Best Practice Guide

Replacing a consumer
unit in domestic and
similar premises

Issue 4
Best Practice Guide In electronic format, this Guide is intended to be
made available free of charge to all interested parties.
Electrical Safety First is indebted to the following
organisaƟons for their contribuƟon and/or Further copies may be downloaded from the websites
Best Practice Guide
support to the development of this Guide: of some of the contributing organisations.
Electrical Safety First is indebted to the following
AESM
BEAMAon and/or The version of this Guide on the Electrical Safety First website
organisaƟons for their contribuƟ
www.aesm.uk.com
www.beama.org.uk
Best Practice Guide
support to the development of this Guide: (www.electricalsafetyfirst.org.uk)
In electronic format, thiswill always
Guide be the latest.
is intended to be made ava
of charge to all interested parƟes. Further copies may be d
Electrical Safety First is indebted Feedback from
on any ofwebsites
the Best Practice
of someGuides is always ng organisaƟon
BEAMAto the following the of the contribuƟ
organisaƟons for their contribuƟ on and/or
BriƟsh Gas
www.beama.org.uk welcome - email: enquiries@electricalsafetyfirst.org.uk
In
Theelectronic
version offormat, this Guide
this Guide on theisElectrical
intendedSafety to be First
madewebs
ava
support to the development of this Guide:
www.briƟshgas.co.uk of charge to all interested
(www.electricalsafety parƟes. Further
rst.org.uk) will alwayscopies
be may be d
the lates
Electrical Safety First is supported by all sectors of the
from
on any theofwebsites
the Best of some
PracƟ of the contribuƟ
ce Guides is always ng organisaƟ
welcome on
– em
BEAMA electrical bpg@electricalsafety
industry, approvals and rst.org.uk
research bodies,
BriƟsh Gas The version offormat,
this Guide on theisElectrical Safety
www.beama.org.uk
BSI Product Services consumerIninterest
electronic
organisations, thistheGuide intended
electrical to be First
distribution madewebs
ava
www.briƟ shgas.co.uk (www.electricalsafety
Electrical rst.org.uk) will
allalways be the
thelates
www.bsigroup.com of charge Safety First is supported
to all interested parƟes. by Further sectors
copiesofmay elecd
be
industry, professional
on any
industry, institutes
ofapprovals
the Best of PracƟ
and and institutions,
ce Guides
research regulatory
is always welcome – em
from the websites some of thebodies,
contribuƟ consumer
ng interes
organisaƟ on
bodies, tradebpg@electricalsafety
and industry
organisaƟ rst.org.uk
ons, theassociations
electrical and federations,
distribuƟ on industry, professio
BriƟsh Gas Services
BSI Product The version of this Guide onbodies,
the Electrical Safety First webs
Certsure trade unions,and and
insƟlocal
tuƟons, regulatory
andFirst
central government. trade and industry asso
www.briƟ shgas.co.uk
www.bsigroup.com Electrical Safety
(www.electricalsafety is supported
rst.org.uk) by allalways
sectors ofthethelates
elec
www.certsure.com federaƟons, trade unions, and localwill and centralbe governmen
industry, approvals and research bodies,
on any of the Best PracƟce Guides is always welcome – em consumer interes
*Electrical Safety First (formerly the NationaldistribuƟ
Inspectionon Council
organisaƟ
*Electrical ons, theFirst
Safety
bpg@electricalsafety electrical
(formerly
rst.org.ukthe NaƟ onal for
industry, professio
InspecƟ on Co
BSI Product Services
Certsure Electrical Installation
and Contracting)
insƟtuƟ
Electrical onis ContracƟ
a charitable
ons, regulatory
InstallaƟ non-profit
bodies,
ng) istrade making
and industry
a charitable assot
non-pro
www.bsigroup.com
City & Guilds
www.certsure.com organisation Electrical
federaƟ
organisaƟ Safety
set up inons,
on trade
1956 Firstinis1956
upunions,
to protect
set supported
usersand
of localbyand
toelectricity
protect allusers
sectors
central
against of the eleca
governmen
of electricity
www.cityandguilds.com the hazardsindustry,
of unsafeof
hazards approvals
and unsound
unsafe and
and research
electrical
unsound bodies, consumer
installations.
electrical interes
installaƟons.
*Electricalons,
organisaƟ Safety
theFirst (formerly
electrical the NaƟ
distribuƟ onal InspecƟ
on industry, on Co
professio
Certsure Electrical
and insƟtuƟ InstallaƟ on ContracƟ
ons, regulatory ng) istrade
bodies, a charitable non-pro
and industry assot
City
EAL & Guilds
www.certsure.com organisaƟ
federaƟ on trade
ons, set upunions,
in 1956and to protect
local and users of electricity
central governmen a
www.cityandguilds.com
www.eal.org.uk hazards of unsafe and unsound electrical installaƟons.
*Electrical Safety First (formerly the NaƟonal InspecƟon Co
Electrical InstallaƟon ContracƟng) is a charitable non-prot
City
EAL & Guilds organisaƟon set up in 1956 to protect users of electricity a
