Professional Documents
Culture Documents
Flexural Strengthening of Prestressed Bridge Slabs With FRP Systems
Flexural Strengthening of Prestressed Bridge Slabs With FRP Systems
76 PCI JOURNAL
west abutment east abutment
westpiers eastpiers
bearing bearing
Precast concrete
bearing piles
Cross section
1 ft’0.3048m Plan
Modelled for testing
January-February 2002 77
r’ 2
r-
6 sets 3” 3 @5”
1
No 6 sets. @3”
4 No. 5
“Iw
II I
Ifl +[ j I I
12-0.6” diam ter strands 5No.5
I IIII -
16”
No.3 @ ioirt___
L2
5’-ll” 8-00” 8’-OO” 5’—ll”
5,—il,’ 16’00” 5’—ll”
27’-lO”
Sec. Elevation
1 ft’0.3048m
1 in.=25.4mm
4 No. 5 4No.5
E H FFFTI4J
---
l No. 3@ 3”
5 No. 5
16” * ..
4 I— No. 3@ 5”
5No.5
31
L 3’-ll” -
No. 3@ 3”
No.3 @“
termediate pier columns of a bridge The number and layout of the ten (254 mm) on center in the simply sup
constructed in the early 1970s in Win dons were selected to have the same ported span. Reinforcement details of
nipeg, Manitoba, Canada. The bridge stress level of the bridge under service the specimens are shown in Fig. 2.
consists of four spans, as shown in load conditions. The critical bending Bursting reinforcement was pro
Fig. 1, and was designed for moments for the bridge were evalu vided using six pairs of No. 3 looped
AASHTO HSS2O truck design load ated based on a linear elastic finite ele bars spaced at 3 in. (75 mm) on center.
5 The thickness of the bridge slab
ing. ment analysis using a commercial Twelve 0.6 in. (15 mm) seven-wire
along the spans is 32 in. (810 mm), computer program, SAP2000.
6 The strands were used for post-tensioning
cast in place, partially voided and loss of the prestressing force was cal the specimens. The compressive
post-tensioned. The solid slab over the culated according to the current strength of concrete after 28 days
intermediate pier columns is post-ten AASHTO Specifications.
5 ranged from 6500 to 7200 psi (45 to
sioned transversely to resist the nega The specimens were reinforced with 50 MPa) for the three slabs.
tive moments at the columns and the four No. 5 mild steel bars on the top
positive moment at midspan. surface and five No. 5 mild steel bars
STRENGTHENING
To simulate the combined effect of on the bottom surface. The bars have a
high flexural and shear stresses at the yield strength of 60 ksi (400 MPa) and
TECHNIQUES
intermediate supports of the bridge, an elastic modulus of 29,000 ksi (200
three half-scale models of the solid GPa). The number of bars in the top Slab Si
slab designated as Si, S2, and S3 were surface was selected to represent the One cantilever of Slab Si was
constructed. The support configuration same reinforcement ratio in the can strengthened using near surface
of the specimens was designed to ex tilever portion of the bridge. mounted Leadline CFRP bars while the
amine the FRP repair system at the Shear reinforcement consisted of other cantilever remained unstrength
zones of maximum negative moment No. 3 U-shaped stirrups. The stirrups ened. The Leadline bars were produced
at the support, which coincides with were spaced at 5 in. (127 mm) on cen by Mitsubishi Chemicals Corporation,
the maximum shear. ter in the cantilever span and 10 in. Japan. The bars have a modulus of
78 PCI JOURNAL
elasticity of 21,000 ksi (147 GPa) and
an ultimate tensile strength of 285 ksi
(1970 MPa) as reported by the manu
facturer. Based on equilibrium and
compatibility conditions, six 3/ in. (10
mm) diameter Leadline CFRP bars
were used to achieve a 30 percent in
crease in the ultimate load carrying ca
pacity of the slab.
