ST-2 to IEC 60502-1.The color of the sheath is as per dimension
sheet.

Printing on the sheath CU/XLPE/PVC/GSWA/PVC NO OF CORES C X ...MM2 600/1000V MESC YEAR IEC 60502-
1 IEC 60332-3 CAT C LENGTH METER MARKING

Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)

Voltage Rating 600/1000 Volts as per IEC 60502-1

DC Cond. Res. at 20ºC Max. (Ω/km) 12.1(1.5mm2), 7.41(2.5mm2)


AC Cond. Res. at 90ºC Max. (Ω/km) 15.43(1.5mm2), 9.45(2.5mm2)
Inductance at 50-60Hz (mH/km) 0.336(1.5mm2), 0.314(2.5mm2)
Inductive Reactance at 50-60Hz (Ω/km) 0.106(1.5mm2), 0.099(2.5mm2)
Impedance at 50-60Hz & at 90ºC (Ω/km) 15.43(1.5mm2), 9.449(2.5mm2)
Cond. Short Circuit Current Rating (kA/sec) 0.21(1.5mm2), 0.50(2.5mm2)
Voltage Withstand (V/Minute) 3500 VRMS / 5 or 8400 VDC / 5

Page 1 of 18
Middle East Specialized Cables (MESC)
POWER & CONTROL CABLE
MULTI CORE, ARMORED FLAME RETARDANT
CU/XLPE/PVC/GSWA/PVC
SPECIFICATION: IEC 60502-1 & IEC 60332-3 CAT C
MESC Doc. No.: TD-175166-01-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT C

Halogen Acid Gas (Outer Sheath) MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV / Sunlight Resistance (Outer Sheath) Passes after 720 hrs (UL 1581)

Oil Resistance (Outer Sheath) Passes (ICEA-S-73-532)

Min. Bending Radius 12 x Cable Overall Diameter

DIMENSIONAL DATA

INNER SHEATH (mm)

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)
Nos. x mm (Nom.)

APPROX. CABLE
OUTER SHEATH

OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
STRAND x DIA.
NO OF CORE
MESC CODE

INSULATION
SIZE (mm2)

DIA. OVER

DIA. (mm)
ITEM NO.

COLOR

(mm)

(mm)
1 7614-05C00150-W0BK8-00 Black 5C 1.5 7x0.53 0.7 1.0 10.7 0.9 12.5 1.8 16.1 464
2 7614-05C00250-W0BK8-00 Black 5C 2.5 7x0.67 0.7 1.0 11.8 0.9 13.6 1.8 17.2 546
3 7614-07C00150-W0BK8-00 Black 7C 1.5 7X0.53 0.7 1.0 11.6 0.9 13.4 1.8 17.0 528
4 7614-07C00250-W0BK8-00 Black 7C 2.5 7X0.67 0.7 1.0 12.9 1.25 15.4 1.8 19.0 730
5 7614-12C00150-W0BK8-00 Black 12C 1.5 7X0.53 0.7 1.0 15.2 1.25 17.7 1.8 21.3 860
6 7614-12C00250-W0BK8-00 Black 12C 2.5 7X0.67 0.7 1.0 16.9 1.25 19.4 1.8 23.0 1037
7 7614-19C00150-W0BK8-00 Black 19C 1.5 7X0.53 0.7 1.0 17.8 1.25 20.3 1.8 23.9 1086
8 7614-19C00250-W0BK8-00 Black 19C 2.5 7X0.67 0.7 1.0 19.9 1.6 23.1 1.8 26.7 1485
9 7614-27C00150-W0BK8-00 Black 27C 1.5 7X0.53 0.7 1.0 21.3 1.6 24.5 1.8 28.1 1532
10 7614-32C00150-W0BK8-00 Black 32C 1.5 7X0.53 0.7 1.0 23.0 1.6 26.2 1.8 29.8 1696

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 2 of 18
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI TRIAD COLLECTIVELY SCREENED, ARMORED FIRE RESISTANCE CABLE
CU/MICA/XLPE/OS/LSZH/GSWA/LSZH
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-02-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

CONSTRUCTION
Conductor Stranded annealed plain copper to Class 2 of IEC 60228.