InsƟ tuƟon of Engineering
www.cityandguilds.com
www.eal.org.uk hazards of unsafe and unsound electrical installaƟons.
and Technology
www.theiet.org
EAL Published by
ECA
InsƟ tuƟon of Engineering
www.eal.org.uk Electrical Safety First
www.eca.co.uk
and Technology
NAPIT
www.theiet.org Published
45 Great Guildford by:
Street
www.napit.org.uk London
Electrical Safety First
InsƟtuƟon of Engineering
SE1 0ES Unit 331
and Technology
NAPIT Published
Metal by:
Box Factory
www.theiet.org Email: enquiries@electricalsafetyfirst.org.uk
SPACES
www.napit.org.uk 30 Great Guildford Street
Electrical Safety First
www.thespaces.org.uk London SE1 0HS
Website: www.electricalsafetyfirst.org.uk
Unit 331
Metal
Tel: 0203 Box Factory
NAPIT Published
Electrical Safety First463by:
and 5100
other contributors believe that the
SPACES 30 Great Guildford Street
www.napit.org.uk guidance andEmail:
Electrical bpg@electricalsafety
information
Safety contained
First rst.org.uk
in this Best Practice Guide is
SELECT
www.thespaces.org.uk London SE1 0HS
correct, butUnit
Website: 331
all parties must rely on their ownrst.org.uk
www.electricalsafety skill and judgement
www.select.org.uk Tel: 0203
Metal Box463 5100
Factory
when making use of it.
SPACES Electrical
30 Great
Email: Safety First
Guildford and otherrst.org.uk
Street
bpg@electricalsafety contributors believe that th
Several of the photographs in this Guide have been extracted
SELECT
www.thespaces.org.uk and
London
Neither Electrical informaƟ
SE1 0HS
Safety on contained
First in this Bestassumes
nor any contributor PracƟceany Guide is co
from a superseded Electrical Safety First DVD, courtesy of
www.select.org.uk all parƟeswww.electricalsafety
Website: must rely on their ownrst.org.uk
skill and judgement when
Navigator ProducƟons Ltd. Others were kindly supplied by Nick liability toTel: 0203
anyone 463
any5100
use of it.for
Neitherloss or damage
Electrical caused
Safety Firstbynor
anyany
error
contributor
Blakeley Electrical and Bradford Metropolitan District Council. Electrical Safety First and other contributors believe that th
Several of the photographs in this Guide have been extracted or omission anyin
Email: this Guide,
liability to whether
anyone such
for
bpg@electricalsafety any error
loss or
or omission
rst.org.ukdamage is the by an
caused
SELECT and informaƟ on contained in this Best PracƟ ce Guide is co
from
This isa one
superseded Electrical
of a series of Best Safety
PracƟceFirst DVD,produced
Guides courtesy ofby omission in
result of negligence or this
any Guide,
other whether
cause. Wheresuch error orisomission
reference made is t
www.select.org.uk all parƟeswww.electricalsafety
Website: must rely on their ownrst.org.uk
skill and judgement when
Navigator ProducƟ
Electrical Safety ons in
First* Ltd. Otherson
associaƟ were
withkindly supplied
leading by bodies
industry Nick negligence or any other cause. Where reference is made to
use itofisit.not
to legislation, Neither Electrical Safety
to be considered First
as legal nor any
advice. Any contributor
and all
Blakeley Electrical
for the bene and Bradford
t of electrical Metropolitan
contractors District Council.
and installers, and their it is not toSafety
Electrical be considered
First and as legalcontributors
advice. Any and all that
suchth l
Several of
Several the
of photographs
the photographsin this
in Guide
this have
Guide been
have extracted
been extracted such anyisliability
liability to anyone
disclaimed. for other
any loss or damagebelievecaused by an
customers. disclaimed.
and informaƟ on contained in this Best PracƟ ce Guide is co
This isa one
from of a series
superseded of Best Safety
Electrical PracƟce Guides produced by omission in this Guide, whether such error or omission is t
from a superseded Electrical Safety FirstFirst
DVD,DVD, courtesy
courtesy of of all parƟes must rely on their own skill and judgement when
Electrical Safety
Navigator ProducƟFirst*
ons in associaƟ
Ltd. Otherson withkindly
were leading industry
supplied by bodies
Nick © Electrical negligence
© Safety
Electrical orSafety
any other cause.
Council. May Where
2015 reference is made to
Navigator Productions
for the bene Ltd. Others
t of electrical were kindly
contractors andsupplied by Nick
installers, and their use of it.toCouncil.
it is not Neither June 2019Safety First nor any contributor
Electrical
be considered as legal advice. Any and all such l
Blakeley Electrical and Bradford Metropolitan District Council.
customers.
Blakeley Electrical and Bradford Metropolitan District Council. any liability to anyone for any loss or damage caused by an
disclaimed.
This is one of a series of Best PracƟce Guides produced by omission in this Guide, whether such error or omission is t
Page 3

