Professional Documents
Culture Documents
18th Ammendment 2 Pocket Notes
18th Ammendment 2 Pocket Notes
?
CKET GUIDES ATION
WHAT ARE PO S AND LEGISL
DATE WITH REGULATION
KEEP YOU UP-TO-
FERENCE GUIDES TO
CHNICAL RE
35 HANDY TE
GUIDES UPDATED TO
BS 7671:2018 + A2:2022
* Zone 1
Zone 2
Outside
zones
2.25 m
Zone 0
0.6 m
The space underneath the bath is
zone 1 if accessible without the use
of a tool, or outside the zones if
accessible only with the use of a tool
Zone 1
2.25 m Zone 2
Outside
zones
Zone 0
0.6 m
Notes:
All low voltage circuits either serving the location or passing through
zones 1 and/or 2, but not serving the location must have additional
protection provided by one or more RCDs that have a rated residual
operating current (IΔn) not exceeding 30 mA (701.411.3.3).
roviding all final circuits of the location have additional protection,
P
meet the requirements for automatic disconnection and the
installation is fitted with effective protective equipotential bonding,
then supplementary equipotential bonding may be omitted
(701.415.2).
OFF OFF
MAIN
SWITCH OFF
Step 2
Prove the correct operation of a suitable voltage detection
instrument, see Note 5, against a known voltage source, such as
that illustrated.
OFF OFF
MAIN
SWITCH
OFF
Step 4
Prove the voltage detection instrument again against the known
source to check that it was functioning correctly when testing for
the presence of voltage.
L1 L2
150 mm
Cooker
control
switch
Entrance
to Room 2
Cooker
connection
point
13 A socket-outlet
this side
Light switch
reverse side
150 mm
Light switch
this side
Entrance
from
Room 1
13 A socket-outlet
reverse side
100 mm or less
Contractors are advised to always check for
installed cables, or gas or water pipes before
carrying out work on or in traditional walls and
partitions. A cable/pipe detector can help
identification of installed cables or pipes.
THIS IS TO BE AVOIDED
100 mm
0.6 m
0.6 m
Cross-section through a flat type cable, cable overall diameter indicating the major axis.
**
HA
Available from
www.shop.niceic.com
Main protective
bonding conductors
Water Gas
meter meter
Metallic
Main Earthing Terminal pipework
Note 1: Table 54.8 should be used as a guide only, and the specific
minimum requirements of the electricity distributor should
always be obtained with regard to the selection of main
protective bonding conductors.
Note 2: The PEN referred to in Table 54.8 is the neutral conductor
of the electricity distributor’s low voltage network. It is
not the neutral conductor on the consumer’s side of the
supply terminals, which may have a different csa.
The advice of the electricity distributor should always be obtained
where it is proposed to use a main protective bonding conductor
of a metal other than copper.
Minimum csa of A S 16
the corresponding
protective conductor
B
(mm2)
The csa of the protective conductor must be not less than required
by Row A or Row B of the above table, as applicable.
Row A should be used where the protective conductor is of the
same material as the associated line conductor.
Row B should be used where the protective conductor is not of the
same material as the associated line conductor.
Where row B is used, values of k1 for the line conductor and k2
for the protective conductor are required. The values of k1 can
normally be determined from Table 43.1 of BS 7671, and of k2 from
Tables 54.2 to 54.6, as applicable (data reproduced in part next).
Note: The data from Table 54.6 of BS 7671 is outside the scope of
this pocket guide.
Where:
S is the nominal csa of the protective conductor in mm2.
I is the value in amperes (rms for AC) of the fault current for
a fault of negligible impedance, which can flow through the
associated protective device, due account being taken of
the current limiting effect of the circuit impedances and the
limiting capability (I2t) of that protective device.
Where:
I the fault current (I) at the furthest point in the circuit.
U0 the nominal voltage.
Zs the measured value of earth fault loop impedance corrected
to allow for the circuit conductors being at their normal
operating temperature.
The value of operating time (t) for the disconnecting device, for use
in the adiabatic equation, can often be found from the time/current
characteristic for the device. An example of determining t is given
next.