Insulation MICA impregnated glass tape + XLPE to BS EN 50290-2-29.

Color Code Single Pair: Black & White.

Two insulated conductor are uniformly twisted to form a pair with 10-14 twists per meter.
Pair Construction

Required numbers of twisted pairs are assembled with non-hygroscopic filler and the
Cabling
assembly is wrapped with a polyester binder tape.

Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
Collective Screen
down in contact with a stranded tinned copper drain wire of 0.5mm² (7x0.3mm) run
longitudinally over the binder tape.

Low smoke zero halogen thermoplastic as per BS EN 50290-2-27 in Black color.


Inner Sheathing

A single layer of galvanized steel wire armor to BS EN10257-1 is applied over the inner
Wire Armor
sheath.

Outer sheath Low Smoke Zero Halogen thermoplastic to EN 50290-2-27. Outer sheath is anti-vermin,
rodent termite protected. The color of the sheath shall be as per dimension sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/MICA/XLPE/LSZH/GSWA/LSZH SHIELDED NO OF PAIRS


X 2 X…MM2 500V MESC YEAR BS EN 50288-7 IEC 60331 IEC 60332-3 CAT A LENGTH
METER MARKING

Technical Data:
- 5°C to 50°C (During installation) - 15°C to 90°C (During Operation)
Temperature Range
Voltage Rating 500 Volts

≤ 12.1 (single pair/triad for 1.5mm2) Ω/km at 20°C


Conductor Resistance
≤ 7.41 (single pair/triad for 2.5mm2) Ω/km at 20°C

≤ 100nF/Km
Mutual Capacitance (at 1KHz)
Capacitance Unbalance (at 1kHz) ≤ 500 pF/500m (Not applicable for single pair/triad)

≤ 40 (1.5mm2) µH/Ω & 60 (2.5mm2) µH/Ω


L/R Ratio
Insulation Resistance ≥ 5000 MΩ - Km at 20°C (500 VDC1 minute)

Dielectric Strength Test (Core to core & 2000 VAC / 3000 VDC. For 1 minute.
core to screen)

Page 3 of 18
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI TRIAD COLLECTIVELY SCREENED, ARMORED FIRE RESISTANCE CABLE
CU/MICA/XLPE/OS/LSZH/GSWA/LSZH
SPECIFICATION: BS EN 50288-7, IEC 60331 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-02-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT A

Fire Resistance IEC 60331-21 (750°C @ 90 minutes)

Halogen Acid Gas (Outer Sheath) MAX. 0.5% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

Light Transmission ≥ 60% (IEC 61034)

UV / Sunlight Resistance (Outer Sheath) Passes after 720 hrs. (UL 1581)

Oil Resistance (Outer Sheath) Passes (ICEA S-73-532)

Min. Bending Radius 12 x Cable Overall Diameter

DIMENSIONAL DATA

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
STRAND x DIA.

SHEATH (mm)
MESC CODE

INSULATION
SIZE (mm2)

DIA. (mm)
ITEM NO

(n x mm)
COLOR

(mm)

(mm)
PAIR

11 021G-01P00150-W0BK8-ZA Black 1P 1.5 7x0.53 0.5 0.9 9.5 0.9 11.3 1.3 13.9 340
12 021G-01P00250-W0BK8-ZA Black 1P 2.5 7x0.67 0.6 0.9 10.8 0.9 12.6 1.4 15.4 407

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 4 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/LSZH/GSWA/LSZH
SPECIFICATION: BS EN 50288-7, IEC 60331-21(180mins. @ 750ºC) & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-03-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation MICA impregnated glass tape + XLPE to BS EN 50290-2-29.

Color Code Multi pair: Black & White with each core numbered.

Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.

Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25% with
the metallic side down in contact with a stranded annealed tinned copper drain wire of
0.5mm2 (7x0.3mm). All pair shields are electrically isolated from each other.

Cabling Required numbers of individually screened pairs are assembled with non-hygroscopic fillers
if necessary and the assembly is wrapped with a polyester binder tape.

Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic
side down in contact with a stranded annealed tinned copper drain wire of 0.5mm2
(7x0.3mm) run longitudinally over the binder tape.

Inner Sheath Low Smoke Zero Halogen thermoplastic to EN 50290-2-27 in Black color.