To strengthen the cantilever slab
using near surface mounted bars,
grooves had to be cut on the top sur
face of the concrete. The location of Fig. 3. Cutting
the grooves was first marked using a grooves for near
chalk line. The grooves were 8 in. surface mounted
(200 mm) apart. A concrete saw was CFRP bars.
used to cut six grooves approximately
0.6 in. wide and 1.2 in. deep (16 x 30
mm) at the tension surface of the can grooves and gently pressed to displace Slab S2
tilever as shown in Fig. 3. the bonding agent as shown in Fig. 4. The second slab, S2, was used to in
The groove ends were widened to The grooves were then filled com vestigate the performance of both near
provide wedge action and to prevent pletely with the epoxy. Quality control surface mounted and externally
possible slippage of the bars. Tapering was achieved through continuous in bonded CFRP strips in strengthening
the ends of the grooves was intended spections and measurements during of concrete bridges. Recently, test re
to induce inclined frictional forces at the installation procedures. suits of near surface mounted CFRP
the concrete-epoxy interface. These in After completion of the first two strips reported good and uniform bond
clined forces provided radial confining tests on both cantilevers, the resulting distribution of the strips to the con
forces on the bars and, consequently, cracks were injected with epoxy. crete and full utilization of the
increased the pullout resistance. Based on an equilibrium and compati strength of the strip up to rupture.
7
Kemko 040 epoxy adhesive was bility approach, ten /8 in. (10 mm) di The analysis indicated a need of six
used for bonding the CFRP bars to the ameter Leadline CFRP bars were used CFRP strips, 2 in. wide and 0.055 in.
surrounding concrete. The epoxy was to achieve a 30 percent increase in the thick (50 x 1.4 mm), to achieve a 30
produced by ChemCo Systems, Inc., ultimate capacity of the midspan sec percent increase in the ultimate capac
United States. The adhesive is com tion of the simply supported slab. The ity of the cantilever slab.
monly used for grouting bolts, dowels, grooves on the bottom surface were The first cantilever was strength
and steel bars in concrete. The epoxy 4.7 in. (120 mm) apart. The same pro ened using six externally bonded
was pressure injected into the grooves cedures as described before for cut CFRP strips. The concrete substrate
to cover two-thirds of the groove ting the grooves and placing the bars was prepared by grinding the surface
height. The bars were placed in the were applied. at the locations of the strips. The
10”
0.6”
1 ‘,,
1 in. =25.4 mm
January-February 2002 79
Fig. 5. Bonding CFRP strips to surface.
epoxy was then placed over the strips The CFRP strips were produced by Slab S3
and on the concrete surface. Finally, S&P Clever Reinforcement Company,
A widespread method for the reha
the strips were placed on the concrete Switzerland. The strips had a modulus
bilitation of concrete structures is the
surface and gently pressed into the of elasticity of 21,800 ksi (150 GPa)
epoxy using a ribbed roller as shown and an ultimate tensile strength of 290 externally bonded CFRP sheets. This
in Fig. 5. ksi (2000 MPa) as reported by the method can be seen as a state-of-the-
The second cantilever was strength manufacturer. art technique despite some detailing
ened also using six CFRP strips in After testing both cantilevers, the problems and design aspects that
serted into grooves cut at the top sur areas above the supports were sub could influence the failure modes.
face of the concrete. In order to insert stantially cracked. To enable further To investigate the effectiveness of
the strips within the concrete cover testing of the midspan, the cracks this strengthening method in compari
layer, the strips were cut into two were injected similar to Slab SI. son to the three previously prescribed
halves, each 1 in. (25 mm) wide. Eighteen near surface mounted CFRP techniques, the simply supported span
Using a concrete saw, grooves approx strips, 1 in. wide and 0.055 in. thick and one cantilever of Slab S3 were
imately 0.2 in. wide and 1 in. deep (5 (25 x 1.4 mm), spaced by 2.6 in. (66 both strengthened using externally
x 25 mm) were cut at the tension sur mm) on center were used to achieve a bonded CFRP sheets. The sheets were
face of the second cantilever. 30 percent increase in the ultimate ca manufactured by Master Builders
The grooves were injected with the pacity of the simply supported slab. Technologies, Ltd., Ohio. The re
epoxy adhesive to provide the neces En-Force CFL was used in bonding quired area of CFRP sheets was calcu
sary bond with the surrounding con both near surface mounted and exter lated to achieve a 30 percent increase
crete as shown in Fig. 6a. The strips nally bonded CFRP strips to the con in the flexural capacity of the can
were then placed in the grooves and crete. The epoxy was produced by tilever slab.
completely covered with the epoxy as Structural Composites, Inc., United For the first cantilever, the sheets
shown in Fig. 6b. States. were applied in two plies. The first ply
80 PCI JOURNAL
covered the entire width of the slab
while the second ply covered 19 in.