Replacing a consumer
unit in domestic and
similar premises

1. Aim can provide satisfactory overcurrent protection.


Further, a consumer unit need not be replaced
1.1. The aim of this Guide is to promote best because it does not incorporate RCD protection,
practice by providing practical advice and as there may be ways to provide this protection
guidance for designers, installers, verifiers and other than replacing the consumer unit.
inspectors where the consumer unit or other Similarly, in light of the changes made in
main switchgear is being replaced in domestic Amendment No 3 of BS 7671: 2008, a consumer
or similar premises wired in accordance with unit need not be replaced because its enclosure
earlier versions of the current edition of BS is made of combustible materials such as, for
7671. The guidance is intended to protect users example, plastic. See also Best Practice Guide
and installers against dangerous situations that No 4. Electrical Installation Condition Reporting
could arise from the existing installation. - Classification Codes for Domestic and Similar
1.2. The guidance recognises that the existing Electrical Installations
circuits being connected to a replacement
consumer unit may not comply with the current
edition of BS 7671, as amended. In following
the guidance in this Guide, the installer accepts
this and must be satisfied that all new work on
a particular installation addresses the risks.

1.3. A consumer unit need not be replaced simply


because it has rewireable fuses, cartridge fuses
or older-type circuit-breakers, as these devices
Page 4

2. Limitation 3.5. Installers are reminded of the need to comply


with the relevant parts of the Electricity at
2.1. This guidance applies only to the replacement Work Regulations 1989 when replacing a
of a consumer unit, the reconnection of existing consumer unit. In particular, attention is drawn
circuits and the connection of any new circuits to:
installed during the work.
• regulation 12, Means for cutting off the supply
and for isolation,

3. Legal requirements • regulation 13, Precautions for work on


equipment made dead,
3.1. There is no legal requirement that calls for an
• regulation 14, Work on or near live
existing installation to be upgraded to current
conductors.
standards.
3.6. These regulations mean that, unless a suitable
3.2. However there is a requirement under the
isolating switch has been provided on the
Building Regulations for England and for Wales
supply side of the consumer unit for this
to leave the installation and the building no
purpose, arrangements will need to be made
worse in terms of the level of compliance with
with the Distribution Network Operator for
other applicable parts of Schedule 1 to the
the cut-out fuse to be withdrawn in order
Building Regulations than before the work was
to disconnect the incoming supply for the
undertaken. (Schedule 1 gives the requirements
purpose of isolation. Guidance on safe isolation
with which building work must comply).
procedures is given in Best Practice Guide No 2.
3.3. Similarly, the Scottish Building Standards
Technical Handbooks, which provide guidance
on achieving the standards set in the Building
(Scotland) Regulations 2004, as amended,
require that any work associated with the
replacement of a service, fitting or equipment
by another of the same general type is to a
standard no worse than at present.

