THIS ROOF MOUNTED PHOTOVOLTAIC (PV) SYSTEM IS TO BE INSTALLED AT THE SINGLE-FAMILY DWELLING IN PHOENIX, ARIZONA.
THE ENERGY PRODUCED BY THE PV SYSTEM SHALL BE INTERCONNECTED WITH THE UTILITY GRID THROUGH THE EXISTING ON-SITE ELECTRICAL EQUIPMENT VIA
A BACK-FED BREAKER IN THE MAIN SERVICE PANEL. THIS PROJECT DOES NOT INCLUDE STORAGE BATTERIES.
Sheet Title:
Sheet Number:
T1.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS
FENCE
PV AZIMUTH
180°
BRANCH #2 (10)
PV SYSTEM UTILITY
36" ACCESS PATHWAYS DISCONNECT SWITCH
19° PITCH (V.I.F.) PV PRODUCTION UTILITY METER
3/4" EMT
TO BE TRIMMED OR
UTILITY HAS 24-HR UNRESTRICTED REMOVED AS NECESSARY
ACCESS TO ALL PHOTOVOLTAIC SYSTEM
COMPONENTS LOCATED AT THE
SERVICE ENTRANCE. Sheet Title:
PROPERTY LINE
WORKSPACE IN FRONT OF THE AC
ELECTRICAL SYSTEM COMPONENTS SHALL BE IN
Sheet Number:
ACCORDANCE WITH APS & NEC REQUIREMENTS.
FOR APS REQUIREMENTS, REFERENCE SECTION DRIVEWAY A1.0
300 OF THE APS ESRM & SECTION 8.2 OF THE APS Sheet Size:
INTERCONNECTION REQUIREMENTS. ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
REFERENCE SECTION 301.15 OF THE ANDREW DOBBINS
APS ESRM FOR ELECTRIC METER SEPARATION
BETWEEN WATER & GAS.
PV AZIMUTH
180°
28'-1"
2'
TYP.
6' MAX. AC Modules Project:
RIDGE
PHOENIX, AZ 85027
Engineering Approval:
3' MIN.
Sheet Title:
Sheet Number:
A1.1
EAVE Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
21'-1" ANDREW DOBBINS
2 ft 4 ft 8 ft
PHOENIX, AZ 85027
Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF
Engineering Approval:
STRUCTURAL CALCULATIONS
QT Y WEIGHT EA. TOTAL
PV MODULE 20 x 41.0 LBS = 820 LBS
RACKING RAIL 140 x 1.30 LB/FT = 182 LBS
ATTACHMENT 28 x 4.0 LBS = 112 LBS
TOTAL WEIGHT: 1114 LBS 2
ARRAY AREA: 351 SQ. FT. -
REVISIONS
DEAD LOAD: 3.2 PSF DESCRIPTION DATE REV
8 in 16 in 32 in
MOUNTING PLAN VIEW ORIGINAL 10/25/2017 A
POINT LOAD: 39.8 LBS 1
SCALE: 1" = 16"
Sheet Title:
Sheet Number:
A2.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS
NOTE: THE CONDUCTORS BETWEEN ALL ROOF MOUNTED CONDUIT PHOENIX, AZ 85027
THE AC DISCONNECT AND THE PV MUST BE MOUNTED A MINIMUM
BREAKER MUST BE A MINIMUM OF 1/2" ABOVE THE ROOF. 3 5 6 8 Project Details:
OF 4' IN LENGTH. MAIN SERVICE PANEL 6.90 kWstc, 6.40 kW AC
240 VAC, 200 A, 1-PH. AHJ: PHOENIX, CITY OF
AC1 CONDUCTORS NOT LOCATED
UTILITY METER
ALL WIRE TERMINALS SHALL BE RATED UNDERNEATH MODULES MUST BE PROTECTED BY 3/4" EMT. Engineering Approval:
MINIMUM 75° C. 100 A / 2P
TO UTILITY GRID
TO EXISTING LOADS
3 7
2 3 2 3 9
AC COMBINER BOX
PV SYSTEM PV PRODUCTION PV SYSTEM UTILITY
AC DISCONNECT UTILITY METER DISCONNECT SWITCH
4 35 A / 2P
JUNCTION BOX
PV AC MODULES AC3 AC3 AC3 AC3
20 A / 2P
(1) BRANCH OF
REVISIONS
(10) PV AC MODULES DESCRIPTION DATE REV
AC1
ORIGINAL 10/25/2017 A
PV AC MODULES
20 A / 2P
(1) BRANCH OF
(10) PV AC MODULES
AC1 AC2
Sheet Title:
120% Rule Calculation per NEC 705.12(D)(2) WIRE AND CON DUIT SCHEDUL E
Ma in Bus ba r Ra ti ng: 200 Amps CON D CON D CON D GN D GN D GN D CON DUIT CON DUIT ES T.