(480 mm) and was centered along the
width of the slab. Installation proce
dures are illustrated in Fig. 7. The
sheets had a modulus of elasticity of
33,000 ksi (228 GPa) and an ultimate
tensile strength of 620 ksi (4275 MPa)
as reported by the manufacturer.
The second cantilever was strength
ened using eight near surface mounted
C-BAR CFRP bars. The bars were
manufactured by Marshall Industries
Composites Inc., United States. Based
on testing, the bars had a modulus of
elasticity of 16,100 ksi (111 GPa) and
an ultimate tensile strength of 280 ksi
(1918 MPa). The bars were sand-
blasted to enhance their bond to the
epoxy adhesive. The bars were then
inserted inside grooves cut at the top
surface of the concrete. The grooves
were 6 in. (150 mm) apart. The groove
dimensions were 0.6 in. wide and 1.2
in. deep (16 x 30 mm).
The simply supported span was
strengthened with externally bonded
CFRP sheets after injecting the cracks
resulting from cantilever tests. Three
plies of CFRP sheets were used to
achieve a 30 percent increase in flexu
ral capacity. The first two plies cov
ered the entire width of the slab, while
the third ply covered 16 in. (400 mm)
and was centered along the width of
the slab. Detailed information about
the tested specimens is provided in
Table I. The designation of the tested
specimens are C or SS for cantilever
or simply supported specimens, re
spectively.
TESTING SCHEME
The slabs were tested under static
loading conditions using a uniform
line-load acting on a width equivalent Fig. 7. Installation procedures for externally bonded CFRP sheets.
to the width of a tire contact patch ac
cording to the AASHTO HSS3O de
sign vehicle. A closed-loop MTS 1200 Table 1. Details of test specimens.
kip (5000 kN) testing machine was Slab No. -
j Specimen Strengthening technique
—
January-February 2002 81
Notes
I 27’—lO’ I
1 ft0.3048m
1 in.25.4mm
Fig. 8a. Schematic of test setup for cantilever specimens.
82 PCI JOURNAL
I I I
Notes: MTS
(I) Elastomeric bearings 16”x16”xO. 16”
January-February 2002 83
strips showed the highest increase in
160 strength, 43 percent. Using the same
I kip = 4.448 kN
un. =25.4mm area of CFRP strips as externally
140 C6
C4 bonded reinforcement increased the
C2 strength by only 11 percent due to the
120
premature peeling failure of the strips.
100 The delamination strain was 18 per
Cl cent less than the value recommended
Yielding of steel
80 by ACT Committee 440F, 2001, which
reinforcement
is equal to 0.66 percent (0.5 times the
0 60
rupture strain) without consideration
40 of the reduction factor.
8 Using exter
nally bonded CFRP sheets provided
20 superior strength above all the tech
niques considered in this study and in
0
creased the strength by 44 percent.
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 The premature failure of Specimen
Cantilever deflection (in) C3 is believed to be due to the large
thickness of the externally bonded
Fig. 10. Load-deflection behavior of cantilever specimens strengthened with near
surface mounted CFRP reinforcement.
strips, which is four times the thick
ness of the externally bonded sheets
used for Specimen CS. No delamina
until crushing of concrete occurred. control specimen exhibited plastic tion was observed in Specimen C5
The observed mode of failure for all failure with concrete failing in com throughout the test. It should be noted
other cantilever specimens was due to pression and steel yielding. that near surface mounted strips have
crushing of the concrete in the com The failure load of the control speci double the bond area compared to ex
pression zone at the face of the sup men was 107 kips (476 kN). Strength ternally bonded strips.
port. At the onset of failure, the bot ening the specimen using near surface Typical failure due to crushing of
tom steel bars and the steel stirrups mounted Leadline bars increased the concrete is shown in Fig. 13. The ap
were exposed, followed by buckling strength by 36 percent in comparison plied load versus crack width relation
of the bottom steel bars. Experimental to the design value of 30 percent. ships for the cantilever specimens
results for the cantilever specimens are Using C-BAR CFRP bars instead of strengthened with near surface
summarized in Table 2. Leadline bars increased the strength mounted CFRP strips, C4, and exter
In general, the CFRP-strengthened by 39 percent. nally bonded CFRP sheets, CS, are
cantilever specimens showed consid The cantilever specimen strength shown in Fig. 14, compared to the
erable enhancement of strength. The ened with near surface mounted CFRP control specimen. In general, these
two techniques have proved their su
perior efficiency and decreased the
crack width by 50 to 70 percent com
pared to the control specimen.