Armor A single galvanized steel wire armor to EN 10257-1 is applied over the inner sheath.

Outer Sheath Low Smoke Zero Halogen thermoplastic to EN 50290-2-27. Outer sheath is anti-vermin,
anti-termite and anti-rodent protected. The color of the sheath shall be as per dimension
sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/MICA/XLPE/LSZH/GSWA/LSZH SHIELDED NO. OF


PAIRS X 2 X …MM2 500V MESC YEAR BS EN 50288-7 IEC 60331 IEC 60332-3 CAT A
LENGTH METER MARKING

Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)

Voltage Rating 500V

Conductor Resistance ≤ 12.3 (1.5mm2) Ω/km at 20ºC

Mutual Capacitance (at 1kHz) ≤ 100nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance Constant ≥ 5000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)

Page 5 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FIRE RESISTANT
CU/MICA/XLPE/IS/OS/LSZH/GSWA/LSZH
SPECIFICATION: BS EN 50288-7, IEC 60331-21(180mins. @ 750ºC) & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-03-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT A

Fire Resistance IEC 60331-21 (750°C @ 90 minutes)

Halogen Acid Gas (Outer Sheath) MAX. 0.5% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

Light Transmission ≥ 60% (IEC 61034)

UV / Sunlight Resistance (Outer Passes after 720hrs. (UL 1581)


Sheath)
Oil Resistance (Outer Sheath) Passes (ICEA S-73-532)

Min. Bending Radius 12 x Cable Overall Diameter

DIMENSIONAL DATA

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
(n x mm) (nom.)
STRAND x DIA.

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. (mm)
COLOR

(mm)

(mm)
PAIR

13 041G-02P00150-W0BK8-ZA Black 2P 1.5 7x0.53 0.5 1.1 16.2 0.9 18.0 1.5 21.0 633
14 041G-05P00150-W0BK8-ZA Black 5P 1.5 7x0.53 0.5 1.2 21.1 0.9 22.9 1.6 26.1 981
15 041G-06P00150-W0BK8-ZA Black 6P 1.5 7x0.53 0.5 1.2 23.1 1.25 25.6 1.6 28.8 1243
16 041G-08P00150-W0BK8-ZA Black 8P 1.5 7x0.53 0.5 1.3 26.4 1.25 28.9 1.7 32.3 1514
17 041G-10P00150-W0BK8-ZA Black 10P 1.5 7x0.53 0.5 1.4 30.3 1.6 33.5 1.8 37.1 2020

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 6 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI PAIR COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-04-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

CONSTRUCTION
Conductor Stranded annealed plain circular copper to Class 2 of IEC 60228.

Insulation XLPE to EN 50290-2-29.

Color code Single Pair: Black & White.

Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.

Cabling Required numbers of twisted pairs are assembled with non-hygroscopic fillers and the
assembly is wrapped with a polyester binder tape.

Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
down in contact with a stranded annealed tinned copper drain wire of 0.5mm2 (7x0.3mm) run
longitudinally over the binder tape.

Inner Sheath Flame retardant PVC to EN 50290-2-22 in Black color.

Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the inner sheath.

Outer Sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/XLPE/PVC/GSWA/PVC SHIELDED NO OF PAIRS X 2 X


…. MM2 500V MESC YEAR BS EN 50288-7 IEC 60332-3 CAT A LENGTH METER
MARKING

Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)

Voltage Rating 500V

Conductor Resistance (at 20ºC) ≤ 12.1 : 12.3 (single pair/triad : multi pair/triad for 1.5mm2) Ω/km

Mutual Capacitance (at 1kHz) ≤ 100nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance Constant ≥ 5000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)

Page 7 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI PAIR COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-04-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT A

Halogen Acid Gas MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV /Sunlight Resistance (Outer Passes after 720 hrs (UL 1581)


Sheath)
Oil Resistance (Outer Sheath) Passes (ICEA S-73-532)

Min. Bending Radius 12 x Cable Overall Diameter

DIMENSIONAL DATA

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
(n x mm) (nom.)
STRAND x DIA.