3.4. Replacing a consumer unit in domestic premises


in England or Wales is notifiable work under
the Building Regulations. Unless the work is
undertaken by a person registered with an
electrical self-certification scheme prescribed
in the regulations, notification of the proposals
to carry out the work must be given to the
appropriate building control body before the Result of DIY work by a home owner where a 10.5 kW
electric shower was connected to a 45 A circuit-breaker
work begins, or, where the work is necessary using 2.5 mm² cable. (Photo courtesy of British Gas)
because of an emergency, the building control
body should be notified as soon as possible
after completion of the work.
Page 5

4. Requirements of BS 7671 4.5. Circuits that are to be provided with RCD


protection must be divided between a sufficient
4.1. Replacing a consumer unit is an alteration to number of RCDs or otherwise designed as
that installation. Additions and alterations are necessary to avoid hazards and minimise
classed as new work. The work must therefore inconvenience in the event of a fault (Regulations
be designed, erected and verified in accordance 314.1 and 314.2).
with the requirements of the current edition of
4.6. A consumer unit must not be replaced until it has
BS 7671, as amended (Regulation 110.1.2(vi))
been established that:
and must not impair the safety of the existing
installation (Regulation 610.5). On completion • the rating and condition of any existing
of the verification of the work an Electrical equipment, including that of the distributor,
Installation Certificate must be issued will be adequate for the altered circumstances,
(Regulation 644.1). and

4.2. BS 7671 does not require existing circuits to • the earthing and bonding arrangements
be upgraded to current standards in order for necessary for the safety of the alteration are
them to be connected to the outgoing ways of adequate (Regulation 132.16).
the replacement consumer unit.
4.7. Any defects found in the reconnected
4.3. However, circuits that are defective or non- circuits that would not result in immediate
compliant with the requirements of BS 7671 or potential danger must be recorded in the
in a way that would result in immediate or Comments on existing installation section of the
potential danger must not be reconnected to Electrical Installation Certificate issued for the
the consumer unit. replacement of the consumer unit.

4.4. Where a consumer unit is being replaced, Note. Guidance on classification codes attributable to
additional protection by means of RCDs in damage, defects and non-compliances is given in Best
accordance with Regulation 415.1 must be Practice Guide No 4.
provided to the extent required by the current
edition of BS 7671, as amended, such as for:

• socket-outlets (Regulation 411.3.3) 5. Main earthing, main protective


bonding and meter tails
• mobile equipment for use outdoors
(Regulation 411.3.3) 5.1. The installer must verify, as a minimum, that:

• cables concealed in floors, ceilings, walls or a) The main earthing terminal of the installation is
partitions (Regulations 522.6.201 to 203 as connected to an adequate means of earthing via
appropriate) a suitably sized earthing conductor, (see notes
1, 2 and 5), b) The main protective bonding is
• low voltage circuits serving a location
adequate, (see notes 3 and 5), and
containing a bath or a shower or passing
through the zones of the location ( (Regulation c) The meter tails and the distributor’s equipment
701.411.3.3). have adequate current-carrying capacity (see
notes 4 and 5).
• AC final circuits supplying luminaires
d) The polarity of the incoming supply is correct.
Page 6