The Japan Society of Civil Engi
neers, 1997, The Canadian Highways
Bridge Design Code, 1996,10 and ACT
Committee 440F, 2001,8 set the maxi
mum allowable crack width to 0.020
in. (0.5 mm) for exterior exposure
when FRP reinforcement is used.
Using a maximum allowable crack
width of 0.02 in. (0.5 mm), Fig. 14
shows that Specimens C4 and CS can
sustain a service load level of 92 kips
(410 kN), which is three times the
AASHTO HSS3O truck design load.
84 PCI JOURNAL
Fig. 12. Initial cracking in concrete substrate of Specimen C3 at 90 kips (400 kN).
shown in Fig. 15. To investigate dif Table 2. Experimental results of cantilever specimens.
ferent strengthening techniques, it was Percent
decided not to test a control specimen P,. .
P increase in
for the midspan and to rely on the re Specimen Strengthening technique (pL (in.) (kips) (in.) j capacity
suits obtained from nonlinear finite el Cl
C2
N.A. (control)
Near surface mounted Leadline bars
40.5 0.36 107 3.64 L —
* Specimen
slightly increased the cracking load. C3 failed due to delamination of CFRP strips, followed by crushing of concrete.
= cracking load
However, this behavior is also influ = ultimate load
enced by the value of the tensile = deflection at cracking
strength used in the analysis in com = deflection at failure
Fig. 13. Overview and closeup of typical failure due to crushing of concrete for cantilever specimens.
January-February 2002 85
COST ANALYSIS
One of the prime objectives of this
investigation was to provide a cost-ef
fective analysis for each strengthening
technique considered in this study. It
should be mentioned that all techniques
were designed to increase the strength
by 30 percent using the characteristics
of each FRP material. An approximate
0
cost for each strengthening technique
used for the cantilever specimens is
given in Table 4. The total construction
cost accounts for the cost of materials,
equipment, and labor.
The percentage increase in the flexu
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 ral capacity and the construction cost
Maximum crack width (in) for each of the strengthening tech
niques considered in this study for the
Fig. 14. Load versus crack width for cantilever specimens. cantilever specimens are shown in Fig.
17a. The figure indicates that using
near surface mounted CFRP strips and
spectively, showed comparable stiff Fig. 16. The unstrengthened slab ex externally bonded CFRP sheets pro
nesses up to failure. hibited classical failure due to crush vided the maximum increase in
After yielding of the tension steel ing of the concrete at a load level of strength. The construction cost of ex
reinforcement at a load level of 148 167 kips (741 kN). Experimental re ternally bonded CFRP sheets was only
kips (660 kN), the stiffnesses of Spec sults of simply supported specimens 25 percent in comparison to near sur
imens SS1 and SS2 were three times are given in Table 3. face mounted strips. Using either near
higher than that of the unstrengthened Strengthening the slab using near surface mounted Leadline bars or C-
slab. Using externally bonded CFRP surface mounted Leadline bars in BAR CFRP bars provided approxi
sheets in Specimen SS3 increased the creased the strength by 34 percent in mately the same increase in ultimate
stiffness by an extra 25 percent. comparison to the design value of 30 load carrying capacity.
Traditional flexural failure due to percent. Using near surface mounted With respect to cost, strengthening
crushing of the concrete at the CFRP strips instead of Leadline bars using C-BAR CFRP bars was 50 per
midspan section was observed for all increased the strength by 38 percent. cent less. Using an efficiency scale (E)
three specimens. Typical crack pattern Using externally bonded CFRP sheets defined by Eq. (1), the efficiency of
development for the strengthened sim provided the highest increase in each technique was evaluated as shown
ply supported specimens is shown in strength by 50 percent. in Fig. 17b:
86 PCI JOURNAL
tensioned bridge slabs strengthened
with FRP. The analytical prediction is
compared to the experimental results.