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. (mm)
COLOR

PAIR

(mm)

(mm)

18 0214-01P00150-W0BK8-E5 Black 1P 1.5 7x0.53 0.5 0.9 7.9 0.9 9.7 1.3 12.3 291

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 8 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-05-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation XLPE to EN 50290-2-29.

Color Code Multi pair: Black & White with each core numbered.

Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.

Individual Screen Aluminum Backed Mylar tape (25μm) is applied over each pair with 100% coverage and an
overlap of 25% with metal side down in contact with a stranded tinned copper drain wire of
0.5mm2 (7x0.3mm). All pair shields are electrically isolated from each other.

Cabling Required numbers of individually screened pairs/triads are assembled with non-hygroscopic
filler and the assembly is wrapped with a polyester binder tape.

Collective Screen Aluminum Backed Mylar tape (25μm) is applied with 100% coverage and an overlap of 25%
with metal side down in contact with a stranded tinned copper drain wire of 0.5mm2
(7x0.3mm) run longitudinally over the binder tape.

Inner Sheath Flame retardant PVC to EN 50290-2-22 in Black color.

Armor A single layer of galvanized steel wire armor to EN 10257-1 applied over the inner sheath.

Outer Sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/XLPE/PVC/GSWA/PVC SHIELDED NO. OF PAIRS X 2 X


… MM2 500V MESC YEAR BS EN 50288-7 IEC 60332-3 CAT A LENGTH METER
MARKING

Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)

Voltage Rating 500V

Conductor Resistance ≤ 12.1 : 12.3 (single pair/triad : multi pair/triad for 1.5mm2) Ω/km

Mutual Capacitance (at 1kHz) ≤ 100nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance ≥ 5000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)

Page 9 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-05-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT A

Halogen Acid Gas MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV /Sunlight Resistance (Outer Passes after 720 hrs (UL 1581)


Sheath)
Oil Resistance (Outer Sheath) Passes (ICEA S-73-532)

Min. Bending Radius 12 x Cable Overall Diameter

DIMENSIONAL DATA

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
(n x mm) (nom.)
STRAND x DIA.

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. (mm)
COLOR

PAIR

(mm)

(mm)

19 0414-02P00150-W0BK8-E5 Black 2P 1.5 7x0.53 0.5 1.1 13.4 0.9 15.2 1.5 18.2 527
20 0414-05P00150-W0BK8-E5 Black 5P 1.5 7x0.53 0.5 1.2 17.3 0.9 19.1 1.6 22.3 800
21 0414-10P00150-W0BK8-E5 Black 10P 1.5 7x0.53 0.5 1.4 24.6 1.25 27.1 1.8 30.7 1482
22 0414-12P00150-W0BK8-E5 Black 12P 1.5 7x0.53 0.5 1.5 25.7 1.25 28.2 1.8 31.8 1619
23 0414-15P00150-W0BK8-E5 Black 15P 1.5 7x0.53 0.5 1.5 28.6 1.25 31.1 1.8 34.7 1874
24 0414-20P00150-W0BK8-E5 Black 20P 1.5 7x0.53 0.5 1.7 32.3 1.6 35.5 2.0 39.5 2535

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 10 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/OS/AL/HDPE/PA/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-05-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation XLPE as per EN 50290-2-29.

Color Code Single pair: Black & White.

Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.

Cabling Required numbers of pairs are assembled with non-hygroscopic filler if necessary and the
assembly is wrapped with a polyester binder tape.

Collective Screen & An Aluminum (Al) foil (0.20mm) coated on up side with a protective plastic coating (0.05mm)
Multilayer Sheath is applied longitudinally over the assembly to form laminated aluminum moisture barrier
sheath. A stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run longitudinally in
contact with the Aluminum side of the Aluminum tape. A Black extruded bedding of High
Density Polyethylene compound meeting the requirement of EN 50290-2-24 shall be applied
over the Aluminum foil and shall be bonded to the Aluminum foil. Over the High Density
Polyethylene bedding, a protective sheath 0.3mm of Black Polyamide shall be extruded.

Armor A single layer of galvanized steel wire armor to EN 10257-1 applied over the multilayer
sheath.