1
TIME, SECONDS
0.1
6A 20 A 32 A 50 A 80 A 125 A 200 A
10 100 1000 I 10000
PROSPECTIVE CURRENT, r.m.s. AMPERES
0 No protection No protection
50 mm diameter
1 Back of hand
solid foreign object
Finger
12.5 mm diameter
2 Standard joint test (12 mm
solid foreign object
diameter, 80 mm length)
2.5 mm diameter
3 Tool
solid foreign object
1.0 mm diameter
4 Wire
solid foreign object
5 Dust-protected Wire
6 Dust-tight Wire
0 No protection
Fuses
Rated BS 88-2 BS 88-3
BS 88 (gG) BS 1361 or
Current BS 3036 Fuse systems Fuse system
Parts 2 & 6 BS 1362
(A) E and G* C
0.4 s 5s 0.4 s 5s 0.4 s 5s 0.4 s 5 s 0.4 s 5s
2 26.48 35.20
3 12.48 17.60
4 12.48 16.80
5 7.94 12.48 7.28 13.44 7.94 11.68
6 6.47 10.28 6.24 9.60
10 3.88 5.63 3.72 5.44 3.71 5.45
13 1.84 2.91
15 2.49 3.80 1.94 4.06
16 2.05 3.17 1.94 3.20 1.84 3.12
20 1.34 2.20 1.28 2.12 1.34 2.91 1.34 2.24 1.54 2.56
25 1.08 1.74 1.03 1.76
30 0.87 1.39 0.83 2.00
32 0.79 1.39 0.79 1.36 0.72 1.28
40 0.62 1.02 0.6 1.04
45 0.43 0.72 0.44 1.20 0.45 0.80
50 0.45 0.79 0.45 0.79
60 0.28 0.52 0.32 0.85
63 0.34 0.62 0.35 0.62 0.28 0.54
80 0.23 0.43 0.21 0.37 0.44 0.40
100 0.17 0.31 0.14 0.27 0.14 0.40 0.33 0.30
125 0.12 0.24 0.25
160 0.09 0.19 0.21
200 0.07 0.14 0.14
Earthing conductor
Distributor’s earthing
facility (TN system)
or installation Means of earthing
earth electrode
(TT or IT system)
SAFETY ELECTRICAL
CONNECTION Earthing
DO NOT REMOVE SAFETY ELECTRICAL
conductor CONNECTION
DO NOT REMOVE
Non-metallic
conduit or duct
≤0.25L ≤0.2L
≤0.125D
≥0.07L ≥0.1L
≤0.15
0.5D 0.5D
D ≤250
≥100 mm
L
≤0.4L ≤0.4L
≥0.25L ≥0.25L
0.5D 0.5D
D ≤250
≤0.25D
≤0.4L
≥0.1L
0.5D 0.5D
D ≤150
Do not make
holes in timber
Ceiling board
Minimum 50 mm
to top or bottom,
as appropriate, of joist 3. Suitable mechanical protection
*The titles of the British Standards given in Regulation 522.6.204 can be found
in Appendix 1 of BS 7671.
Fir
Fir Ex e
it
Ex e
it
PU
SH
TO
O
PE
N
PU
SH
TO
O
PE
N
e
Firit
Ex
Final Exit
Corridors – Stairways –
Within 2 m Within 2 m
horizontal horizontal
distance of distance of
a change of change in floor
direction in an level or stairs
escape route. (each tread to
receive direct
light).
Fir
Ex e
it
Escalators – Toilets –
Should not be Install in all toilets
used as an exceeding 8 m2
escape route, area or where
but require the natural light is not
same illumination present.
to protect users
when the supply
fails.
INSTALLATION MUST BE
CONNECTED TO EARTH
50
0V
25
0V
20
OF 00
F MΩ
Co 20
nt 0M
1M Ω
Ω
20
20 0Ω
TE Ω
ST
ELV
LOOP Pfc mA
2000 A
200 A
100 300
30
kA
20
10 500
00
20
20 1A
0Ω
Ω
MΩ 20 Ω
TEST
OFF
1kV
V
500
0V
25
V
AUTO MEM
100
MΩ RCD NULL
Temporary link
ELV
LOOP Pfc mA
2000 A
200 A
100 300
30
kA
20
10 500
00
20
20 1A
0Ω
Ω
MΩ 20 Ω
TEST
OFF
1kV
V
500
0V
25
V
AUTO MEM
100
MΩ RCD NULL
Type AC
Type A
Type F
I - ON
63 A
Type B
Nature of
Have appropriate measures for any particular fire
processed
522.14 risks to minimise fire spread in accordance with
or stored
Section 422 and Section 527, respectively.
materials
Have appropriate supports to avoid excessive stress
Building in the event of structural movement. A flexible wiring
522.15
design system may be required where such movement
is expected.