Up-to-date but very limited informa
tion has been reported on the use of
nonlinear finite element techniques to
simulate the overall behavior of pre
stressed concrete members strength
ened with FRP. Some analyses are re-
ported on the normal and shear stress
distributions at the end zones of the
FRP strip/sheet.
The finite element modeling de
scribed in this paper was conducted
using the program ANACAP (Version
2.1). ANACAP is known for its ad 1ft0.3048m
vanced nonlinear capabilities of the in. = 25.4 mm
Concrete block Concrete blOCk”N
concrete material model. 12 The
Specimen SSI
ANACAP software employs the clas
sical incremental theory of plasticity Fig. 16. Typical crack pattern development for strengthened simply supported
that relates the increment of plastic specimens.
strain to the state of stresses and stress
increment.
Formulation of the yield surfaces, Interfacial failures are not consid the symmetry of the cantilever slab,
loading, and failure surfaces take into ered in ANACAP. Consequently, only one-half of the slab in the longi
account the effect of confinement on peeling failures cannot be predicted tudinal direction was modeled. The
the concrete behavior. The concrete and the analysis will be limited to fail concrete was modeled using 20-node
material is modeled by the smeared ures due to crushing of the concrete or isoparametric brick elements with a
cracking methodology in which pro rupture of the FRP reinforcement. The 2 x 2 x 2 reduced Gauss integration
gressive cracking is assumed to be dis analysis is conducted using an incre scheme. Each node has three transla
tributed over an entire element.’
3 Over mental-iterative solution procedure, in tional degrees of freedom. The slab
the past 35 years, the distributed which the load is incrementally in was supported on elastic springs hav
smeared crack model has been used creased. Within each increment, equi ing the same stiffness of the neoprene
for plane stress, plane strain and three- librium is iteratively achieved. pads used in the test program.
dimensional solid systems.
5
”
14 Iteration is repeated until internal The load was applied as a uniform
Cracks are assumed to form perpen equilibrium conditions are sufficiently pressure acting on an area of 9 x 24 in.
dicular to the principal tensile strain fulfilled and convergence is obtained. (228 x 610 mm). The load was applied
direction in which the cracking crite At the end of each step, the ANACAP gradually using a step-by-step analy
rion is exceeded. When cracking oc program adjusts the stiffness matrix to sis. The number of load steps and step
curs, the stress normal to the crack di reflect the nonlinear changes in the size were chosen based on the experi
rection is reduced to zero, which stiffness. Verification of the ence gained through different analyti
results in redistribution of stresses ANACAP program using independent cal simulations conducted on bridge
around the crack. The ability of experimental results can be found deck slabs. The influence of the step
cracked concrete to share the tensile ’ 17
6
elsewhere.’ size at failure is performed and re
forces with the steel/FRP reinforce ported elsewhere.’
8
ment between cracks is modeled in Three analytical simulations were
Modeling of the Cantilever Slab carried out by varying the size of the
ANACAP by means of the tension
softening model. The descending The cantilever slab and adjacent elements at the anticipated failure
branch of the tensile stress-strain panel were modeled to account for the zone and the number of layers within
curve is assumed to follow an expo continuity effect. Taking advantage of the slab thickness. The number of ele
nential function. Cracks are allowed to
form in the three principal directions. Table 3. Experimental results of simply supported specimens.
The program also accounts for the Percent
reduction in shear stiffness due to ‘.,r 4r P, 4 increase in
Specimen Strengthening technique (kips) (in.) (kips) (in.) capacity*
cracking and further decay as the crack
SS 1 Near surface mounted Leadline bars 79 0.26 223 2.5 34
2 The reinforcement is assumed
opens.’
SS2 Near surface mounted CFRP strips 83 0.26 230 2.4 38
to be distributed throughout the con SS3 Externally bonded CFRP sheets 81 0.27 251 2.6 50
crete element. Full bond is assumed be Note: 1 kip = 4.448 kN; 1 in. = 25.4 mm.
tween the reinforcement and concrete. * Ultimate load
of unstrengthened specimen was based on nonlinear finite element analysis.