Notes: is any condition that would cause unwanted


1. A measurement of the external earth fault loop impedance tripping of an RCD, in the existing installation
(Ze) should be carried out at this stage if practicable.
affected by the change. As a minimum the
2. A 6mm² or 10 mm² earthing conductor used with an survey should include:
associated line conductor of 25 mm² could be considered
adequate if the requirements of Regulation 543.1.3 are met.
• making enquiries with the user as to whether
3. A 6 mm² main protective bonding conductor size could there are any known defects, faults or damage,
be deemed adequate where the minimum size required by
Regulation 544.1.1 of BS 7671 is 10 mm², if the bonding • an internal visual inspection of the existing
conductors have been in place for a significant time and
consumer unit to determine, amongst other
show no signs of thermal damage.
things, the type and condition of the wiring
4. 16 mm² meter tails with a 100 A cut-out fuse could be
adequate if the maximum demand of the installation (taking
system used for the installation,
into account diversity and load profile) does not exceed the
current-carrying capacity of the tails, and also provided that • an external visual inspection of other readily
the requirements of Regulation 434.5.2 for protection of the accessible parts of the installation,
tails against fault current are met.
• a measurement of the external earth fault loop
5. Some electricity distributors have requirements regarding
the earthing conductor, main protective bonding conductors impedance (Ze),
and meter tails that exceed the requirements of BS 7671.
Local requirements should be confirmed before starting • a test of circuit protective conductor continuity
work. at the end of each final circuit,

5.2. If any of conditions 5.1.a), b), c) or d) are not • a test of earth fault loop impedance at readily
met, the customer should be informed that accessible socket-outlets and
upgrading is required. If the customer refuses,
the installer should not proceed with the • an insulation resistance measurement of
replacement of the consumer unit until the the whole installation at the consumer unit,
necessary remedial work is undertaken. between the live conductors connected
together and the protective conductor
connected to the earthing arrangement.

6. Reason for change 6.2.3. If any condition that would present an


immediate danger, potential danger, or cause
6.1. The replacement of a consumer unit could be a the unwanted tripping of an RCD is found, the
planned change (see Section 6.2.) or a distress customer should be informed that remedial
change (see Section 6.3.). work is necessary to improve safety.

6.2. Planned change Note:


Immediate danger corresponds to one or more observations
6.2.1. The initial approach of the contractor planning that would warrant a code C1 classification. Potential
the replacement of the consumer unit should danger corresponds to one or more observations that would
warrant a code C2 classification. Guidance on classification
be to encourage the customer to have an codes attributable to damage, defects and on-compliances
Electrical Installation Condition Report found during a periodic inspection is given in Best Practice
prepared on the installation in advance of the Guide No 4.

consumer unit being replaced. 6.2.4. Depending on the extent, the remedial work
6.2.2. If the customer refuses, a pre-work survey could involve considerable additional cost, not
should be carried out to ascertain if there are only in installing new cables or accessories, but
any immediate or potential dangers or if there also in the renewal of decorations, unless the
customer is willing to accept surface wiring.
Page 7

6.2.5. If the customer is unable, or not prepared 7. Risk assessment


to accept the cost of the remedial works,
but still requires a new consumer unit to be 7.1. As stated in Section 6.2.5. where it is proposed
installed, the installer needs to carry out a risk to replace a consumer unit but the customer
assessment as described in section 7 of this is unable or unwilling to accept either the
Guide. cost or disruption of remedial works, a risk
assessment should be undertaken. This is for
6.3. Distress change
the purpose of advising the customer as to the
6.3.1. A distress change occurs when the consumer level of risk that would exist on completion
unit has suffered damage, has become of the proposed work. A disclaimer does not
unusable through overheating, or is in a absolve the installer from responsibility.
dangerous condition with exposed live parts.
7.2. In all cases, the initial approach should
This situation usually requires immediate
be to encourage the customer that
replacement of the consumer unit. However,
remedial action should be taken to
the installation of the consumer unit must still
correct or remove any immediate danger,
comply with the requirements of the current
potential danger or condition that would
edition of BS 7671, as amended. This means,
cause unwanted tripping of an RCD.
amongst other things, that requirements a),
b), c) and d) referred to in Section 5.1. must be 7.3. The risk assessment requires inspection
met. and testing (except to the extent that
these have already been carried out as
6.3.2. It should be explained to the occupant before
part of the Electrical Installation Condition
the consumer unit is replaced that: if an
Reporting or any pre-work survey).
immediately dangerous condition is found in
an existing final circuit, it will not be possible 7.4. The inspection and testing is necessary
to reconnect that circuit until the necessary to establish, for the circuits concerned,
remedial action is carried out, and it will be at least whether or not there are:
necessary to return to the installation to carry
a) any immediate dangers (observations that
out any further work that would have been
would warrant a code C1 classification in an
required had the replacement of the consumer
Electrical Installation Condition Report),
unit been planned. This further work, where
required, must be carried out without delay. b) any potential dangers (observations that
would warrant a code C2 classification in an
Note:
It is recommended that a record of the customer’s Electrical Installation Condition Report), or
agreement to the above is obtained and suitably recorded.
c) any lighting circuits that do not have a
circuit protective conductor (cpc).