Table 1. Typical maximum Earth Fault Loop Impedance values for existing
connections (applicable to all distributed system earth arrangements)
Typical values of EFLI under
normal network conditions
Maximum
Installation voltage
service Proportion of
and type
capacity (A) EFLI (Ω) installations where
EFLI will occur (%)
< 0.34 90
230 V single-phase
100 < 0.64 98
(residential premises)
> 0.64 2
150 ≤ 0.42
400 V three-phase 200 ≤ 0.31
(large residential,
300 ≤ 0.21 95
commercial and light
industrial premises) 400 ≤ 0.16
600 ≤ 0.10
Load
P R1
Ze
Combined
N&E
R2
Source Earth
Load
P R1
Ze
N
E R2
Source Earth
Fig 2. TN-S System
1
12
23 24
13 14 15
22
21
1
6
0 17
18 19 2
4 9
5
PWR
MAIN
HAN
SWITCH
WA N
4
2 11 8
MET
3
12
1
DB equipment
1 Service cable
2 Cut-out (or main or DB fuse)
3 DB earth terminal
Supplier equipment
4 Meter tails (cut-out to meter and meter to timeswitch)
5 Communications hub if fitted (may be within the meter)
6 Meter
7 Timeswitch (if fitted)
Customer equipment
8 Meter tails (between the meter/timeswitch and the
Customer equipment)
9 Customer isolating switch (if fitted)
10 Customer consumer unit
11 Customer earthing conductor (and earth block if fitted)
12 Meter board (and external meter box if fitted)
100A
FUSE
SAFETY ELECTRICAL
EARTH
DO NOT REMOVE
SAFETY ELECTRICAL
EARTH
DO NOT REMOVE For illustration purposes
only, manufacturer’s
instructions must
be followed
System 1
Background ventilators and intermittent
extract fans
System 2
Passive stack ventilation
System 3
Continuous mechanical extract
System 4
Continuous mechanical supply and
extract with heat recovery
For further information –
England & Wales
• Approved Document F (Ventilation)
• Domestic Ventilation Compliance Guide
Scotland
• Technical Handbook – Domestic
• Building Standards Supporting Guidance Domestic Ventilation
2nd Edition
Commissioning
Work Notifiable
Notice*
Emergency repairs to ventilation system
No Yes
(no changes made to ventilation system)
Note: In such cases it will be necessary for the work to comply with the
relevant requirements and to give a notice to the BCB at the earliest
opportunity.
* A commissioning notice is always required where testing and adjustment
must be carried out to ensure the system operates efficiently.
continues...
Note: S
uch as replacement of parts or unit on a like-for-like basis (using
existing cabling), or the addition of an output or control device where
testing and adjusting is not possible or would not affect the system’s
energy efficiency
System 1 installation (no open flued
No Yes
combustion appliance installed)
Note: P
rovision of a self-contained mechanical ventilation appliance provided
that any electrical work is exempt from a requirement to give advance
notice to a BCB, and testing and adjustment is not possible or would
not affect its energy efficiency, and the appliance is not installed in a
room containing an open flued combustion appliance. Examples might
be a cooker hood, a bathroom extract fan or a room air-conditioning
unit, which cannot be adjusted from their factory settings.
* A commissioning notice is always required where testing and adjustment
must be carried out to ensure the system operates efficiently.
continues...
Rear knock-out
NOT permitted
to be used
External Medium-Pressure
Meter Installation
PEB connection
within meter box
Meter outlet
ECV
External Low-Pressure
Meter Installation
Acceptable PEB
connection within
meter box
Preferred PEB
connection
within 600 mm
of entering property
External Internal
3. Standard ECV
3
2
4. Steel fitting incorporating electrical insulation
4
5. Steel gas service with applied corrosion
protection (other forms of corrosion protection
5
to that shown and which are not visible may
also be utilised)