January-February 2002 87
Table 4. Cost analysis for cantilever specimens.
Strengthening Material Total Epoxy Labor Equipment Total
Specimen technique cost per ft material cost cost hours* cost cost
C2 Near surface mounted 12.6 1058 150 7 67 1394
Leadline bars
C3 Externally bonded 17.0 1224 Includedt 5 None 1309
CFRPstris - - -
88 PCI JOURNAL
Element size=4”x5.9 “x5.33”
MESH I
(324 elements)
Elevation
Plan
MESH 2
(435 elements)
Elevation
Plan
ift 0.3048m
1 m25.4mm
Plan
January-February 2002 89
cantilever and simply supported
160 specimens. A comparison between
analytical and experimental results is
140 presented.
120
Cantilever Specimens
Cl) 100 To validate the finite element model,
the unstrengthened cantilever was
modeled first. Predicted load-deflec
C
tion curves were compared to the ex
perimental results as shown in Fig. 20.
The predicted load-deflection behavior
using the finite element analysis com
pared very well with the measured val
ues. The predicted failure load using
the finite element analysis underesti
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 mated the measured value by 7 per
Cantilever deflection (in) cent. Failure was due to crushing of the
concrete at the face of the support.
Fig. 19. Influence of mesh size on load-deflection behavior. The second stage of the model de
velopment involved the addition of
CFRP reinforcement. Six /8 in. (10
only one-quarter of the slab was mod slab was supported on spring elements mm) diameter Leadline bars were
eled using 20-node brick elements. To in the vertical direction to simulate the added to model the behavior of Speci
focus on the slab behavior and to re neoprene pads. The load was applied men C2, which was strengthened with
main within a realistic computer exe as a uniform pressure acting on an near surface mounted Leadline bars.
cution time, the cantilevers were not area of 4.5 x 24 in. (114 x 609 mm). The epoxy was not modeled in the
included in the model since they are The load was applied gradually using analysis as no slip between the epoxy
not loaded. The specimen was dis a step-by-step analysis. and the bars was observed during the
cretized into 255 elements. test. The CFRP bars were considered
The element size at the anticipated to be bonded to the concrete.
failure zone was set to 3 x 4.72 x 5.33
RESULTS OF THE
NUMERICAL ANALYSIS The predicted load-deflection be
in. (76 x 120 x 135 mm), the same di havior is shown in Fig. 21. Compared
mensions that were previously de This section discusses the results to the test results, the flexural stiffness
scribed in the cantilever model. The of the finite element analysis for both of the cantilever slab was simulated
with a very high accuracy using the fi
nite element analysis. The predicted
failure load using the finite element
analysis underestimated the measured
value by 6 percent.
Specimens Cl and C2 were ana
lyzed also using a strain compatibility
approach to predict the flexural behav
ior up to failure. The concrete is as
sumed to be subjected to uniform uni
axial strains over the entire width of
the slab. Strains were assumed to vary
linearly over the depth of the section.
The stress-strain relationship of the
concrete was modeled using a
parabolic relationship in compression.
The internal compression force in the
concrete was evaluated using the
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 stress-block parameters introduced by
Cantilever deflection (in) Collins and Mitchell in 1991.’
The stress-strain behavior of CFRP
Fig. 20. Comparison of predicted load-deflection behavior with laboratory results reinforcement was assumed to be lin
(Specimen Cl). early elastic up to failure. The deflec
90 PCI JOURNAL
tion was calculated by integrating the
curvature at each load increment. Pre
dicted loads and deflections at crack
ing and at failure are given in Table 5.
The predicted failure loads using
strain compatibility approach underes
timated the measured values for Speci
mens Cl and C2 by 6 and 10 percent,
respectively. Predicting the deflection
values using strain compatibility ap -g
proach underestimated also the initial 0
stiffness of the slabs by 13 percent as
given in Table 5.
cracking load, ultimate load and flexu CI Finite element 45.0 0.37 100 3.3 0.93
ral stiffness after cracking of the con Strain compatibility 46 0.47 101 2.0 0.94
Experimental 42.5 0.33 145.5 4.02
crete. Failure was due to crushing of
—
CONCWSIONS
Based on the findings of this inves
n
tigation, the following conclusions can
be drawn:
1. The use of near surface mounted I0
CFRP reinforcement is feasible and
cost effective for strengthening or re
pairing prestressed concrete girders
and slabs.