d) any circuits wired using lead sheathed


or rubber insulated cables.
Page 8

8. Action following risk 9.2. As a minimum, the following tests should be


carried out on the existing circuits connected
assessment
to the replacement consumer unit:
8.1. If the risk assessment indicates that • A test of the continuity of the protective
there are no immediately dangerous conductor of each circuit, to the point
conditions and no potentially dangerous or accessory electrically furthest
conditions, the replacement of the from the consumer unit and to each
consumer unit may proceed. accessible exposed-conductive-part.
8.2. If any immediately dangerous conditions • A test of the continuity of ring final circuit
or potentially dangerous conditions conductors on all ring final circuits.
are indicated the consumer unit
should not be replaced unless: • A measurement of the combined insulation
resistance of all the circuits. The measurement
• the defects are corrected, or need only be made between the line and
• the defective circuits are left disconnected neutral conductors connected together and
from the replacement consumer unit. the protective conductor connected to the
earthing arrangement, to avoid potential
8.3. If there are any lighting circuits that damage to any electronic components.
do not have a protective conductor,
the recommendations of Section 10 • A confirmtion of the polarity,
of this Guide should be followed. • A test to establish the fault loop impedance
8.4. If there are any circuits wired in lead (Zs), at each accessible socket-outlet and at
sheathed or rubber insulated cables, least one point or accessory in every other
the recommendations of Section 11 circuit, preferably the point or accessory
of this Guide should be followed. electrically furthest from the consumer unit.

Note: Testing of each RCD using both a test


instrument and the integral test facility
9. Inspection, testing and in the device should have been carried
certification out under Section 9.1 of this Guide.

9.1. The alteration or additions themselves (the 9.3. The Electrical Installation Certificate should
installation of the replacement consumer identify, in the Comments on existing
unit and any other new work, such as installation section, any defects which
additional final circuits) should be verified exist in the reconnected circuits for which
fully in accordance with the requirements of improvement is recommended (observations
Section 641 of BS 7671, as amended, and an that would warrant a code C3 classification in
Electrical Installation Certificate, together with an Electrical Installation Condition Report). If
schedules of inspection and schedules of test a full Electrical Installation Condition Report
results, based on the models in Appendix 6 of on the installation has not been provided
BS 7671, should be given by the installer to as part of the work, consideration should
the customer (Regulations 644.1 and 644.3). be given by the installer to stating this on
the certificate with a recommendation that
a Condition Report should be carried out.
Page 9