Outer Sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/XLPE/AL/HDPE/PA/GSWA/PVC SHIELDED NO. OF PAIR


X 2 X … MM2 300V MESC YEAR BS EN 50288-7 IEC 60332-3 CAT A LENGTH METER
MARKING

Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)

Voltage Rating 500V

Conductor Resistance (at 20ºC) ≤ 12.1 : 12.3 (single pair/triad : multi pair/triad for 1.5mm2) Ω/km

Mutual Capacitance (at 1kHz) ≤ 100nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance Constant ≥ 5000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)

Page 11 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
SINGLE PAIR COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/OS/AL/HDPE/PA/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-05-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT A

Halogen Acid Gas MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV /Sunlight Resistance (Outer Passes after 720 hrs (UL 1581)


Sheath)
Oil Resistance (Outer Sheath) Passes (ICEA S-73-532)

Min. Bending Radius 20 x Cable Overall Diameter

DIMENSIONAL DATA

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
(n x mm) (nom.)
STRAND x DIA.

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. (mm)
COLOR

PAIR

(mm)

(mm)

25 0214-01P00150-WABK8-E5 Black 1P 1.5 7x0.53 0.5 1.0 9.7 0.9 11.5 1.4 14.3 352

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 12 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/AL/HDPE/PA/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-07-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation XLPE to EN 50290-2-29.

Color Code Multi pair: Black & White with each core numbered.

Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.

Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25% with
the metallic side down in contact with a stranded annealed tinned copper drain wire of
0.5mm2 (7x0.3mm). All pair shields are electrically isolated from each other.

Cabling Required numbers of individually screened pairs/triads are assembled with non-hygroscopic
filler and the assembly is wrapped with a polyester binder tape.

Collective Screen & An Aluminum (AL) foil (0.20mm) coated on up side with a protective plastic coating (0.05mm)
Multilayer Sheath is applied longitudinally over the assembly to form laminated aluminum moisture barrier
sheath. A stranded tinned copper drain wire of 0.5mm2 (7x0.3mm) run longitudinally in
contact with the Aluminum side of the Aluminum tape. A Black extruded bedding of High
Density Polyethylene compound meeting the requirement of EN 50290-2-24 shall be applied
over the Aluminum foil and shall be bonded to the Aluminum foil. Over the High Density
Polyethylene bedding, a protective sheath 0.3mm of Black Polyamide shall be extruded.

Armor A single layer of galvanized steel wire armor to EN 10257-1 applied over the multilayer
sheath.

Outer Sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/XLPE/AL/HDPE/PA/GSWA/PVC SHIELDED NO. OF


PAIRS X 2 X …MM2 500V MESC YEAR BS EN 50288-7 IEC 60332-3 CAT A LENGTH
METER MARKING

Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)

Voltage Rating 500V

Conductor Resistance ≤ 12.3 (multi pair/triad for 1.5mm2) Ω/km

Mutual Capacitance (at 1kHz) ≤ 100nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance ≥ 5000MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)

Page 13 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUALLY & COLLECTIVELY SCREENED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/AL/HDPE/PA/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-07-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

Flame Behavior Characteristics:


Flame Retardant (Outer Sheath) IEC 60332-3 CAT A

Halogen Acid Gas (Outer Sheath) MAX. 15% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

Temperature Index ≥ 250ºC (ASTM D2863)

Smoke Density ≥ 60% (ASTM D2843)

UV / Sunlight Resistance (Outer Sheath) Passes after 720hrs. (UL 1581)

Oil Resistance (Outer Sheath) Passes (ICEA-S-73-532) / IEC 60811-404

Min. Bending Radius 20 x Cable Overall Diameter

DIMENSIONAL DATA

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

APPROX. CABLE
OUTER SHEATH

OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
STRAND x DIA.
(n x mm) (nom.)

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. (mm)
COLOR

PAIR

(mm)

(mm)

26 0414-02P00150-WABK8-E5 Black 2P 1.5 7x0.53 0.5 1.1 14.9 0.9 16.7 1.5 19.7 582
27 0414-05P00150-WABK8-E5 Black 5P 1.5 7x0.53 0.5 1.2 18.8 1.25 21.3 1.6 24.5 980
28 0414-10P00150-WABK8-E5 Black 10P 1.5 7x0.53 0.5 1.5 26.4 1.25 28.9 1.8 32.5 1556

Note: The tolerance on the cable overall diameter shall be ± 2.5mm up to 30mm & ± 3.0mm above 30mm.