2. Both the stiffness and strength of
concrete slabs strengthened with
CFRP materials were substantially in
creased. The ultimate load carrying 0 0.5 1 1.5 2 2.5 3
capacity of the slabs can be increased Mid-span deflection (in)
by as much as 50 percent.
3. The magnitude of strength in Fig. 22. Comparison of predicted load-deflection behavior with laboratory results
crease was influenced by the type and (Specimen SS1).
January-February 2002 91
configuration of the CFRP materials. 70 percent compared to the un behavior. Analytical models describing
In general, near surface mounted CFRP strengthened specimen. the load transfer mechanism of near
strips and externally bonded CFRP 9. The predicted results using non surface mounted FRP reinforcement to
sheets provided superior strength in linear finite element analysis were in concrete are urgently needed.
crease for both cantilever and simply excellent agreement with the experi Work is currently under way by the
supported specimens. The overall cost mental results. The error is less than authors to provide complete design
of strengthening using CFRP sheets is 10 percent. guidelines regarding the development
only 25 percent of that using near sur 10. Test results indicated full com length needed for the proposed FRP
face mounted CFRP strips. posite action between the near surface strengthening techniques; these will be
4. Strengthening using either near mounted CFRP reinforcement and the reported in a future paper. The authors
surface mounted Leadline bars or C- concrete and no slip occurred through recommend also that future research
BAR CFRP bars provided approxi out the tests. be focused on examining the durabil
mately the same increase in strength. ity aspects of various FRP strengthen
With respect to construction cost, ing systems under severe environmen
RECOMMENDATIONS AND
strengthening using C-BAR CFRP tal conditions.
bars is considerably less. FUTURE RESEARCH
5. Strengthening using externally Test results of the experimental
bonded CFRP strips provided the least program and predicted values using ACKNOWLEDGMENTS
increase in strength by 11 percent due numerical modeling provided suffi The authors wish to acknowledge
to peeling of the strips from the con cient evidence and confidence of the the support of the Network of Centres
crete surface. Using the same amount proposed strengthening technique of Excellence, ISIS Canada, program
of strips but as near surface mounted using near surface mounting as a new of the Government of Canada and the
reinforcement enhanced the ultimate and promising technology. Delamina Natural Science and Engineering Re
load carrying capacity by 43 percent. tion-type failures, occasionally ob search Council. The writers gratefully
Groove dimensions of 0.2 in. wide by served by using externally bonded re acknowledge the support provided by
1 in. deep (5 x 25 mm) were adequate inforcement, can be precluded using Mitsubishi Chemical Corporation,
to prevent splitting of the epoxy cover. this technique. Japan, Marshall Industries Composites
6. Strengthening using externally Epoxy adhesives commonly used for Ltd., United States, S&P Clever Rein
bonded CFRP sheets is the most effi bonding steel bars have proved to be forcement Company, Switzerland, and
cient technique in terms of strength effective in bonding CFRP bars. How Master Builders Technologies Ltd.,
improvement and construction cost. ever, characterizing the bond perfor United States, for providing the mate
7. Delamination of the CFRP strips mance of the adhesives is compulsory rials used in the test program.
occurred at a strain of 0,54 percent, prior to any application. It is recom The authors would like also to ac
which is equivalent to 41 percent of mended to use the groove dimensions knowledge the support provided by
the rupture strain of the strips as re outlined in this paper for near surface Vector Construction Ltd., Winnipeg,
ported by the manufacturer. The de mounted bars and strips for strengthen Canada, for performing all the
lamination strain is 18 percent less ing reinforced and prestressed concrete strengthening work. Special thanks are
than the value recommended by ACT structures. owed to M. McVey for his assistance
Committee 440F. Additional research is needed to du during the fabrication and testing of
8. Using near surface mounted plicate the findings of this research the specimens. Finally, the authors
CFRP strips or externally bonded program and to determine the effect of want to thank the PCI JOURNAL re
CFRP sheets for flexural strengthen different parameters, such as fatigue viewers for their thoughtful and con
ing reduced the crack width by 50 to loading and temperature, on the overall structive comments.