10. Lighting circuits having no existing consumer unit and all Class I light
fittings and metal plate accessories. If the
protective conductor
resistance value is 1 Ω or less, the equipment
may be considered to be earthed.
10.1. This guidance fully recognises that unearthed
lighting circuits do not comply with BS 7671. 10.5.3. An insulation resistance test should be
applied between the live conductors (line and
10.2. In homes built before 1966, the Wiring
neutral connected together) and the earthing
Regulations current at that time did not
terminal in the consumer unit, with that
require a protective conductor to be
terminal connected to the means of earthing.
taken to every lighting point and related
The resistance should be at least 1 MΩ.
accessory as is the case nowadays.
10.5.4. An insulation resistance test should be
10.3. It is strongly recommended that a lighting
applied between line and neutral connected
circuit having no protective conductor
together and the exposed-conductive-parts
should not be reconnected unless:
of every Class I lighting fitting and metal
• it is rewired with cables having switch plate found to not be earthed by the
a protective conductor, or continuity testing described in Section 10.5.2.
The resistance should be at least 1 MΩ.
• a circuit protective conductor is provided
with a means of connection available 10.5.5 If the circuit does not fulfil the requirements
at all accessible points of that circuit. of either 10.5.3 or 10.5.4. there would be
a risk of electric shock if the circuit were
10.4. Where the customer will not agree to one
to be re-energised. The customer must be
of the remedial measures described in
advised in writing that this danger exists,
Section 10.3. of this Guide the customer
and that the circuit must be disconnected
should be advised that the circuit cannot
from the supply and should not be
be reconnected unless they agree to
connected into a new consumer unit.
have all associated metallic or Class I
fittings or accessories present replaced 10.6. If the customer will not agree to the risk
by all-insulated or Class II alternatives. assessment as described in Section 10.5.
being carried out, they should be advised
10.5. Risk assessment testing for a lighting
that a lighting circuit having no protective
circuit having no protective conductor with
conductor that has metal or Class I switches,
metallic or Class I fittings or accessories
light fittings or other accessories fitted
10.5.1. As an absolute last resort and only where is potentially dangerous (and so would
the customer will not agree to either the warrant a Code C2 classification in an
provision of a protective conductor for the Electrical Installation Condition Report).
circuit or the replacement of all metallic This will mean that the circuit cannot
or Class I fittings or accessories by similar be connected into a new consumer
items of Class II construction, the following unit (see Section 4.3 of this Guide).
risk assessment may be applied, with all
10.7. It should be noted that the protective
testing carried out with the supply to the
measure double or reinforced insulation
consumer unit in question safely isolated:
is only applicable to electrical installations
10.5.2. Carry out a continuity test applied or circuits therein that are under effective
between the earthing terminal in the supervision in normal use to ensure that
Page 10

no change is made that would impair testing. Consideration for the renewal of
the effectiveness of the protective cables should also take into account the
measure (regulation 412.1.2). Domestic requirements for earthing the lead sheath.
and similar premises falling within the
scope of this Guide cannot be considered
to be under effective supervision.
12. Procedure
10.8. Subject to the recommendations of
12.1. The procedures described in this
Section 10.3 to 10.5 of this Guide being
Best Practice Guide are summarised
met, where lighting circuits having no
in the flowcharts in Annex A.
protective conductor are connected to a new
consumer unit, it is strongly recommended
that a warning notice with black letters
on a yellow background should be fixed 13. References to other Best
on or adjacent to the consumer unit: Practice Guides
13.1. This Best Practice Guide makes reference to
the following Best Practice Guides, which
may be downloaded from the websites of
some of the contributing organisations.
The version on the Electrical Safety First
website will always be the latest.

www.electricalsafetyfirst.org.uk
10.9. On completion of the work a record electricalprofessionals/ best-practice-guides/
of any non-compliances, including
• Best Practice Guide No 2 – Guidance
the lack of protective conductors on
on management of electrical safety
the lighting circuits, must made in
and safe isolation procedures for
the Comments on existing installation
low voltage installations.
section of the electrical installation
certificate issued to cover the work • Best Practice Guide No 4 – Electrical installation
condition reporting: Classification codes for
domestic and similar electrical installations.

11. Lead sheathed and rubber


insulated cables
11.1. In all cases where lead sheathed or rubber
insulated cables are encountered it is
strongly recommended that the consumer
unit should not be changed until the cables
are replaced. This is because an unacceptable
level of deterioration of the insulation is
likely to occur whilst the cables are handled
during removal of the old consumer
unit and their re-termination into the
replacement consumer unit and subsequent
Page 11

Annex A
A1 Distress Change

Inial enquiry

change

Customer agrees to
Yes No
a pre-work survey?

Main earthing, main


bonding and Customer agrees to
No No
consumer’s meter remedial work?
tails all adequate?

Yes Yes

Any code C1 or C2 Carry out remedial


observaons or work
anything to cause Leave circuit
unwanted RCD Customer agrees to disconnected or do
Yes No
operaon? remedial work? not change
consumer unit

No

Carry out remedial


Yes
work
Any lead-sheathed
or rubber insulated
cables present? Yes
No

No

Exceponally, does
Does customer
Any Class I circuit meet risk
agree to
Any ligh ng circuits equipment or assessment
Yes Yes replacement by No
having no cpc? accessories in requirements given
Class II equipment
circuit? in Secon 10.5 of
or accessories?
this guide?