Page 14 of 18
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI PAIR COLLECTIVELY SCREENED, LEAD, ARMORED, FLAME RETARDANT CABLE
CU/XLPE/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-08-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation XLPE as per EN 50290-2-29.

Color Code Single pair: Black & White.

Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per meter.

Cabling Required numbers of individually pairs are assembled with non-hygroscopic filler and the
assembly is wrapped with a polyester binder tape.

Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with the metallic side
down in contact with a stranded tinned copper drain wire of 0.5mm² (7x0.3mm) run
longitudinally over the binder tape.

Inner Sheathing Flame retardant PVC as per BS EN 50290-2-22 in Black color.

Lead Sheath Lead Sheath as per BS EN 50307.

Bedding Flame retardant PVC as per BS EN 50290-2-22 in Black color.

Wire Armour A single layer of galvanized steel wire armor to BS EN10257-1 is applied over the Bedding.

Outer sheath Flame retardant PVC to EN 50290-2-22.The color of the sheath shall be as per dimension
sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/XLPE/PVC/LC/PVC/GSWA/PVC SHIELDED NO OF PAIRS


X 2 X…MM2 500 V MESC YEAR BS EN 50288-7 IEC 60332-3 CAT A LENGTH METER
MARKING

Technical Data:
Temperature Range - 5°C to 50°C (During installation) & - 15°C to 90°C (During Operation)

Voltage Rating 500 Volts


Conductor Resistance (Ω/Km at 20°C) ≤ 12.1 : 12.3 (single pair/triad : multi pair/triad- for 1.5mm2)

Mutual Capacitance (at 1KHz) ≤ 100nF/Km

Capacitance Unbalance (at 1kHz) ≤ 500 pF/500m (Not applicable for single pair/triad)

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance ≥ 5000 MΩ - Km at 20°C (500 V DC 1 minute)

Dielectric Strength Test (Core to core & 2000 VAC or 3000 VDC for 1 minute
core to screen)

Page 15 of 18
Middle East Specialized Cables(MESC)
INSTRUMENTATION CABLE
SINGLE/MULTI PAIR COLLECTIVELY SCREENED, LEAD, ARMORED, FLAME RETARDANT CABLE
CU/XLPE/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-08-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

Flame Behavior Characteristics:


Flame retardant IEC 60332-3 CAT A

Halogen acid gas (outer sheath) MAX. 17% ( IEC 60754-1)

Limiting Oxygen index (outer sheath) ≥ 30% (ASTM D2863)

UV /Sunlight resistance (outer sheath) Passes after 720 hrs. (UL 1581)

Oil Resistance (outer sheath) Passes (ICEA S-73-532)

Min. Bending Radius 20 X Cable Overall Diameter

DIMENSIONAL DATA

THICKNESS (mm)
OUTER SHEATH

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

BEDDING THICK.

APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
(n x mm) (Nom.)

BEDDING (mm)
STRAND x DIA.

LEAD SHEATH
SHEATH (mm)

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. OVER

DIA. (mm)
COLOR

TRIAD

(mm)

(mm)

(mm)

Nom.

Min.
29 0214-01P00150-WLBK8-LV Black 1P 1.5 7x0.53 0.5 0.9 7.8 0.9 9.4 1.0 11.5 0.9 13.3 1.5 1.00 15.9 665

Note: The tolerance on the cable overall diameter shall be +/- 2.5mm up to 30mm & +/- 3.0mm above 30mm.

Page 16 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-09-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

CONSTRUCTION
Conductor Stranded annealed plain copper Class 2 as per IEC 60228.

Insulation XLPE to EN 50290-2-29.

Color Code Multi pair: Black & White with each core numbered.

Pair Construction Two insulated conductors are uniformly twisted to form a pair with 10-14 twists per
meter.

Individual Screen Aluminum backed Mylar tape (25μm) is applied over each pair with an overlap of 25%
with metallic side down in contact with a stranded tinned copper drain wire of 0.5mm²
(7x0.3mm). All pair shields are electrically isolated from each other.

Cabling Required numbers of individually screened pairs are assembled with non-hygroscopic
filler and the assembly is wrapped with a polyester binder tape.