92 PCI JOURNAL
REFERENCES
1 U.S. Department of Transportation (DOT), Bureau of Trans 10. Canadian Standards Association, Canadian Highways Bridge
portation Statistics, Transportation Statistics Annual Report, Design Code, Section 16, Fiber Reinforced Structures, Ottawa,
Washington DC, 1997, 286 pp. Ontario, 1996, 28 pp.
2. Tann, D. B., and Delpark, R., “Experimental Investigation of 11. Hassan, T., Horeczy, G., Svecova, D., Rizkalla, S., Shehata,
Concrete Beams Reinforced with Narrow Carbon Strips,” Pro E, and Stewart, D., “Flexural Strengthening of Post-Tensioned
ceedings of the International Conference on Structural Faults Bridge Slab Using FRP,” Proceedings of the International
and Repair, CD-ROM, 1999. Conference on Advanced Composite Materials for Bridges and
3. Corry, R., and Dolan, C. W., “Strengthening and Repair of a Structures (ACMBS-III), Ottawa, Ontario, 2000, pp. 291-298.
Column Bracket Using Carbon Fibre Reinforced Polymer 12. James, R. G., ANA CAP Concrete Analysis Program Theory
(CFRP) Fabric,” PCI JOURNAL, V. 46, No. 1, January-Febru Manual, Version 2.1, Anatech Corp., San Diego, CA, 1997.
ary 2001, pp. 54-63. 13. Rashid, Y. R., “Analysis of Prestressed Concrete Pressure Ves
4. Burke, C. R., and Dolan, C. W., “Flexural Design of Pre sels,” Nuclear Engineering Design, V. 7, No. 4, 1968, pp. 334-
stressed Concrete Beams Using FRP Tendons,” PCI JOUR 344.
NAL, V. 46, No. 2, March-April 2001, pp. 76-87. 14. Scordelis, C. A., “Past, Present and Future Development,”
5. AASHTO, Standard Specifications for Highway Bridges, Seminar on Finite Element Analysis of Reinforced Concrete
American Association for State Highway and Transportation Structures, Japan Concrete Institute, V. 1, 1985, pp. 203-2 12.
Officials, Washington, DC, 1998. 15. Gerstle, K. H., “Material Modeling of Reinforced Concrete,”
6. Integrated Finite Element Analysis and Design of Structures, TAB SE Colloquium on Advanced Mechanics of Reinforced
SAP2000 Graphic User Inteiface Manual, Version 7.0, Com Concrete, Introductory Report, Delft, Netherlands, 1981.
puter and Structures Incorporation, Berkeley, CA, 1998. 16. Hassan, T., Abdelrahman, A., Tadros, G., and Rizkalla, S.,
7. Blaschko, M., and Zilch, K., “Rehabilitation of Concrete “FRP Reinforcing Bars for Bridge Decks,” Canadian Journal
Structures with Strips Glued Into Slits,” Proceedings of the of Civil Engineering, V. 27, No. 5, 2000, pp. 839-849.
12th International Conference on Composite Materials, Paris, 17. Mufti, A., Hassan, T., Memon, A., and Tadros, G., “Analytical
France, CD-ROM, 1999. Study of Punching Shear Strength of Restrained Concrete
8. ACT Committee 440F, “Guide for the Design and Construction Slabs,” Proceedings of the Canadian Society of Civil Engi
of Externally Bonded FRP Systems for Strengthening Con neering Annual Conference (CSCE), Victoria, British
crete Structures,” Draft Report, American Concrete Institute, Columbia, CD-ROM, 2001.
Farmington Hills, MI, October 2001, 150 pp. 18. Hassan, T., “Behavior of Concrete Bridge Decks Reinforced
9. Japan Society of Civil Engineers (JSCE), 1997b, “Recommen With FRP,” M.Sc. Thesis, University of Manitoba, Canada,
dations for Design and Construction of Concrete Structures 1999, 226 pp.
Using Continuous Fiber Reinforcing Materials,” Concrete En 19. Collins, M., and Mitchell, D., Prestressed Concrete Structures,
gineering Series, No. 23, Tokyo, Japan, 1997, 325 pp. Prentice Hall, Englewood Cliffs, NJ, 1991, 766 pp.
January-February 2002 93