No Yes

Yes
Install Class II
equipment /
accessories

Affix presence of
unearthed lighng
No
circuit label to consumer
unit front

Replace consumer unit


and connect only those

compliances

Return to premises at
earliest opportunity Finalise inspecon and
Remedy any code C3 tesng Issue Electrical Nofy Building control
non-compliances (if Issue Electrical Installaon Cerficate (England and Wales)
agreed) Installaon Cerficate
Complete work
Annex A
A2 Planned Change

Inial enquiry

change

Customer agrees to
Yes No
EICR?

Main earthing, main Customer agrees to


bonding and Yes No
a pre-work survey
consumer’s meter
tails are adequate

Customer agrees to
No No
remedial work?

Yes
Carry out remedial
Yes
work

Any code C1 or C2
observa ons or
Customer agrees to
anything to cause Yes No
remedial work?
unwanted RCD
opera on?

No

Carry out remedial


Yes
work
Leave circuit
Any lead-sheathed
disconnected or
or rubber insulated
Do not change
cables present?
consumer unit
Yes

No No

Does customer
Any Class I
agree to
Any lighng circuits equipment or
Yes Yes replacement by No
having no cpc? accessories in
Class II equipment
circuit?
or accessories?
Exceponally, does
circuit meet risk
assessment
No
No Yes requirements given
in Secon 10.5 of
this guide?

Install Class II
equipment /
accessories

Affix presence of
unearthed lighng
circuit label to consumer Yes
unit front

Replace
consumer unit

Issue Electrical Nofy Building


Finalise inspecon
Installaon control
and tesng
Cerficate (England and Wales)
11 22 33
Best Practice Guide Best Practice Guide Best Practice Guide

Best Practice Guide Best Practice Guide Best Practice Guide

Guidance on the Connecting a


Guidance
management of on the Connecting a

44 55 66
microgeneration
Replacing
unit in domestic anda consumer
Replacing a consumer
electrical safety system to a domestic
similar premises
unit in domestic and management
and safe isolation
procedures for
of microgeneration
or similar electrical
installation in

similar
Issue 4 premises electrical
low voltage
installations
safety system to a domestic
parallel with the
main supply
and
Issue 4safe isolation orIssuesimilar
4 electrical
procedures for installation in
low voltage parallel with the
Issue 4
installations main supply
Best Practice Guide Best Practice Guide Issue 4
Best Practice Guide Issue 4

Best Practice Guide Best Practice Guide Best Practice Guide

77 88 99
Electrical installation Electrical installations Portable and stationery
Electrical
condition reporting: installation Electrical installations
and their impact on
the fire performance of Portable
private rented and stationery
appliance testing in
Classification codes for
condition
domestic and similar reporting:
electrical installations
and their impact on
domestic premises used
as single family houses appliance
accomodation
testing in
the
Issuefire performance of private rented
Issue 3
Classification codes for
3
Issue 5

domestic and similar domestic premises used accomodation


electrical installations as single family houses
Issue 3
Issue 3
Best Practice Guide Issue 5
Best Practice Guide Best Practice Guide

Best Practice Guide Best Practice Guide Best Practice Guide

Test instruments for Selection and use of Safe installation of


Test instruments
electrical installations: for Selection and use of
plug-in socket-outlet
test devices
Safe installation
retrofit LED lamps of
Accuracy and
electrical
consistency installations: plug-in
Issue 3
socket-outlet retrofit
Issue 1
LED lamps
Accuracy
Issue 3 and test devices
consistency Issue 1
Issue 3
Issue 3

The latest versions of all the BestPracticeGuides


are available to download from www.electricalsafetyfirst.org.uk

Electrical Safety First, 45 Great Guildford Street, London SE1 0ES

Email: enquiries@electricalsafetyfirst.org.uk

Web: www.electricalsafetyfirst.org.uk

Registered Charity (England and Wales) No.257376 (Scotland) No. SCO39990

Electrical Safety First is the UK charity dedicated to reducing


deaths and injuries caused by electrical accidents. Our aim is
to ensure everyone in the UK can use electricity safely