TAG
Mai n Service Brea ker Ra ti ng: 100 Amps QTY S IZE TYP E QTY S IZE TYP E S IZE TYP E DIS T.
PV Ba ckfeedi ng Current: 33.3 Amps AC1 2 AWG #12 THWN-2 1 AWG #8 THWN-2 N/A N/A 20
MAIN MAX PV AC2 4 AWG #10 THWN-2 1 AWG #8 THWN-2 3/4" EMT 50
BUSBAR x 120% - =
BREAKER BREAKER AC3 3 AWG #8 THWN-2 1 AWG #8 THWN-2 3/4" EMT 30
240 - 100 = 140 Array Configuration
ON ROOFTOP BLDG EXTERIOR WALL, INSIDE FENCE
Array Power (kWstc): 6.90 AC Modules Project:
3 7
(N) AC COMBINER BOX Micro-Inverter Quantity: 20
PHOENIX, AZ 85027
SQ D HOM612L100RB Branch Circuit Quantity: 2
(OR EQUIVALENT)
240 VAC, 100 A Length of Branch #1: 10 Project Details:
SUNPOWER NEMA 3R, UL LISTED
4 6.90 kWstc, 6.40 kW AC
AC PV MODULE Length of Branch #2: 10 AHJ: PHOENIX, CITY OF
(N) JUNCTION BOX L1
NEMA 4X, UL LISTED L2 Total Module Quantity: 20
TO PV SYSTEM
Engineering Approval:
L1 L1 N AC DISCONNECT
L2 L2 G AC System Summary
20 A
AC1 L1 Sys tem Vol tage: 240 VAC
10 2 1 AC3
G L2
690.8(A) Ma x Current: 26.6 Amps
BRANCH #1
690.8(B) Ma x Current: 33.3 Amps
20 A
L1 L1 L1
G G G L2 L2 L2 TO UTILITY GRID
BRANCH #2 AC1 G
10 2 1 REVISIONS
G G (2) AWG #14 CU
AC2 G DESCRIPTION DATE REV
IN MIN. 1/2" EMT L1 L2 N
BRANCH N ORIGINAL 10/25/2017 A
LENGTH INDICATOR (E) BI-DIRECTIONAL
UTILITY METER
1-PHASE, 240 V
L1 L2 N
CT SUNPOWER PV L1
TO ETHERNET OR (E) BONDING JUMPER
NOTE: THE CONDUCTORS BETWEEN PLC (POWER LINE LAN SUPERVISOR L2 PER NEC 250.92(A)(2)
COMMUNICATION)
THE AC DISCONNECT AND THE PV L1 L2 N
SPLIT-CORE CT'S
Sheet Title:
CT
BREAKER MUST BE A MINIMUM BLDG EXTERIOR WALL, OUTSIDE FENCE (E) MAIN SERVICE DISCONNECT
CT
Sys tem Vol ta ge: 240 VAC Voc Temp Coeff: -0.27 %/°C 120% Rule Calculation per NEC 705.12(D)(2) Project Details:
6.90 kWstc, 6.40 kW AC
690.8(A) Ma x Current: 26.6 Amps AHJ: PHOENIX, CITY OF
Ma in Bus ba r Ra ting: 200 Amps
690.8(B) Ma x Current: 33.3 Amps Ma in Service Brea ker Ra ting: 100 Amps Engineering Approval:
PV System Maximum Voltage Calculation per NEC 690.7(A) PV Ba ckfeedi ng Current: 33.3 Amps
Loca l Record Low Temp: -3 °C Da ta Source: PHOENIX SKY HARBOR INTL AP MAIN MAX PV
BUSBAR x 120% - =
25°C - Voc Voc Ma x # of Tempera ture
BREAKER BREAKER
Voc Temp
x Record +1 = Correcti on Correcti on x Voc x Modules = Corrected Open 240 - 100 = 140
Coeffi ci ent
Low Temp. Fa ctor Fa ctor i n Series Ci rcuit Vol ta ge
REVISIONS
0.27%/°C x 28°C +1 = 1.076 1.076 x 68.2 x 1 = 73.4 Volts DC DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A
Sheet Title:
Sheet Number:
E1.1