Collective Screen Aluminum backed Mylar tape (25μm) is applied with an overlap of 25% with metallic
side down in contact with a stranded tinned copper drain wire of 0.5mm² (7x0.3mm) run
longitudinally over the binder tape.

Inner Sheath Flame retardant PVC to EN 50290-2-22 in Black color.

Lead Sheath Lead sheath to EN 50307.

Bedding Flame retardant PVC to EN 50290-2-22 in Black color.

Wire Armor A single layer of galvanized steel wire armor to EN 10257-1 is applied over the bedding.

Outer Sheath Flame retardant PVC to EN 50290-2-22. The color of the sheath is as per dimension
sheet.

Printing on the sheath INSTRUMENTATION CABLE CU/XLPE/PVC/LC/PVC/GSWA/PVC SHIELDED NO OF


PAIRS X 2 X …MM2 500V MESC YEAR BS EN 50288-7 IEC 60332-3 CAT A LENGTH
METER MARKING

Technical Data:
Temperature Range -5°C to 50°C (during installation) & -15°C to 90°C (during operation)

Voltage Rating 500 Volts

Conductor Resistance ≤ 12.3 (1.5mm2) Ω/km at 20°C

Mutual Capacitance (at 1kHz) ≤ 100nF/km

Capacitance Unbalance (at 1kHz) ≤ 500pF/500m (Not applicable for single pair/triad)

L/R Ratio ≤ 40 (1.5mm2) µH/Ω

Insulation Resistance ≥ 5000 MΩ-km at 20°C (500 VDC for 1 minute)

Dielectric Strength Test (core to core 2000 VAC / 3000 VDC for 1 minute
& core to screen)

Page 17 of 18
Middle East Specialized Cables (MESC)
INSTRUMENTATION CABLE
MULTI PAIR INDIVIDUAL & COLLECTIVELY SCREENED, LEAD SHEATHED, ARMORED FLAME RETARDANT
CU/XLPE/IS/OS/PVC/LC/PVC/GSWA/PVC
SPECIFICATION: BS EN 50288-7 & IEC 60332-3 CAT A
MESC Doc. No.: TD-175166-09-00 Date: 02.02.2019 Customer Ref.: Email Dated 31 Jan 2019

Flame Behavior Characteristics:


Flame Retardant IEC 60332-3 CAT A

Halogen Acid Gas (Outer Sheath) MAX. 17% (IEC 60754-1)

Limiting Oxygen Index (Outer Sheath) ≥ 30% (ASTM D2863)

UV /Sunlight Resistance (Outer Passes after 720 hrs (UL 1581)


Sheath)
Oil Resistance (Outer Sheath) Passes (ICEA-S-73-532)

Min. Bending Radius 20 x Cable Overall Diameter

DIMENSIONAL DATA

THICKNESS (mm)
OUTER SHEATH

APPROX. OVERALL
DIA. OVER ARMOR
ARMOR WIRE DIA.
DIA. OVER INNER
THICKNESS (mm)

THICKNESS (mm)

THICKNESS (mm)

BEDDING THICK.

APPROX. CABLE
DIA. OVER LEAD
OUTER SHEATH

WEIGHT (kg/km)
INNER SHEATH
(n x mm) (Nom.)

BEDDING (mm)
STRAND x DIA.

LEAD SHEATH
SHEATH (mm)

SHEATH (mm)
MESC CODE

INSULATION
SERIAL NO.

SIZE (mm2)

DIA. OVER

DIA. (mm)
COLOR

TRIAD

(mm)

(mm)

(mm)

Nom.

Min.
30 0414-02P00150-WLBK8-LV Black 2P 1.5 7x0.53 0.5 1.1 13.3 1.0 15.1 1.0 17.2 1.25 19.7 1.6 1.08 22.5 1263
31 0414-05P00150-WLBK8-LV Black 5P 1.5 7x0.53 0.5 1.2 17.2 1.1 19.2 1.0 21.3 1.25 23.8 1.7 1.16 26.6 1768

Note: The tolerance on the cable overall diameter shall be +/- 2.5mm up to 30mm & +/- 3.0mm above 30mm.

Page 18 of 18