Sheet Size:
CONDUCTOR SPECIFICATIONS AMPACITY CHECK #1 AMPACITY CHECK #2 VOLTAGE DROP ANSI B - 17" x 11"
CIRCUIT AMPACITY @ REQUIRED REQUIRED DERATED ESTIMATED DESIGN & DRAFTING BY:
TAG CIRCUIT ORIGIN TEMP. TRADE CONDUCTOR VOLTAGE ANDREW DOBBINS
DESTINATION MATERIAL RATING 30°C PER AMPACITY < AMPACITY < CONDUCTOR ONE-WAY
SIZE AMPACITY DROP
310.15(B)(16) 690.8(B)(1) 690.8(B)(2) AMPACITY DISTANCE
AC1 MICRO-INVERTER JUNCTION BOX COPPER 90°C AWG #12 30 Amps 16.6 Amps < 30.0 Amps 13.3 Amps < 26.1 Amps 20 ft 0.44%
AC2 JUNCTION BOX AC COMBINER BOX COPPER 90°C AWG #10 40 Amps 16.6 Amps < 40.0 Amps 13.3 Amps < 20.8 Amps 50 ft 0.67%
Reviewed & Approved by:
AC3 AC COMBINER BOX PV BREAKER COPPER 75°C AWG #8 50 Amps 33.3 Amps < 50.0 Amps 26.6 Amps < 29.0 Amps 30 ft 0.52% EH
WARNING WARNING
REQ'D BY: NEC 690.5(C) REQ'D BY: NEC 690.13(B) REQ'D BY: NEC 690.17(E) REQ'D BY: NEC 690.31(G)(3) REQ'D BY: NEC 705.12(D)(3)
1 2 3 4 5
APPLY TO: APPLY TO: APPLY TO: APPLY TO: APPLY TO:
INVERTER(S), IF NOT APPLIED BY MFR AC DISCONNECT SWITCHES DISCONNECTS, FUSES, CIRCUIT BREAKERS JUNCTION BOXES, RACEWAYS, CABLE TRAYS, ANY/ALL ELECTRICAL PANELS
CONDUIT BODIES WITH AVAILABLE OPENINGS, CONNECTED TO MULTIPLE POWER SOURCES
EVERY 10', WITHIN 1' OF TURNS/PENETRATIONS
AC Modules Project:
PHOENIX, AZ 85027
Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF
Engineering Approval:
REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A
Sheet Title:
Sheet Number:
D1.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS
PHOENIX, AZ 85027
Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF
Engineering Approval:
REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A
Sheet Title:
Sheet Number:
D2.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS
PHOENIX, AZ 85027
Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF
Engineering Approval:
REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A
Sheet Title:
Sheet Number:
D3.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS
PHOENIX, AZ 85027
Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF
Engineering Approval:
REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A
Sheet Title:
Sheet Number:
D4.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS
PHOENIX, AZ 85027
Project Details:
6.90 kWstc, 6.40 kW AC
AHJ: PHOENIX, CITY OF
Engineering Approval:
REVISIONS
DESCRIPTION DATE REV
ORIGINAL 10/25/2017 A
Sheet Title:
Sheet Number:
D5.0
Sheet Size:
ANSI B - 17" x 11"
DESIGN & DRAFTING BY:
ANDREW DOBBINS
N
KEY: